Plan Review Details - Permit 99080415
Plan Review Stops For Permit 99080415
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-09-22 Cont ID  
Sent By dpalmer Date 1999-09-22 Time 20:00 Rev Time 0.00
Received By dpalmer Date 1999-09-22 Time 20:00 Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO***************
  
 1)NOTE;AS PER NFPA 1996/1993 SMOKE
 DETECTORS ARE REQ`D INSIDE AND OUTSIDE
 ALL SLEEPING ROOMS.
 2)NOTE;NEED AIC RATING OF EQUIPMENT AND
 BREAKERS FIGURED FROM FAULT CURRENT
 CALCULATIONS.AS PER ARTS;110-9/215-5
 3)NOTE;AS PER ART;210-8-A-6 ALL RECEPTS.
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
 4)NOTE; ASPER ART;250-81 GROUNDING
 ELECTRODE CONDUCTOR TO GOT TO BLDG.
 STEEL ALSO.
 5)NOTE:AS PER ART;210-52 2`6`12` RULE.
  
 NEED TO SUBMIT THE ABOVE INFORMATION
 TO BE APPROVED BEFORE FIRST ELECTRICAL
 ROUGH INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-09-27 Cont ID  
Sent By jcaloger Date 1999-09-27 Time 14:45 Rev Time 1.00
Received By jcaloger Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVIEWED & APPROVED BY JOHN LEECH

Review Stop P PLUMBING
Rev No 4 Status P Date 1999-11-18 Cont ID  
Sent By tlarge Date 1999-11-18 Time 20:35 Rev Time 0.50
Received By tlarge Date 1999-11-18 Time 20:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 1999-10-29 Cont ID  
Sent By tlarge Date 1999-10-29 Time 09:07 Rev Time 0.50
Received By tlarge Date 1999-10-29 Time 09:07 Sent To  
Notes
2001-01-08 00:00:00SUBMIT DETAIL OF REINFORCEMENT OF WALLS
 FOR FUTURE INSTALLATION OF GRAB BARS AS
 REQUIRED BY FEDERAL FAIR HOUSING ACT
 24 CFR 100.205 SECTION 3 REQUIREMENT #6.
 NOTE:ALL BATHROOMS WITHIN THE COVERED
 DWELLING UNIT SHALL COMPLY.
  
 ALL BATHROOMS IN THE DWELLING UNIT SHALL
 COMPLY W/THE PROVISIONS OF FEDERAL FAIR
 HOUSING ACT 24 CFR 100.205 (C)(3)(IV)
 REQ.#7 (2)PARAGRAPH (A)OR (B).CLEAR
 FLOOR SPACE SHALL BE PROVIDED AT
 FIXTURES TO ALLOW A PERSON IN A WHEEL-
 CHAIR OR OTHER MOBILITY AID USE OF THE
 FIXTURES.CLEAR FLOOR SPACE SHALL BE
 SHOWN ON THE PLANS AND DESIGNATE WHICH
 OPTION OF REQUIREMENT #7(A OR B)IS BEING
 USED.

Review Stop P PLUMBING
Rev No 2 Status F Date 1999-10-29 Cont ID  
Sent By tlarge Date 1999-10-27 Time 15:03 Rev Time 0.50
Received By tlarge Date 1999-10-27 Time 15:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-08-25 Cont ID  
Sent By tlarge Date 1999-08-25 Time 08:58 Rev Time 0.50
Received By tlarge Date 1999-08-25 Time 08:58 Sent To  
Notes
2001-01-08 00:00:00MAGELLAN MODEL
  
 M.B.LAV.CANNOT BE INSTALLED AS DRAWN.
 SEPARATE STACK REQ'D.
  
 UNITS SHALL COMPLY W/FEDERAL FAIR
 HOUSING ACT/24 CFR 100.205 & FLA.STATUTE
 760.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-12-03 Cont ID  
Sent By jcaloger Date 1999-09-27 Time 14:46 Rev Time 1.00
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-08-11 Cont ID  
Sent By gjoyce Date 1999-08-11 Time 08:01 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***