Plan Review Details - Permit 99080492
Plan Review Stops For Permit 99080492
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-04-04 Cont ID  
Sent By hpiskura Date 2000-04-04 Time 15:27 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO STRUCT CALCULATIONS REQ

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-01-07 Cont ID  
Sent By hpiskura Date 2000-01-07 Time 14:29 Rev Time 0.00
Received By hpiskura Date 2000-01-05 Time 09:39 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 1999-09-27 Cont ID  
Sent By hpiskura Date 1999-09-27 Time 14:42 Rev Time 12.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-03-25 Cont ID  
Sent By dpalmer Date 2000-03-25 Time 10:13 Rev Time 0.00
Received By dpalmer Date 2000-03-25 Time 10:13 Sent To  
Notes
2001-01-08 00:00:00************* PROVISO *****************
  
 1)NOTE: LOCAL CODE FOR OUTLET SPACING.
  
 2)NOTE: MISSING OUTLET FOR MECH ROOM
 ART 210-63
  
 3)NOTE:ALL BATH REC TO BE GFI 210-8-B
  
 4)NOTE: ROOMS SHOWN AS STORAGE WITH
 ELEC. PANELS?? SEE 240-24-D AND 384-7
 PLEASE CHECK YOUR LOACTIONS
  
 PLEASE SUBMIT THE REVISED SHEETS FOR
 REVIEW BEFORE ROUGH ELECTRICAL IS CALLED
 IN. IF THERE ARE ANY QUESTIONS PLEASE
 CALL 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 1999-12-17 Cont ID  
Sent By dpalmer Date 1999-12-17 Time 07:21 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00*****************UNSAT*****************
  
 SAME AS ORIGINAL NOTES
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF ALL
 EQUIPMENT!! TO INCLUDE PANELS. AS PER
 ARTS:230-65/110-9/215-5
  
 2)NOTE: PLEASE CHECK GROUNDING ELECTRODE
 CONDUCOTR SIZE AS PER TABLE 250-94
 EXCEPT. #2 SUM OF SERVICE CONDUCTORS.
  
 3)NOTE: PLEASE SHOW BLDG.STEEL AS PART
 OF THE GOUNDING SYSTEM AS PER 250-81/
 215-5
  
 PLANS WOULD HAVE PASSED AS PROVISO BUT
 WERE COMING BACK TO YOU FOR PLUMB/MECH.
 PLEASE DRAW UP NEW FULL SIZE E-4 FOR
 LARGE SET WITH THE INFORMATION ABOVE
 FOR REVIEW AND APPROVAL. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 561-659-8096
 EXT.8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 1999-09-29 Cont ID  
Sent By dpalmer Date 1999-09-29 Time 10:48 Rev Time 0.00
Received By dpalmer Date 1999-09-29 Time 10:48 Sent To  
Notes
2001-01-08 00:00:00**************DENIED*******************
  
 1)NEED TO SUBMIT AIC RATING OF ALL
 EQUIPMENT,MAINS,DISC.`S FUSES,BRKRS.
 AS PER ARTS;110-9/215-5
 2)NEED TO SUBMIT GROUNDING SYSTEM.
 TO INCLUDE GROUNDING ELECTRODE SYSTEM
 WITH ALL POINTS OF ATTACHMENT.ALSO
 INCLUDE WIRE SIZES FIGURED FROM ART;/
 TABLE 250-94/250-95
 3)NEED LOAD CALCULATIONS FOR EACH PANEL
 AND FOR MDP.AS PER ART; 215-5

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 1999-12-08 Cont ID  
Sent By hpiskura Date 1999-09-27 Time 14:42 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00AS PER99120274

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-09-29 Cont ID  
Sent By dpalmer Date 1999-09-29 Time 10:47 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-04-05 Cont ID  
Sent By ndenmark Date 2000-04-05 Time 07:17 Rev Time 1.00
Received By ndenmark Date 2000-04-05 Time 07:17 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1) FIRE DAMPERS REQUIRED AT ALL DUCT
 PENETRATIONS OF RATED WALLS. PROVIDE
 SPECIFIC LOCATION AND INSTALLATION
 DETAILS AS PER 1997 SMC 610.6
 2) EXHAUST FAN NUMBERS ON SCHEDULE DO
 NOT CORRESPOND TO EXHAUST FANS SHOWN ON
 PLAN. PROVIDE REVISED PLANS SHOWING
 CLARIFICATION OF EXHAUST FAN INFORMATION
 IF THIS REQUIRES A CHANGE OF THE AIR
 BALANCE SCHEDULE PROVIDE REVISED
 SCHEDULE
 3) EQUIPMENT SERVING AREAS USED FOR
 EGRESS SHALL HAVE FAN SHUT DOWN BY DUCT
 SMOKE DETECTOR REGARDLESS OF SIZE OF
 EQUIPMENT PER 1997 SMC 406.2
 4) ADDITIONAL PERMITS REQUIRED FOR
 KITCHEN HOOD, SUPPRESSION SYSTEMAND
 WALK IN COOLERS/FREEZERS SUBMIT DETAILED
 PLANS AT TIME OF MECHANICAL PERMIT APP-
 LICATION FOR THESE SYSTEMS
 5) THE ABOVE CLARIFICATIONS EXCEPT ITEM
 4 SHALL BE SUBMITTED FOR PLAN REVIEW
 PRIOR TO ANY MECHANICAL WORK BEING DONE
 ON THIS PROJECT

Review Stop M MECHANICAL (A/C)
Rev No 2 Status A Date 2000-04-05 Cont ID  
Sent By ndenmark Date 1999-12-06 Time 15:29 Rev Time 0.50
Received By ndenmark Date 1999-12-06 Time 15:29 Sent To  
Notes
2001-01-08 00:00:00**REVISION 3 ACCEPTED W/ PROVISO********
 PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 PROVIDE AIR BALANCE CALCULATIONS PER
 1997 SMC 501.2
 1997 SMC DOES NOT ALLOW THE USE OF
 PUBLIC EXIT CORRIDORS FOR PLENUMS FOR
 ADJOINING AREAS 609.1.1
 EF 2A SHOWS AS RESTROOM EXHAUST ON
 SCHEDULE BUT IS IN CORRIDOR ON PLAN
 DEFINE USE/LOCATION
 AHU IN CORRIDOR SHOW NO RETURN AIR. IS
 THIS 100% OUTSIDE AIR? SEE AHU 8 AND 16

Review Stop M MECHANICAL (A/C)
Rev No 1 Status A Date 2000-04-05 Cont ID  
Sent By ndenmark Date 1999-09-23 Time 11:46 Rev Time 1.50
Received By ndenmark Date 1999-09-23 Time 11:46 Sent To  
Notes
2001-01-08 00:00:00****REVISION 3 ACCEPTED W/ PROVISO******
  
 1)ASHRAE 62-89 6.1.3.4 ALLOWS FOR REDUC-
 TION OF OUTDOOR AIR ONLY WHEN PEAK OCCUP
 ANCIES OCCUR FOR LESS THAN 3 HOURS DURA-
 TION AND NOT LESS 1/2 THE MAX. IS USED
 FOR THE AVERAGE. THIS DOES NOT FIT THAT
 CRITERIA.
 2)ASHRAE 62-89 6.1.3.2 ALLOWS REDUCTION
 OF OUTSIDE AIR BELOW TABLE 2 AMOUNTS
 USING PROCEDURE 6.2 PROVIDE CALCULATIONS
 ON BASIS FOR EQUIPMENT DETERMINATION AND
 AIR SYSTEM CLEANING EFFICIENCY PER
 SECTION 6.2
 3) RE: ITEM NO. 2 AIR BALANCE, SCHEDULE
 REQUESTED ON AIR BALANCE TO ASSURE COMP-
 LIENCE WITH 1994 SMC 501.2 SHOW TOTAL
 OUTSIDE AIR SUPPLIED, TOTAL EXHAUST AIR
 AND EXFILTRATION QUANTITIES.
 4)KITCHEN/DINING ROOM REQUIRES 20 CFM
 PER PERSON,NOT 15 CFM PER PERSON.
 5)REDUCTION RATE ACCEPTABLE FOR DINING
 ROOM AND AUDITORIUM IF PEAK OCCUPANCY IS
 LESS THAN 3 HOURS AND AVERAGE OCCUPANCY
 USED IS NOT LESS THAN 1/2 THE MAXIMUM.
 6) ITEM NO. 3 RE: DUCT SMOKE DETECTORS,
 THE DOCUMENT RECEIVED BY THE BUILDING
 DIVISION IS A COPY AND THERE IS NO
 "MECHANICAL LEGEND" ON SCALED PLAN AND
 THE SYMBOLS ON PLANS RECEIVED ARE UNREAD
 ABLE DO TO COPY QUAILITY
 7) AIR HANDLERS PROVIDING AIR FOR AREAS
 USED FOR EXITS OR EXIT ACCESS CORRIDORS
 SHALL HAVE AUTOMATIC SHUT DOWN PER 1994
 SMC 406.2
 8) PLAN DOCUMENTS RECEIVED ARE NOT
 ORIGINAL SIGNED AND SEALED DOCUMENTS AND
 ARE NOT ACCEPTABLE AS SUBMITTED. PROVIDE
 ORIGINAL, LEGABLE DOCUMENTS, SIGNED AND
 SEALED BY STATE OF FLORIDA LICENSED ENG-
 INEER 104.2.3 CITY AMENDMENTS

Review Stop P PLUMBING
Rev No 5 Status P Date 2000-03-25 Cont ID  
Sent By tlarge Date 2000-03-25 Time 08:46 Rev Time 3.00
Received By tlarge Date 2000-03-25 Time 08:46 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO*****************
 PROVIDE SIGNED AND SEALED DRAWINGS FOR
 THE GREASE TRAP.COMPLY W/CITY OF WPB
 BUILDING DEPT.DETAILS.
  
 A 30"X 48" CLEAR FLOOR SPACE SHALL BE
 PROVIDED ADJACENT TO THE SHOWERS PER
 FACBC SEC.4.21.2 AND FIG.35.
  
 THE TOILET ROOM INTHE ISOLATION ROOM
 SHALL COMPLY W/FACBC SEC.4.16.2 AND FIG.
 28.

Review Stop P PLUMBING
Rev No 4 Status F Date 2000-03-15 Cont ID  
Sent By tlarge Date 2000-03-15 Time 19:03 Rev Time 1.50
Received By tlarge Date 2000-03-15 Time 19:02 Sent To  
Notes
2001-01-08 00:00:00COMPLY W/ALL PREVIOUS COMMENTS.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-03-07 Cont ID  
Sent By tlarge Date 2000-03-07 Time 11:59 Rev Time 6.50
Received By tlarge Date 2000-03-07 Time 11:59 Sent To  
Notes
2001-01-08 00:00:00JOB SPEC.15400-PART 1-REVISE STANDARD TO
 READ NFPA 54,NOT NFPA 56.
  
 SPEC.15400-PART 2-FITTINGS NOT PERMITTED
 ON WATER DISTRIBUTION LINES UNDER BLDG.
 SLAB PER COUNTYWIDE AMENDMENTS TO SPC
 611.3.
  
 SUBMIT MANUF.SHEETS FOR WATER SOFTENER
 PER SPC SEC.615.
  
 CITY OF WPB UTILITIES SHALL APPROVE SIZE
 AND DESIGN OF GREASE TRAP.SUBMIT
 APPROVAL FORM FROM UTILITIES.CONTACT
 R.COMPO AT (561)835-7423.
  
 PLBG.FIXTURES IN ISOLATION ROOM SHALL BE
 FULLY ACCESSIBLE PER FACBC SEC.4.1.3(11)
 TOILET IN PRESIDENT'S OFFICE SHALL BE
 ADAPTABLE.
  
 SINK IN TEACHER'S LOUNGE SHALL COMPLY W/
 FACBC SEC.4.24.1-4.24.7.CLEARLY SHOW
 ON PLANS.
  
 CLEARLY SHOW HEIGHT OF H.C. URINAL ON
 PLANS.COMPLY W/FACBC SEC.4.18.2.
  
 SUBMIT A COMPLETE ISOMETRIC FOR THE
 ENTIRE STORM WATER SYSTEM.SHOW ALL PIPE
 SIZES AND SQUARE FOOTAGE DRAINED BY EACH
 ROOF DRAIN PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1.,SPC SEC.1108.
  
 AN ADDITIONAL STALL COMPLYING W/FACBC
 SEC.4.22.4.SHALL BE PROVIDED IN THE
 WOMEN'S TOILET ROOM.
  
 A TWO WAY CLEANOUT BROUGHT TO GRADE
 SHALL BE INSTALLED IN THE INLET AND
 OUTLET OF THE GREASE INTERCEPTOR PER
 SPC SEC.1004.8,
  
 THE CURRENT C.O.'S SHALL BE RELOCATED TO
 COMPLY W/SPC SEC.307.5.
  
 THE DISTANCE BETWEEN SAN.AND WATER SHALL
 COMPLY W/SPC SEC.608.3(SHT.P-1)
  
 SUBMIT SANITARY ISOMETRIC FOR REVEW.THE
 DRAWING ON THE PLANS HAS TOO MANY
 VIOLATIONS TO LIST.COUNTYWIDE AMENDMENT
 TO SPC SEC.104.2.1`.
  
 SIZE THE WATER RISER IN ITS ENTIRETY.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SEC.610.4.1.,610.4.4
  
  
  
  
  
 YOU MUST COMPLETE A WAIVER FOR THE USE
 OF CHILREN'S FIXTURES IN THE SCHOOL.THE
 ACCESSIBILITY STANDARD IS ONLY A GUIDE -
 LINE AND HAS NOT BEEN ADOPTED BY THE
 DEPT.OF JUSTICE.THE WAIVER SHALL BE
 SUBMITTED TO STATE OF FL.DEPT.OF COMM.
 AFFAIRS.
  
 THE TOILET STALLS IN THE GYM SHALL CON-
 TAIN AN ACCESIBLE LAV.WITHIN THE STALLS
 PER FACBC SEC.4.17.3.
  
 SHOWERS IN GYM SHALL COMPLY W/FACBC
 4.21.2.FOR SIZE AND CLEARANCE.SEE SECS.
 4.21.3- 4.21.7.
  
 ALL PUBLIC AND COMMON AREA TOILET ROOMS
 SHALL COMPLY W/FACBC SEC.4.1.3(11),4.22.
  
 THE BUILDING PLANS SHALL BEAR THE STAMP
 FROM THE HEALTH DEPT.,NOT JUST THE CIVIL
 DWGS.COUNTYWIDE AMENDMENTS TO SPC SEC.
 101.4.7.

Review Stop P PLUMBING
Rev No 2 Status F Date 1999-12-03 Cont ID  
Sent By tlarge Date 1999-12-03 Time 14:32 Rev Time 6.50
Received By tlarge Date 1999-12-03 Time 14:32 Sent To  
Notes
2001-01-08 00:00:00CIVIL DRAWINGS SHALL BE SIGNED AND
 SEALED BY PROFESSIONAL OF RECORD PER F.S
 471.025.
  
 SHOW LOCATION AND SIZE OF GREASE TRAP
 ON PLANS.MIN.SIZE SHALL BE 750 GALS.
 CONTACT RODNEY COMPO/CITY OF WPB
 REGIONAL SEWER TREATMENT PLANT FOR
 SIZING REQS.AT (561)835-7423.(GREASE
 TRAP CANNOT BE LOCATED IN FOOD PREP AREA
  
 SUBMIT RISER DIAGRAM FOR STORM DRAINAGE
 SYSTEM AND SHOW PROVISIONS FOR SECONDARY
 DRAINAGE.COMPLY W/CHAPT.11 OF SPC.
  
 SUBMIT SANITARY AND WATER RISERS THAT
 COMPLY FULLY TO THE SPC IN ALL RESPECTS.
  
 SINK IN TEACHER'S LOUNGE SHALL COMPLY
 W/FACBC SEC.4.24.1-4.24.7.
  
 EACH PUBLIC AND COMMON USE TOILET ROOM
 SHALL COMPLY W/FACBC SEC.4.1.3.(11),
 4.22.
  
 WATER CLOSETS IN H.C.STALLS SHALL BE
 LOCATED IN THE CORNER,DIAGONAL TO THE
 DOOR.FACBC SEC.4.17.3.
  
 CLEARLY SHOW DISTANCE BETWEEN THE WATER
 SERVICE AND THE BUILDING SEWER.COMPLY
 W/SPC 608.3.
  
 SHOWERS IN GYM SHALL COMPLY W/FACBC
 SEC.4.21.1-4.21.7.
  
 GYM RESTROOMS SHALL BE EQUIPPED W/FULLY
 ACCESSIBLE STALLS PER FACBC SECS.4.1.3
 (11),4.22.,
  
 SUBMIT OCCUPANT LOAD OF GYM.TYPE AND
 AMOUNT OF REQD.PLBG.FIXTURES SHALL
 COMPLY W/TABLE 407 OF SPC.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7(A).A PERMANENT LADDER
 SHALL BE INSTALLED OR HEATER SHALL BE
 LOCATED ON FLOOR.
  
 PLANS SHALL BE ROUTED TO PALM BEACH
 COUNTY HEALTH FOR REVIEW AND APPROVAL
 PER COUNTYWIDE AMENDMENTS TO SPC SEC.
 101.4.7.
  
 SHT.A-3-SHOW INSIDE CLEAR DIMENSIONS
 (LXW)OF TOILET ROOMS AND STALLS.COMPLY
 W/FACBC SEC.4.16.2,4.17.3.

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-09-08 Cont ID  
Sent By tlarge Date 1999-09-08 Time 08:50 Rev Time 5.75
Received By tlarge Date 1999-09-04 Time 11:21 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SITE PLAN SHOWING WATER AND SEWER
 LINES TO THE STRUCTURES.SPC 104.2.1.
  
 DRINKING FOUNTAINS SHALL BE REQUIRED AT
 RATIO OF 1 PER 3 CLASSROOMS & NOT LESS
 THAN 1 PER FLOOR.SPC TABLE 407.
  
 SHOW LOCATION AND SIZE OF GREASE TRAP.
 SUBMIT DETAIL OF GREASE TRAP.CONTACT
 RODNEY COMPO /CITY OF WPB REGIONAL SEWER
 TREATMENT PLANT FOR SIZE REQS.AT
 (561)835-7423.(GREASE TRAP CANNOT BE
 LOCATED IN FOOD PREP AREA.)
  
 SUBMIT ISOMETRIC DRAWINGS FOR ALL STORM,
 SANITARY AND WATER SYSTEMS.SPC 104.2.1.
  
 SUBMIT DETAILS AND U.L.ASSEMBLY NUMBER
 FOR FIRE SAFING OF PIPE PENETRATIONS
 THROUGH RATED WALLS PER SPC 104.2.4.
  
 SINK IN TEACHER'S LOUNGE SHALL COMPLY W/
 FACBC SECS.4.24.1-4.24.7.
  
 EACH PUBLIC AND COMMON USE TOILET ROOM
 SHALL COMPLY W/FACBC SEC.4.1.3(11),4.22.
  
 WATER CLOSETS IN H.C.STALLS SHALL BE
 LOCATED IN THE CORNER,DIAGONAL TO THE
 DOOR.FACBC SEC.4.17.3.
  
 NUMBER OF REQD.URINALS SHALL COMPLY W/
 SPC TABLE 407,FOOTNOTE #3.(3 REQD.)
  
 FLOOR DRAINS AND WAINSCOTING ARE REQ'D.
 IN ALL TOILET ROOMS PER SBC SEC.1204.2.
  
 SUBMIT ELEVATION DETAILS FOR ALL
 HANDICAP FIXTURES.COMPLY W/FACBC.
  
 SHEETS P-1 & P-2 SHALL BE SIGNED AND
 SEALED BY DESIGN PROFESSIONAL PER SPC
 SEC.104.2.3.
  
 DISTANCE BETWEEN WATER SERVICE AND BLDG.
 SEWER SHALL COMPLY W/SPC SEC.608.3.
  
 PLBG.FIXTURES IN GYM SHALL COMPLY W/
 FACBC SEC.4.1.3(11),4.22.
  
 SUBMIT OCCUPANT LOAD OF GYM.NUMBER OF
 REQD.FIXTURES SHALL COMPLY W/TABLE 407
 OF SPC.
  
 SHT P-2-DETAIL 3A-FLOOR SINKS EXCEED
 DISTANCE FROM VENT PER TABLE 908.1 AND
 ARE NOT PROPERLY VENTED.
  
 SHT.P-2.DETAIL#4-LOCATION OF LAVATORY
 DOESN'T CORRELATE W/SHT.A-1.COMPLY W/
 FACBC SEC.4.17.3.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC 501.7.A PERMANENT LADDER SHALL
 BE INSTALLED OR HEATER SHALL BE LOCATED
 ON FLOOR.
  
 SUBMIT COMPLETE PLANS FOR ANY GAS WORK
 BEING PERFORMED IF APPLICABLE.STD.GAS
 CODE SEC.302.
  
 PLANS SHALL BE ROUTED TO HEALTH DEPT.FOR
 REVIEW AND APPROVAL PER SPC 101.4.7.

Review Stop Z ZONING
Rev No 2 Status P Date 2000-04-04 Cont ID  
Sent By hpiskura Date 2000-04-04 Time 15:29 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO NEED S&S LANDSCAPE PLANS ANGELA
 JONES 4/4/00 HHP

Review Stop Z ZONING
Rev No 1 Status F Date 1999-08-12 Cont ID  
Sent By hpiskura Date 2000-01-07 Time 14:33 Rev Time 0.75
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEEDS SITE PLAN/LANDSCAPING