| Plan Review Stops For Permit 99080492 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-04-04 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-04-04 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO STRUCT CALCULATIONS REQ |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-01-07 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-01-07 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2000-01-05 |
Time |
09:39 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
1999-09-27 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
1999-09-27 |
Time |
14:42 |
Rev Time |
12.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-03-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-03-25 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-03-25 |
Time |
10:13 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************* PROVISO ***************** | | | | | | 1)NOTE: LOCAL CODE FOR OUTLET SPACING. | | | | | | 2)NOTE: MISSING OUTLET FOR MECH ROOM | | | ART 210-63 | | | | | | 3)NOTE:ALL BATH REC TO BE GFI 210-8-B | | | | | | 4)NOTE: ROOMS SHOWN AS STORAGE WITH | | | ELEC. PANELS?? SEE 240-24-D AND 384-7 | | | PLEASE CHECK YOUR LOACTIONS | | | | | | PLEASE SUBMIT THE REVISED SHEETS FOR | | | REVIEW BEFORE ROUGH ELECTRICAL IS CALLED | | | IN. IF THERE ARE ANY QUESTIONS PLEASE | | | CALL 659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
1999-12-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
1999-12-17 |
Time |
07:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *****************UNSAT***************** | | | | | | SAME AS ORIGINAL NOTES | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF ALL | | | EQUIPMENT!! TO INCLUDE PANELS. AS PER | | | ARTS:230-65/110-9/215-5 | | | | | | 2)NOTE: PLEASE CHECK GROUNDING ELECTRODE | | | CONDUCOTR SIZE AS PER TABLE 250-94 | | | EXCEPT. #2 SUM OF SERVICE CONDUCTORS. | | | | | | 3)NOTE: PLEASE SHOW BLDG.STEEL AS PART | | | OF THE GOUNDING SYSTEM AS PER 250-81/ | | | 215-5 | | | | | | PLANS WOULD HAVE PASSED AS PROVISO BUT | | | WERE COMING BACK TO YOU FOR PLUMB/MECH. | | | PLEASE DRAW UP NEW FULL SIZE E-4 FOR | | | LARGE SET WITH THE INFORMATION ABOVE | | | FOR REVIEW AND APPROVAL. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL 561-659-8096 | | | EXT.8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
1999-09-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
1999-09-29 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
1999-09-29 |
Time |
10:48 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************DENIED******************* | | | | | | 1)NEED TO SUBMIT AIC RATING OF ALL | | | EQUIPMENT,MAINS,DISC.`S FUSES,BRKRS. | | | AS PER ARTS;110-9/215-5 | | | 2)NEED TO SUBMIT GROUNDING SYSTEM. | | | TO INCLUDE GROUNDING ELECTRODE SYSTEM | | | WITH ALL POINTS OF ATTACHMENT.ALSO | | | INCLUDE WIRE SIZES FIGURED FROM ART;/ | | | TABLE 250-94/250-95 | | | 3)NEED LOAD CALCULATIONS FOR EACH PANEL | | | AND FOR MDP.AS PER ART; 215-5 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
1999-12-08 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
1999-09-27 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | AS PER99120274 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
1999-09-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
1999-09-29 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-04-05 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-04-05 |
Time |
07:17 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-04-05 |
Time |
07:17 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | 1) FIRE DAMPERS REQUIRED AT ALL DUCT | | | PENETRATIONS OF RATED WALLS. PROVIDE | | | SPECIFIC LOCATION AND INSTALLATION | | | DETAILS AS PER 1997 SMC 610.6 | | | 2) EXHAUST FAN NUMBERS ON SCHEDULE DO | | | NOT CORRESPOND TO EXHAUST FANS SHOWN ON | | | PLAN. PROVIDE REVISED PLANS SHOWING | | | CLARIFICATION OF EXHAUST FAN INFORMATION | | | IF THIS REQUIRES A CHANGE OF THE AIR | | | BALANCE SCHEDULE PROVIDE REVISED | | | SCHEDULE | | | 3) EQUIPMENT SERVING AREAS USED FOR | | | EGRESS SHALL HAVE FAN SHUT DOWN BY DUCT | | | SMOKE DETECTOR REGARDLESS OF SIZE OF | | | EQUIPMENT PER 1997 SMC 406.2 | | | 4) ADDITIONAL PERMITS REQUIRED FOR | | | KITCHEN HOOD, SUPPRESSION SYSTEMAND | | | WALK IN COOLERS/FREEZERS SUBMIT DETAILED | | | PLANS AT TIME OF MECHANICAL PERMIT APP- | | | LICATION FOR THESE SYSTEMS | | | 5) THE ABOVE CLARIFICATIONS EXCEPT ITEM | | | 4 SHALL BE SUBMITTED FOR PLAN REVIEW | | | PRIOR TO ANY MECHANICAL WORK BEING DONE | | | ON THIS PROJECT |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
A |
Date |
2000-04-05 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-12-06 |
Time |
15:29 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
1999-12-06 |
Time |
15:29 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **REVISION 3 ACCEPTED W/ PROVISO******** | | | PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 | | | PROVIDE AIR BALANCE CALCULATIONS PER | | | 1997 SMC 501.2 | | | 1997 SMC DOES NOT ALLOW THE USE OF | | | PUBLIC EXIT CORRIDORS FOR PLENUMS FOR | | | ADJOINING AREAS 609.1.1 | | | EF 2A SHOWS AS RESTROOM EXHAUST ON | | | SCHEDULE BUT IS IN CORRIDOR ON PLAN | | | DEFINE USE/LOCATION | | | AHU IN CORRIDOR SHOW NO RETURN AIR. IS | | | THIS 100% OUTSIDE AIR? SEE AHU 8 AND 16 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
A |
Date |
2000-04-05 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-09-23 |
Time |
11:46 |
Rev Time |
1.50 |
| Received By |
ndenmark |
Date |
1999-09-23 |
Time |
11:46 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ****REVISION 3 ACCEPTED W/ PROVISO****** | | | | | | 1)ASHRAE 62-89 6.1.3.4 ALLOWS FOR REDUC- | | | TION OF OUTDOOR AIR ONLY WHEN PEAK OCCUP | | | ANCIES OCCUR FOR LESS THAN 3 HOURS DURA- | | | TION AND NOT LESS 1/2 THE MAX. IS USED | | | FOR THE AVERAGE. THIS DOES NOT FIT THAT | | | CRITERIA. | | | 2)ASHRAE 62-89 6.1.3.2 ALLOWS REDUCTION | | | OF OUTSIDE AIR BELOW TABLE 2 AMOUNTS | | | USING PROCEDURE 6.2 PROVIDE CALCULATIONS | | | ON BASIS FOR EQUIPMENT DETERMINATION AND | | | AIR SYSTEM CLEANING EFFICIENCY PER | | | SECTION 6.2 | | | 3) RE: ITEM NO. 2 AIR BALANCE, SCHEDULE | | | REQUESTED ON AIR BALANCE TO ASSURE COMP- | | | LIENCE WITH 1994 SMC 501.2 SHOW TOTAL | | | OUTSIDE AIR SUPPLIED, TOTAL EXHAUST AIR | | | AND EXFILTRATION QUANTITIES. | | | 4)KITCHEN/DINING ROOM REQUIRES 20 CFM | | | PER PERSON,NOT 15 CFM PER PERSON. | | | 5)REDUCTION RATE ACCEPTABLE FOR DINING | | | ROOM AND AUDITORIUM IF PEAK OCCUPANCY IS | | | LESS THAN 3 HOURS AND AVERAGE OCCUPANCY | | | USED IS NOT LESS THAN 1/2 THE MAXIMUM. | | | 6) ITEM NO. 3 RE: DUCT SMOKE DETECTORS, | | | THE DOCUMENT RECEIVED BY THE BUILDING | | | DIVISION IS A COPY AND THERE IS NO | | | "MECHANICAL LEGEND" ON SCALED PLAN AND | | | THE SYMBOLS ON PLANS RECEIVED ARE UNREAD | | | ABLE DO TO COPY QUAILITY | | | 7) AIR HANDLERS PROVIDING AIR FOR AREAS | | | USED FOR EXITS OR EXIT ACCESS CORRIDORS | | | SHALL HAVE AUTOMATIC SHUT DOWN PER 1994 | | | SMC 406.2 | | | 8) PLAN DOCUMENTS RECEIVED ARE NOT | | | ORIGINAL SIGNED AND SEALED DOCUMENTS AND | | | ARE NOT ACCEPTABLE AS SUBMITTED. PROVIDE | | | ORIGINAL, LEGABLE DOCUMENTS, SIGNED AND | | | SEALED BY STATE OF FLORIDA LICENSED ENG- | | | INEER 104.2.3 CITY AMENDMENTS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2000-03-25 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-03-25 |
Time |
08:46 |
Rev Time |
3.00 |
| Received By |
tlarge |
Date |
2000-03-25 |
Time |
08:46 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************PROVISO***************** | | | PROVIDE SIGNED AND SEALED DRAWINGS FOR | | | THE GREASE TRAP.COMPLY W/CITY OF WPB | | | BUILDING DEPT.DETAILS. | | | | | | A 30"X 48" CLEAR FLOOR SPACE SHALL BE | | | PROVIDED ADJACENT TO THE SHOWERS PER | | | FACBC SEC.4.21.2 AND FIG.35. | | | | | | THE TOILET ROOM INTHE ISOLATION ROOM | | | SHALL COMPLY W/FACBC SEC.4.16.2 AND FIG. | | | 28. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2000-03-15 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-03-15 |
Time |
19:03 |
Rev Time |
1.50 |
| Received By |
tlarge |
Date |
2000-03-15 |
Time |
19:02 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | COMPLY W/ALL PREVIOUS COMMENTS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2000-03-07 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-03-07 |
Time |
11:59 |
Rev Time |
6.50 |
| Received By |
tlarge |
Date |
2000-03-07 |
Time |
11:59 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | JOB SPEC.15400-PART 1-REVISE STANDARD TO | | | READ NFPA 54,NOT NFPA 56. | | | | | | SPEC.15400-PART 2-FITTINGS NOT PERMITTED | | | ON WATER DISTRIBUTION LINES UNDER BLDG. | | | SLAB PER COUNTYWIDE AMENDMENTS TO SPC | | | 611.3. | | | | | | SUBMIT MANUF.SHEETS FOR WATER SOFTENER | | | PER SPC SEC.615. | | | | | | CITY OF WPB UTILITIES SHALL APPROVE SIZE | | | AND DESIGN OF GREASE TRAP.SUBMIT | | | APPROVAL FORM FROM UTILITIES.CONTACT | | | R.COMPO AT (561)835-7423. | | | | | | PLBG.FIXTURES IN ISOLATION ROOM SHALL BE | | | FULLY ACCESSIBLE PER FACBC SEC.4.1.3(11) | | | TOILET IN PRESIDENT'S OFFICE SHALL BE | | | ADAPTABLE. | | | | | | SINK IN TEACHER'S LOUNGE SHALL COMPLY W/ | | | FACBC SEC.4.24.1-4.24.7.CLEARLY SHOW | | | ON PLANS. | | | | | | CLEARLY SHOW HEIGHT OF H.C. URINAL ON | | | PLANS.COMPLY W/FACBC SEC.4.18.2. | | | | | | SUBMIT A COMPLETE ISOMETRIC FOR THE | | | ENTIRE STORM WATER SYSTEM.SHOW ALL PIPE | | | SIZES AND SQUARE FOOTAGE DRAINED BY EACH | | | ROOF DRAIN PER COUNTYWIDE AMENDMENTS TO | | | SPC SEC.104.2.1.,SPC SEC.1108. | | | | | | AN ADDITIONAL STALL COMPLYING W/FACBC | | | SEC.4.22.4.SHALL BE PROVIDED IN THE | | | WOMEN'S TOILET ROOM. | | | | | | A TWO WAY CLEANOUT BROUGHT TO GRADE | | | SHALL BE INSTALLED IN THE INLET AND | | | OUTLET OF THE GREASE INTERCEPTOR PER | | | SPC SEC.1004.8, | | | | | | THE CURRENT C.O.'S SHALL BE RELOCATED TO | | | COMPLY W/SPC SEC.307.5. | | | | | | THE DISTANCE BETWEEN SAN.AND WATER SHALL | | | COMPLY W/SPC SEC.608.3(SHT.P-1) | | | | | | SUBMIT SANITARY ISOMETRIC FOR REVEW.THE | | | DRAWING ON THE PLANS HAS TOO MANY | | | VIOLATIONS TO LIST.COUNTYWIDE AMENDMENT | | | TO SPC SEC.104.2.1`. | | | | | | SIZE THE WATER RISER IN ITS ENTIRETY. | | | | | | WATER SUPPLY CONTROL SHALL COMPLY W/SPC | | | SEC.610.4.1.,610.4.4 | | | | | | | | | | | | | | | | | | YOU MUST COMPLETE A WAIVER FOR THE USE | | | OF CHILREN'S FIXTURES IN THE SCHOOL.THE | | | ACCESSIBILITY STANDARD IS ONLY A GUIDE - | | | LINE AND HAS NOT BEEN ADOPTED BY THE | | | DEPT.OF JUSTICE.THE WAIVER SHALL BE | | | SUBMITTED TO STATE OF FL.DEPT.OF COMM. | | | AFFAIRS. | | | | | | THE TOILET STALLS IN THE GYM SHALL CON- | | | TAIN AN ACCESIBLE LAV.WITHIN THE STALLS | | | PER FACBC SEC.4.17.3. | | | | | | SHOWERS IN GYM SHALL COMPLY W/FACBC | | | 4.21.2.FOR SIZE AND CLEARANCE.SEE SECS. | | | 4.21.3- 4.21.7. | | | | | | ALL PUBLIC AND COMMON AREA TOILET ROOMS | | | SHALL COMPLY W/FACBC SEC.4.1.3(11),4.22. | | | | | | THE BUILDING PLANS SHALL BEAR THE STAMP | | | FROM THE HEALTH DEPT.,NOT JUST THE CIVIL | | | DWGS.COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 101.4.7. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
1999-12-03 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-12-03 |
Time |
14:32 |
Rev Time |
6.50 |
| Received By |
tlarge |
Date |
1999-12-03 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | CIVIL DRAWINGS SHALL BE SIGNED AND | | | SEALED BY PROFESSIONAL OF RECORD PER F.S | | | 471.025. | | | | | | SHOW LOCATION AND SIZE OF GREASE TRAP | | | ON PLANS.MIN.SIZE SHALL BE 750 GALS. | | | CONTACT RODNEY COMPO/CITY OF WPB | | | REGIONAL SEWER TREATMENT PLANT FOR | | | SIZING REQS.AT (561)835-7423.(GREASE | | | TRAP CANNOT BE LOCATED IN FOOD PREP AREA | | | | | | SUBMIT RISER DIAGRAM FOR STORM DRAINAGE | | | SYSTEM AND SHOW PROVISIONS FOR SECONDARY | | | DRAINAGE.COMPLY W/CHAPT.11 OF SPC. | | | | | | SUBMIT SANITARY AND WATER RISERS THAT | | | COMPLY FULLY TO THE SPC IN ALL RESPECTS. | | | | | | SINK IN TEACHER'S LOUNGE SHALL COMPLY | | | W/FACBC SEC.4.24.1-4.24.7. | | | | | | EACH PUBLIC AND COMMON USE TOILET ROOM | | | SHALL COMPLY W/FACBC SEC.4.1.3.(11), | | | 4.22. | | | | | | WATER CLOSETS IN H.C.STALLS SHALL BE | | | LOCATED IN THE CORNER,DIAGONAL TO THE | | | DOOR.FACBC SEC.4.17.3. | | | | | | CLEARLY SHOW DISTANCE BETWEEN THE WATER | | | SERVICE AND THE BUILDING SEWER.COMPLY | | | W/SPC 608.3. | | | | | | SHOWERS IN GYM SHALL COMPLY W/FACBC | | | SEC.4.21.1-4.21.7. | | | | | | GYM RESTROOMS SHALL BE EQUIPPED W/FULLY | | | ACCESSIBLE STALLS PER FACBC SECS.4.1.3 | | | (11),4.22., | | | | | | SUBMIT OCCUPANT LOAD OF GYM.TYPE AND | | | AMOUNT OF REQD.PLBG.FIXTURES SHALL | | | COMPLY W/TABLE 407 OF SPC. | | | | | | WATER HEATER SHALL BE READILY ACCESSIBLE | | | PER SPC SEC.501.7(A).A PERMANENT LADDER | | | SHALL BE INSTALLED OR HEATER SHALL BE | | | LOCATED ON FLOOR. | | | | | | PLANS SHALL BE ROUTED TO PALM BEACH | | | COUNTY HEALTH FOR REVIEW AND APPROVAL | | | PER COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 101.4.7. | | | | | | SHT.A-3-SHOW INSIDE CLEAR DIMENSIONS | | | (LXW)OF TOILET ROOMS AND STALLS.COMPLY | | | W/FACBC SEC.4.16.2,4.17.3. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
1999-09-08 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-09-08 |
Time |
08:50 |
Rev Time |
5.75 |
| Received By |
tlarge |
Date |
1999-09-04 |
Time |
11:21 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SUBMIT SITE PLAN SHOWING WATER AND SEWER | | | LINES TO THE STRUCTURES.SPC 104.2.1. | | | | | | DRINKING FOUNTAINS SHALL BE REQUIRED AT | | | RATIO OF 1 PER 3 CLASSROOMS & NOT LESS | | | THAN 1 PER FLOOR.SPC TABLE 407. | | | | | | SHOW LOCATION AND SIZE OF GREASE TRAP. | | | SUBMIT DETAIL OF GREASE TRAP.CONTACT | | | RODNEY COMPO /CITY OF WPB REGIONAL SEWER | | | TREATMENT PLANT FOR SIZE REQS.AT | | | (561)835-7423.(GREASE TRAP CANNOT BE | | | LOCATED IN FOOD PREP AREA.) | | | | | | SUBMIT ISOMETRIC DRAWINGS FOR ALL STORM, | | | SANITARY AND WATER SYSTEMS.SPC 104.2.1. | | | | | | SUBMIT DETAILS AND U.L.ASSEMBLY NUMBER | | | FOR FIRE SAFING OF PIPE PENETRATIONS | | | THROUGH RATED WALLS PER SPC 104.2.4. | | | | | | SINK IN TEACHER'S LOUNGE SHALL COMPLY W/ | | | FACBC SECS.4.24.1-4.24.7. | | | | | | EACH PUBLIC AND COMMON USE TOILET ROOM | | | SHALL COMPLY W/FACBC SEC.4.1.3(11),4.22. | | | | | | WATER CLOSETS IN H.C.STALLS SHALL BE | | | LOCATED IN THE CORNER,DIAGONAL TO THE | | | DOOR.FACBC SEC.4.17.3. | | | | | | NUMBER OF REQD.URINALS SHALL COMPLY W/ | | | SPC TABLE 407,FOOTNOTE #3.(3 REQD.) | | | | | | FLOOR DRAINS AND WAINSCOTING ARE REQ'D. | | | IN ALL TOILET ROOMS PER SBC SEC.1204.2. | | | | | | SUBMIT ELEVATION DETAILS FOR ALL | | | HANDICAP FIXTURES.COMPLY W/FACBC. | | | | | | SHEETS P-1 & P-2 SHALL BE SIGNED AND | | | SEALED BY DESIGN PROFESSIONAL PER SPC | | | SEC.104.2.3. | | | | | | DISTANCE BETWEEN WATER SERVICE AND BLDG. | | | SEWER SHALL COMPLY W/SPC SEC.608.3. | | | | | | PLBG.FIXTURES IN GYM SHALL COMPLY W/ | | | FACBC SEC.4.1.3(11),4.22. | | | | | | SUBMIT OCCUPANT LOAD OF GYM.NUMBER OF | | | REQD.FIXTURES SHALL COMPLY W/TABLE 407 | | | OF SPC. | | | | | | SHT P-2-DETAIL 3A-FLOOR SINKS EXCEED | | | DISTANCE FROM VENT PER TABLE 908.1 AND | | | ARE NOT PROPERLY VENTED. | | | | | | SHT.P-2.DETAIL#4-LOCATION OF LAVATORY | | | DOESN'T CORRELATE W/SHT.A-1.COMPLY W/ | | | FACBC SEC.4.17.3. | | | | | | WATER HEATER SHALL BE READILY ACCESSIBLE | | | PER SPC 501.7.A PERMANENT LADDER SHALL | | | BE INSTALLED OR HEATER SHALL BE LOCATED | | | ON FLOOR. | | | | | | SUBMIT COMPLETE PLANS FOR ANY GAS WORK | | | BEING PERFORMED IF APPLICABLE.STD.GAS | | | CODE SEC.302. | | | | | | PLANS SHALL BE ROUTED TO HEALTH DEPT.FOR | | | REVIEW AND APPROVAL PER SPC 101.4.7. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2000-04-04 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-04-04 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO NEED S&S LANDSCAPE PLANS ANGELA | | | JONES 4/4/00 HHP |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
1999-08-12 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-01-07 |
Time |
14:33 |
Rev Time |
0.75 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NEEDS SITE PLAN/LANDSCAPING |
|
|