Plan Review Details - Permit 99080692
Plan Review Stops For Permit 99080692
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 1999-09-20 Cont ID  
Sent By hpiskura Date 1999-09-20 Time 15:52 Rev Time 6.50
Received By hpiskura Date   Time   Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2000-02-09 Cont ID  
Sent By dlauderm Date 2000-02-09 Time 13:02 Rev Time 1.00
Received By dlauderm Date 2000-02-09 Time 13:01 Sent To  
Notes
2001-01-08 00:00:00PASSED WITH PROVISO:
 SANITATION:
 NO DUMPSTER LOCATION SHOWN.
 IF GARBAGE IS TO BE PICKED UP BY CITY OR
 IF IT IS PRIVATE PICKUP, IF TO BE PICKED
 UP BY THE CITY THEN THE FOLLOWING
 REQUIREMENTS MUST BE MET:
  
 1.DUMPSTER MUST HAVE A MINIMUM OF 12'-6"
 OPENING BETWEEN THE GATE POSTS.
  
 2.INTERIOR DIMENSIONS OF THE ENCLOSURE
 MUST BE A MINIMUM OF 12'-6" WIDE AND 12'
 DEEP.A CONCRETE PARKING STOP BARS 10'
 LONG MUST BE CENTERED (FROM GATES) AND
 INSTALLED 18" FROM THE BACK WALL.STEEL
 BARS WILL BE DRILLED THRU THE STOP BAR
 AND INTO THE INTERIOR FLOOR OF THE
 ENCLOSURE TO STOP THE STOP BAR FROM
 MOVING WHEN THE DUMPSTER IS SET INSIDE.
  
 3.THE OPENING OF THE DUMPSTER ENCLOSURE
 MUST BE ANGLED SO THAT A 40' LONG TRUCK
 WITH THE FORKS EXTENDED CAN APPROACH THE
 OPENING AND PICK UP THE DUMPSTER WITHOUT
 MAKING A SHARP TURN.
  
 4.THE TRUCK NEEDS TO HAVE NO LESS THAN A
 16' HIGH VERTICAL CLEARANCE AREA FOR THE
 TRUCK TO PICK UP THE DUMPSTER. THE CLEAR
 AREA MUST OVER THE DUMPSTER AND WHERE
 THE TRUCK WILL BE STOPPED TO UNLOAD THE
 DUMPSTER.
  
 5.THE TRUCK NEEDS TO HAVE NO LESS THAN
 14' HIGH VERTICAL CLEARANCE AND 12'
 HORIZONTAL CLEARANCES FOR THE TRUCK TO
 DRIVE THROUGH.
  
 6.IT IS STRONGLY SUGGESTED THAT YOU ADD
 A RECYCLING CENTER TO YOUR DUMPSTER
 ENCLOSURE.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 1999-09-20 Cont ID  
Sent By hpiskura Date 1999-09-20 Time 15:54 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00FAIL STORM & TRASH

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-09-20 Cont ID  
Sent By hpiskura Date 1999-09-20 Time 15:54 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 1999-12-27 Cont ID  
Sent By ndenmark Date 1999-12-27 Time 07:19 Rev Time 0.25
Received By ndenmark Date 1999-12-27 Time 07:19 Sent To  
Notes
2001-01-08 00:00:00DENIED
 PRIOR ISSUES HAVE NOT BEEN ADDRESSED ON
 THIS REVISION SEE PREVIOUS COMMENTS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 1999-09-08 Cont ID  
Sent By ndenmark Date 1999-09-08 Time 10:32 Rev Time 0.33
Received By ndenmark Date 1999-09-08 Time 10:32 Sent To  
Notes
2001-01-08 00:00:00DENIED
 1) PROVIDE OUTSIDE AIR INFORMATION PER
 ASHRAE 62-89
 2) FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED BY 1997 SMC 406.1
 PROVIDE INFORMATION AND SHALL BE TIED TO
 BUILDING FIRE ALARM OR HORN AND STROBE
 FOR NOTIFICATION PER NFPA 4-4.4.3

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-01-08 Cont ID  
Sent By tlarge Date 2000-01-08 Time 06:15 Rev Time 1.25
Received By tlarge Date 2000-01-08 Time 06:15 Sent To  
Notes
2001-01-08 00:00:00NOT ONE PREVIOUS PLUMBING COMMENT HAS
 BEEN ADDRESSED.CORRECT ALL CODE
 CODE VIOLATIONS ON THE PLANS PRIOR TO
 RESUBMITTAL.
 COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.,104.2.2.,104.3.1.

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-09-08 Cont ID  
Sent By tlarge Date 1999-09-08 Time 15:49 Rev Time 1.50
Received By tlarge Date 1999-09-08 Time 15:48 Sent To  
Notes
2001-01-08 00:00:00CLEARLY SHOW WHEELCHAIR TURNING SPACE
 IN ACCESSIBLE TOILET ROOMS PER FACBC SEC
 4.2.3 AND FIGURES 3A OR 3B.
  
 SINK IN BREAKROOM SHALL BE HANDICAP
 ACCESSIBLE PER FACBC SEC.4.24.1-4.24.7
  
 SUBMIT DETAILS /ELEVATIONS FOR ALL
 HANDICAP ACCESSIBLE FIXTURES.
 COMPLY W/FACBC.SHOW FIXTURE CLEARANCES.
  
 DOOR IN MEN'S TOILET ROOM CANNOT SWING
 INTO CLEAR FLOOR SPACE FOR THE WATER
 CLOSET PER FACBC SEC.4.22.2.
  
 SUBMIT OCCUPANT LOAD PER TABLE 407 OF
 SPC.
  
 SUBMIT DETAILS ON TYPE OF OPERATIONS
 CONDUCTED IN WAREHOUSE.AN EMERGENCY
 SHOWER MAY BE REQD.PER SPC TABLE 407.
  
 SUBMIT A WATER RISER FOR REVIEW THAT
 CLEARLY REFLECTS THE SCOPE OF WORK BEING
 PERFORMED.SPC 104.2.1.
  
 SUBMIT DETAILS ON THE SUMP,DRAIN AND
 PUMPS IN THE TRUCKWELL AREA.SPC 104.2.1.
  
 INSTALLATION OF FIXTURES ON COMMON
 HORIZONTAL BRANCH SHAALL COMPLY W/SPC
 SEC.913.1.1,913.1.2.
  
 WET VENTS SHALL RECEIVE THE DISCHARGE
 OF FIXTURE DRAINS ONLY PER COUNTYWIDE
 AMENDMENTS SEC.911.1.1(MENS TOILET)
  
 DRINKING FOUNTAIN SHALL BE HANDICAP
 ACCESSIBLE AND COMPLY W/FACBC SEC.4.1.3
 (10)(A).
  
 URINAL SHALL BE HANDICAP AND COMPLY W/
 FACBC SEC.4.18.

Review Stop Z ZONING
Rev No 1 Status F Date 1999-09-23 Cont ID  
Sent By hpiskura Date 1999-09-20 Time 15:53 Rev Time 0.75
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEEDS LEVEL I SITE PLAN REVIEW