Plan Review Details - Permit 99080423
Plan Review Stops For Permit 99080423
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-09-22 Cont ID  
Sent By dpalmer Date 1999-09-22 Time 19:15 Rev Time 0.00
Received By dpalmer Date 1999-09-22 Time 19:15 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO*******************
  
 1)NOTE;AS PER ART;210-8-A-6 ALL RECEPTS.
 SERVING KITCHEN COUNTER SPACE ARE TO BE
 GFI/GFI PROTECTED.
 2)AS PER ART;250-81 GROUNDING ELECTRODE
 CONDUCTOR TO BLDG.STEEL ALSO.
 3)NOTE;AS PER 210-52 NOTE MISSING RECEPT
 4)NOTE;AS PER 1996/1993 NFPA-72 SMOKE
 DETECTORS ARE REQ`D INSIDE AND OUTSIDE
 ALL SLEEPING ROOMS.
 5)NOTE;AS PER ARTS;110-9/215-5 PLEASE
 SUBMIT AIC RATING OF EQUIPMENT AND
 BREAKERS.AIC RATING IS FIGURED FROM
 FAULT CURRENT CALCULATIONS.
  
 THE ABOVE NEEDS TO BE SUBMITTED AND
 APPROVED BEFORE FIRST ELECTRICAL ROUGH
 INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-09-27 Cont ID  
Sent By jcaloger Date 1999-09-27 Time 11:01 Rev Time 0.00
Received By jcaloger Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVIEWED & APPROVED BY JOHN LEECH

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-11-18 Cont ID  
Sent By tlarge Date 1999-11-18 Time 20:39 Rev Time 0.50
Received By tlarge Date 1999-11-18 Time 20:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 1999-10-28 Cont ID  
Sent By tlarge Date 1999-10-28 Time 06:43 Rev Time 0.50
Received By tlarge Date 1999-10-29 Time 06:42 Sent To  
Notes
2001-01-08 00:00:00SUBMIT DETAIL OF REINFORCEMENT OF WALLS
 FOR FUTURE INSTALLATION OF GRAB BARS AS
 REQUIRED BY FEDERAL FAIR HOUSING ACT
 24 CFR 100.205 SECTION 3 REQUIREMENT #6.
 NOTE:ALL BATHROOMS WITHIN THE COVERED
 DWELLING UNIT SHALL COMPLY.
  
 ALL BATHROOMS IN THE DWELLING UNIT SHALL
 COMPLY W/THE PROVISIONS OF THE FEDERAL
 FAIR HOUSING ACT 24 CFR 100.205(C)(3)
 (IV) REQ.#7 (2)PARAGRAPH (A)OR(B).
 CLEAR FLOOR SPACE SHALL BE PROVIDED AT
 FIXTURES TO ALLOW A PERSON IN A
 WHEELCHAIR OR OTHER MOBILITY AID USE OF
 THE FIXTURES.CLEAR FLOOR SPACE SHALL BE
 SHOWN ON THE PLANS AND DESIGNATE WHICH
 OPTION OF REQUIREMENT #7(A OR B) IS
 BEING USED.

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-08-21 Cont ID  
Sent By pschmitz Date 1999-08-21 Time 12:49 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00UNSAT:SHT 2-A LAV ON THE ISOMETRIC IN
 THE MASTER BATH IS IN THE WRONG LOCATION
 SHT 2-B ISOMETRIC DOES NOT MATCH FLOOR
 PLAN.
 UNITS SHALL COMPLY WITH FEDERAL FAIR
 HOUSING ACT/24 CFR 100.205 &
 FLORIDA STATUTE 760 .

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-12-06 Cont ID  
Sent By jcaloger Date 1999-09-27 Time 11:01 Rev Time 0.00
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-08-11 Cont ID  
Sent By gjoyce Date 1999-08-11 Time 08:01 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***