Plan Review Details - Permit 99080163
Plan Review Stops For Permit 99080163
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-11-02 Cont ID  
Sent By jwitmer Date 1999-11-02 Time 16:17 Rev Time 99.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00HHP

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-02-17 Cont ID  
Sent By dpalmer Date 2000-02-17 Time 12:13 Rev Time 0.00
Received By dpalmer Date 2000-02-17 Time 12:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-11-02 Cont ID  
Sent By jwitmer Date 1999-11-02 Time 16:18 Rev Time 99.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
 HHP

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-11-02 Cont ID  
Sent By jwitmer Date 1999-11-02 Time 16:18 Rev Time 99.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00HHP

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-10-08 Cont ID  
Sent By ndenmark Date 1999-10-08 Time 15:33 Rev Time 0.25
Received By ndenmark Date 1999-10-08 Time 15:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-10-08 Cont ID  
Sent By ndenmark Date 1999-08-30 Time 12:28 Rev Time 0.00
Received By ndenmark Date 1999-09-10 Time 09:42 Sent To  
Notes
2001-01-08 00:00:00DENIED
 1) PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2) DUCT SMOKE DETECTORS SHALL BE TIED
 TO BUILDING FIRE ALARM FOR NOTIFICATION
 PER NFPA 90A 4-4.4.2 OR IF NO BUILDING
 FIRE ALARM SYSTEM, TIED TO HORN AND
 STROBE PER NFPA 90A 4-4.4.3

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-10-30 Cont ID  
Sent By pschmitz Date 1999-10-30 Time 09:32 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-10-30 Cont ID  
Sent By pschmitz Date 1999-10-05 Time 13:29 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:002 ND PLUMBING PLAN REVIEW
 (1) SHT A-2 SHOW A DETAIL OF SHIPS
 LADDER.
 (2)
 SHT A-7B SHOW HEIGTH OF URINAL MAX 17"
 FACBC 4.18.2
 (3) TOILTT STALLS MEN' & WOMEN'S TO
 COMPLY WITH FACBC 4.17.3 (1) EXCEPTION
 REST RM STALL TO CONTAIN AN ACCESSIBLE
 LAVATORY WITHIN IT. SHT M-2
 (4) SHT M-3 1 LAV MISSING ON ISOMETRIC
 BACK TO BACK OF W/C.
 END OF COMMENTS

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-10-30 Cont ID  
Sent By pschmitz Date 1999-08-28 Time 10:39 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00UNSAT SHT M-2
 (1) WTR HTR TOBE READLY ACCESSIBLE
 SEC 501.7 PROVIDE DETAIL OF SHIPS
 LADDER,OR PUT W/H ON GROUND FLOOR.
 (2) PAN DRAIN MIM. 1" SEC 507.8.2
 (3) TP RELIEF RUN SEPARATELY SEC 507.8.4
 (4) DWV ISOMETRIC, 2 W/C LEFT OUT.
 (5) TRAP PRIMERS ON FLR DRAINS IN
 PUBLIC REST RM'S SEC 409.4
 (6) TOILET STALLS:MEN'S & WOMEN'S
 REST RM'S TO COMPLY WITH FLORIDA
 ACCESSIBILITY CODE SEC 4.17.3 (1)
 SEE EXCEPTION.
 (7) SHT A-5 KITCHEN NOT A WORK AREA
 KITCHEN CABNETS TO BE 34" ABOVE FF
 FAC 4.24.1 & 4.24.7
 END OF COMMENTS