Plan Review Details - Permit 99080430
Plan Review Stops For Permit 99080430
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-06 Cont ID  
Sent By dpalmer Date 1999-10-06 Time 18:34 Rev Time 0.00
Received By dpalmer Date 1999-10-06 Time 18:34 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO******************
  
 1)NOTE;NEED TO SUBMIT AIC RATING OF
 EQUIPMENT AND MAINS. AS PER ARTS;110-9/
 215-5
 2)NOTE;AS PER ART;250-81 GROUNDING
 ELECTRODE CONDUCTOR IS REQ`D TO GO TO
 BLDG.STEEL ALSO.\\
 3)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS IN NEW
 CONSTRUCTION OF DWELLINGS.
 4)NOTE: AS PER ART;210-8-A-6 ALL RECEPTS
 SERVING KITCHEN COUNTER SPACE ARE TO BE
 GFI/GFI PROTECTED.
 5)NOTE: AS PER ART 210-52 OUTLETS REQ`D
 BEDROOM.
  
 NEED TO SUBMIT THE ABOVE INFORMATION
 TO BE APPROVED BEFORE FIRST ROUGH
 ELECTRICAL INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-03-07 Cont ID  
Sent By jleech Date 2000-03-07 Time 16:13 Rev Time 0.25
Received By jleech Date 2000-03-07 Time 16:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-08-19 Cont ID  
Sent By jleech Date 1999-08-19 Time 13:50 Rev Time 0.50
Received By jleech Date 1999-08-19 Time 13:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-11-18 Cont ID  
Sent By tlarge Date 1999-11-18 Time 20:38 Rev Time 0.50
Received By tlarge Date 1999-11-18 Time 20:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-12-06 Cont ID  
Sent By tlarge Date 1999-10-29 Time 08:58 Rev Time 0.50
Received By sgraham Date 1999-10-29 Time 08:58 Sent To  
Notes
2001-01-08 00:00:00SUBMIT DETAIL OF REINFORCEMENT FOR WALLS
 FOR FUTURE INSTALLATION OF GRAB BARS AS
 REQUIRED BY FEDERAL FAIR HOUSING ACT
 24 CFR 100.205 SECTION 3 REQUIREMENT #6.
 NOTE:ALL BATHROOMS WITHIN THE COVERED
 DWELLING UNIT SHALL COMPLY.
  
 ALL BATHROOMS IN THE DWELLING UNIT SHALL
 COMPLY WITH THE PROVISIONS OF THE
 FEDERAL FAIR HOUSING ACT 24 CFR 100.205
 (C)(3)(IV)REQ.#7 (2)PARAGRAPH (A)OR (B).
 CLEAR FLOOR SPACE SHALL BE PROVIDED AT
 FIXTURES TO ALLOW A PERSON IN A
 WHEELCHAIR OR OTHER MOBILITY AID USE OF
 THE FIXTURES.CLEAR FLOOR SPACE SHALL BE
 SHOWN ON THE PLANS AND DESIGNATE WHICH
 OPTION OF REQUIREMENT #7(A OR B)IS BEING
 USED.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-12-06 Cont ID  
Sent By tlarge Date 1999-08-25 Time 07:23 Rev Time 0.50
Received By sgraham Date 1999-08-25 Time 07:23 Sent To  
Notes
2001-01-08 00:00:00M.B.LAV.CANNOT BE INSTALLED AS DRAWN.
 SEPARATE STACK REQ'D.
  
 UNITS SHALL COMPLY W/FEDERAL FAIR
 HOUSING ACT/24 CFR 100.205 & FLA.STATUTE
 760.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-12-06 Cont ID  
Sent By fknapp Date 1999-10-07 Time 11:07 Rev Time 4.00
Received By sgraham Date 1999-10-07 Time 08:30 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 1)PROVIDE NEW ENERGY CALCULATIONS ON 97
 FORM.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-08-11 Cont ID  
Sent By gjoyce Date 1999-08-11 Time 08:01 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***