Plan Review Details - Permit 99080714
Plan Review Stops For Permit 99080714
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-11-19 Cont ID  
Sent By bstaples Date 1999-08-31 Time 09:32 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001. HEALTH DEPARTMENT TO APPROVE PLANS.
 2. ENGINEER TO PROVIDE INFORMATION ON
 GLAZING SYSTEM. AS PER NOTE ON PLAN.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-28 Cont ID  
Sent By dpalmer Date 1999-10-28 Time 07:06 Rev Time 0.00
Received By dpalmer Date 1999-10-28 Time 07:05 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO****************
  
 1)NOTE:EXISTING RISER DIAGRAM SHOWS
 3 PHASE EQUIPMENT AND ONLY SINGLE PHASE
 WIRING.???? FROM MAIN TO PANEL.
 2)NOTE:IF PVC CONDUIT IS USED IN FEEDING
 FROM PANEL "A" TO PANEL "B" THEN SIZE
 EQUIPMENT GROUND SHALL BE SIZED FROM
 TABLE:250-95
 3)NOTE:RISER DIAGRAM SHOWS PANEL"B" AS
 BEING INSTALLED AS NEW ? BUT PANEL
 SCHEDULE SHOWS AS BEING EXISTING??
 IF PANEL "B" IS NEW THEN PROVIDE AIC
 RATING OF BRANCH BREAKERS.AS PER ARTS:
 215-5/110-9
  
 ALL THE ABOVE INFORMATION NEEDS TO BE
 SUBMITTED FOR REVIEW AND APPROVAL BEFORE
 FIRST ROUGH ELECTRICAL INSPECTION IS
 CALLED IN.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-08-31 Cont ID  
Sent By bstaples Date 1999-08-31 Time 09:33 Rev Time 0.50
Received By bstaples Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-11-17 Cont ID  
Sent By ndenmark Date 1999-11-17 Time 07:11 Rev Time 0.33
Received By ndenmark Date 1999-11-17 Time 07:11 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 ALL PRIOR MECH WORK TO BE INSPECTED
 UNDER REISSUED MECH PERMITS
 SEPARATE MECHANICAL PERMITS REQUIRED FOR
 WALK IN COOLER AND HOOD AND SUPPRESSION
 SYSTEM, SUBMIT PLANS WITH MECH PERMIT
 APPLICATION

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-11-06 Cont ID  
Sent By tlarge Date 1999-11-06 Time 08:52 Rev Time 0.65
Received By tlarge Date 1999-11-06 Time 08:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-08-30 Cont ID  
Sent By tlarge Date 1999-08-30 Time 09:15 Rev Time 1.25
Received By pschmitz Date 1999-08-30 Time 07:51 Sent To  
Notes
2001-01-08 00:00:00PLANS SHALL BE REVIEWED BY DEPT.OF
 BUSINESS REG.PRIOR TO REVIEW BY THIS
 DEPT.SPC SEC.101.4.7.
  
 SUBMIT MANUF.SHEETS FOR ALL GAS EQUIP.
 STD.GAS CODE SEC.402.1.
  
 SIZE ALL SECTIONS OF THE GAS RISER AND
 SHOW ALL CUT LENGTHS OF PIPE.STD.GAS
 CODE SEC.302,305.4
  
 INDICATE GAS SUPPLY PRESSURE ON PLANS
 PER STD.GAS CODE SEC.305.2.
  
 SUPPLY COMBUSTION AIR CALCULATIONS FOR
 ALL GAS EQUIPMENT.STD.GAS CODE SEC.402.4
  
 SIZE ALL INDIRECT WASTE LINES ON THE
 RISER.COMPLY W/SPC SEC.713.3,TABLE 713.2
  
 SHT.A-3.NOTE #11-"M" COPPER IS NOT
 PERMITTED FOR U/G USE PER COUNTYWIDE
 AMENDMENTS TO STD.PLBG.CODE SEC.611.3.
  
 PLANS SHALL BE SIGNED AND SEALED PER
 SPC SEC.104.2.3.
  
 SUBMIT SANITARY RISER FOR ANY PLBG.
 CHANGES TO THE RESTROOM.SPC 104.2.1.
  
 RESUBMIT 10-13-99 DENIED SEPERATE PREMIT
 FOR PLUMBING SEE NOTES ON SHT A-3
 END OF COMMENTS PES