Plan Review Details - Permit 99080620
| Plan Review Stops For Permit 99080620 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
1999-09-01 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
1999-09-01 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
1999-09-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
1999-09-28 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
1999-09-28 |
Time |
14:36 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************UNSAT******************** | | | | | | 1)NOTE:COMPLETE INFORMATION REQ`EST ON | | | FIRST CORRECTION SHEET.YOU SHOW 80AMP | | | FEED TO PANEL"B" BUT SHOW PANEL "B" | | | WITH 88AMP LOAD.?????? | | | | | | THE ABOVE NEEDS TO BE TAKEN CARE OF | | | CORRECTED,SUBMITTED AND APPROVED BEFORE | | | FIRST ROUGH ELECTRICAL INSPECTION. | | | PANEL "B" 125 MAIN BRK PANEL SO IF WIRE | | | FEEDING PANEL IS INCREASED AND 80AMP | | | FUSES INCREASED THEN IT WILL MEET CODE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
1999-09-01 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
1999-09-01 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
1999-09-01 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
1999-09-01 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
1999-09-27 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-09-27 |
Time |
08:10 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
1999-09-27 |
Time |
08:10 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | REFRIGERANT LINES SHALL NOT BE INSTALLED | | | IN STAIRWELL PER 1997 SMC 304.3.2.3 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
1999-09-27 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-09-01 |
Time |
09:05 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
1999-09-01 |
Time |
09:05 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | OKAY 9/27/99 PREVIOUS DENIED | | | PROVIDE SCHEDULE OF DIFFUSERS TO BE USED | | | PROVIDE CFM VALUES AT EACH DIFFUSER | | | SPECS CALL FOR ALL NEW MATERIAL, PROVIDE | | | LEGEND FOR PLAN FOR REVIEW PURPOSES |
|
|
|