Plan Review Details - Permit 99080247
Plan Review Stops For Permit 99080247
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 1999-09-16 Cont ID  
Sent By fcounter Date 1999-09-16 Time 08:45 Rev Time 0.00
Received By fcounter Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 1999-08-30 Cont ID  
Sent By ndenmark Date 1999-08-30 Time 11:33 Rev Time 0.00
Received By ndenmark Date   Time 09:31 Sent To  
Notes
2001-01-08 00:00:00CORRECTED W/ 99100267 PERMIT APPL NCD
 1) PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2) FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 REQUIRED PER 1997 SMC 406.1 WITH NOTIFI-
 CATION BY BLDG FIRE ALARM OR HORN AND
 STROBE IF NO BLDG FIRE ALARM PER NFPA
 90A 4-4.4.3

Review Stop P PLUMBING
Rev No 2 Status F Date 1999-10-04 Cont ID  
Sent By tlarge Date 1999-10-04 Time 07:23 Rev Time 1.50
Received By tlarge Date 1999-10-04 Time 07:23 Sent To  
Notes
2001-01-08 00:00:00SUBMIT DETAILS FOR THE CAR CARE ISLANDS.
  
 SHT.B-1. HANDICAP STALLS SHALL COMPLY W/
 FACBC SEC.4.17.3.(SEE EXCEPTION:NEW
 CONSTRUCTION.)
  
 CLEARLY SHOW REQUIRED MOUNTING HEIGHT
 DIMENSIONS AND CLEAR FLOOR SPACE UNDER
 PLBG.FIXTURES PER FACBC 1997 ED.
  
 SHOW FIXTURE CLEARANCES PER FACBC AND
 SPC SEC.403.4.(SHOW CLEAR FLOOR ACCESS
 FOR URINAL.SEE FACBC SEC.4.18.)
  
 A DRINKING FOUNTAIN IS REQD.PER SPC SEC.
 407.1.3.
  
 SINK SHALL COMPLY W/FACBC SEC.4.1.1(1)(A
 4.24.1 - 4.24.7.
  
 SUBMIT OCCUPANT LOAD.STRUCTURE SHALL
 COMPLY W/SPC TABLE 407 FOR MINIMUM
 TOILET FACILITIES.COMPLIANCE W/FLA.
 STATUTE 553.141.MAY BE REQD.(POTTY
 PARITY)
  
 FLOOR DRAINS ARE REQD.IN THE TOILET
 ROOMS PER SPC SEC.409.4.1.1.
  
 SUBMIT SANITARY AND WATER ISOMETRICS FOR
 REVIEW PER SPC SEC.104.2.1.

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-08-30 Cont ID  
Sent By tlarge Date 1999-08-30 Time 10:27 Rev Time 1.00
Received By tlarge Date 1999-08-30 Time 10:27 Sent To  
Notes
2001-01-08 00:00:00MAIN VENT IS REQUIRED FOR THE SANITARY
 SYSTEM PER SPC SEC.904.3.1.
  
 CIRCUIT AND LOOP SYSTEM SHALL COMPLY W/
 SPC 914.1.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7(PERMANENT LADDER REQD.
 OR HEATER SHALL BE INSTALLED ON GROUND
 FLOOR.)SEE DEFIN.OF READILY ACCESSIBLE
 IN SEC.202.
  
 SUBMIT COPY OF WATER USE PERMIT FOR
 IRRIG.SYSTEM PER FLA.STATUTE 373.219 AND
 NOTE ON SHT LS-3.
  
 HANDICAP TOILET STALLS IN CLUBHOUSE
 SHALL COMPLY W/F.A.C.B.C. SEC.4.17.3
 (SEE EXCEPTION:NEW CONSTRUCTION.)
  
 SUBMIT ELEVATION DETAILS FOR PLUMBING
 FIXTURES.SHOW ALL REQD. MOUNTING HEIGHTS
 PER F.A.C.B.C.
  
 WALLS AND FLOORS OF TOILET ROOMS SHALL
 COMPLY W/SBC 1204.2
  
 FLOOR DRAINS ARE REQD.IN TOILET ROOMS
 PER SPC SEC.409.4.1.1
  
 SINK SHALL BE H.C.ACESSIBLE PER
 F.A.C.B.C.SEC.4.24.1-4.24.7, 4.1.1(1)(A)
  
 TOILET ROOM BY OFFICE SHALL BE H.C.
 ADAPTABLE PER F.A.C.B.C. 4.1.3.(11).
  
 A DRINKING FOUNTAIN IS REQD. PER
 TABLE 407.1.3.OF SPC.
  
 SUBMIT OCCUPANT LOAD PER SPC SEC.407.
 COMPLIANCE W/FLA.STATUTE 553.141 MAY BE
 REQD.(POTTY PARITY).