Plan Review Details - Permit 99080634
Plan Review Stops For Permit 99080634
Review Stop E ELECTRICAL
Rev No 2 Status F Date 1999-12-06 Cont ID  
Sent By dpalmer Date 1999-12-06 Time 09:00 Rev Time 0.00
Received By dpalmer Date 1999-12-06 Time 09:00 Sent To  
Notes
2001-01-08 00:00:00SAME NOTES AS FIRST REVIEW MINUS A COUPL

Review Stop E ELECTRICAL
Rev No 1 Status F Date 1999-09-08 Cont ID  
Sent By dpalmer Date 1999-09-08 Time 11:18 Rev Time 0.00
Received By dpalmer Date 1999-09-08 Time 11:18 Sent To P
Notes
2001-01-08 00:00:00**************DENIED*******************
  
 1)NOTE:SHOW COMPLETE RISER DIAGRAM.
 TO INCLUDE ALL OF THE FOLLOWING:
 GROUNDING ELECTRODE CONDUCTOR TO GOT TO
 BLDG.STEEL ALSO 250-81
 )INCLUDE GARAGE DOOR OPENER IN LOAD
 CALCULATIONS AS IT REQ`S A DEDICATED
 CIRCUT.ALSO INCLUDE ON PANEL SCHED.
 )INCLUDE BATHROOMS ON PANEL SCHEDULE AS
 THEY ALSO REQ,DEDICATED CIRCUTS AS PER
 ART:210-52D
 )NOTE:GENERAL LIGHTING SHOWS 20AMP
 OVERCURRENT PROTECTION TO FEED #14 AWG.
 PLEASE MATCH AS PER 310-16
 )ONLY SHOW 15KW HEAT FIGURED IN THE LOAD
 CALCULATIONS,BUT SHOW OTHER HEAT STRIP
 AT 7.5 KW,,,,PLEASE FIGURE 7.5KW IN
 LOAD CALCULATIONS.
 2)NOTE:HOT WATER HEATER,DRYER,WASHER
 SHOWN TO BE ALL GFI,,,
 3)NOTE:AS PER 210-52G GFI RECEPT.REQ`D
 INSIDE GARAGE.
 4)NOTE:POWDERROOM IN FRONT OF HOUSE
 REQ`S GFI REC.AS PER 210-52D
 5)AS PER 1996 NFPA-72 2-2.1.1.1 REQ`S
 SMOKE DETECTORS INSIDE AND OUTSIDE
 BEDROOMS IN ALL NEW CONSTRUCTION HOMES.
 6)AS PER ART:210-52E GFI RECEPT.REQ`D
 FRONT OF DWELLING.
  
 7)PRINTS FROM WAUSAU HOMES SHOW FIRST
 FLOOR??? IF ADDITIONAL PANEL IS LOCATED
 IN SECOND FLOOR THEN IT MUST BE DRAWN
 ON RISER DIAGRAM ALSO.215-5
 PLEASE SUBMIT PLANS MARKED AS SECOND
 FLOOR ELECTRICAL PLANS.NOTE CODE FOR
 SMOKE DETECTORS LISTED ON THESE NOTES
 ABOVE.
 8)NOTE SUBMIT AIC RATING OF ALL EQUIP-
 -MENT AND BREAKERS BEING USED. AS PER
 ARTS:110-9 AND 215-5
  
 PLEASE SUBMIT ALL OF THE FOLLOWING.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 1999-11-13 Cont ID  
Sent By jleech Date 1999-11-13 Time 12:02 Rev Time 0.75
Received By jleech Date 1999-11-13 Time 12:01 Sent To  
Notes
2001-01-08 00:00:00DENIED;
 1.LIST CFMS FOR EACH DROP.
 2.A/C EQUIPMENT INFORMATION REQUIRED ON
 A/C DRAWING.
 1/2 BATH DOWN STAIRS REQUIRES EXHAUST
 FAN TO OUTSIDE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 1999-08-24 Cont ID  
Sent By jleech Date 1999-08-24 Time 10:10 Rev Time 1.00
Received By jleech Date 1999-08-24 Time 10:10 Sent To  
Notes
2001-01-08 00:00:001.A/C EQUIPMENT INFORMATION REQUIRED ON
 A/C DRAWINGS.
 2.SHOW CFMS FOR EACH DROP.
 3.1/2
 BATH DOWN STAIRS REQUIRES EXHAUST FAN
 TO OUTSIDE.
 4.SHOW DRYER VENT.
 5.SHOW RETURN AIR.

Review Stop P PLUMBING
Rev No 2 Status F Date 1999-11-05 Cont ID  
Sent By tlarge Date 1999-11-05 Time 06:45 Rev Time 0.50
Received By tlarge Date 1999-11-05 Time 06:45 Sent To  
Notes
2001-01-08 00:00:00LAUNDRY TRAY AND WASHING MACHINE ARE NOT
 PROPERLY VENTED PER SPC SEC.901.2.
  
 LAUNDRY TRAY NOT SHOWN ON FLOOR PLAN.
 SHOW LOCATION OF LAUNDRY TRAY PER CITY
 OF WPB AMENDMENTS TO SPC SEC.104.2.1.

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-09-08 Cont ID  
Sent By dpalmer Date 1999-09-08 Time 12:13 Rev Time 0.50
Received By tlarge Date 1999-09-08 Time 12:37 Sent To  
Notes
2001-01-08 00:00:00SUBMIT A SANITARY RISER DIAGRAM THAT
 COMPLIES W/THE SPC AND CORRELATES W/THE
 FLOOR PLAN.SPC 104.2.1.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 1999-09-30 Cont ID  
Sent By jcaloger Date 1999-09-30 Time 11:43 Rev Time 3.50
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-08-17 Cont ID  
Sent By gjoyce Date 1999-08-17 Time 09:51 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***