Plan Review Details - Permit 99080096
Plan Review Stops For Permit 99080096
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-08-20 Cont ID  
Sent By bstaples Date 1999-08-20 Time 07:53 Rev Time 5.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00CHECK LIST ON PLANS

Review Stop E ELECTRICAL
Rev No 1 Status F Date 1999-08-19 Cont ID  
Sent By dpalmer Date 1999-08-19 Time 16:01 Rev Time 1.50
Received By dpalmer Date 1999-08-19 Time 16:01 Sent To  
Notes
2001-01-08 00:00:00************DENIED***DENIED*************
  
 1) NOTE;SHOW ALL ELECTRICAL LIGHTS,
 RECEPTS,ETC. E-300
 2)NOTE:NEED FIXTURE SCHEDULE OF FIX.TO
 BE USED.
 3)NOTE:E-301 SHOW ALL ELECTRICAL WORK
 LIGHTING,RECEPTS,EQUIPMENT BEING FED
 ALL SIZES OF EQUIPMENT ETC.
 4)NOTE:E-600 RISER DIAGRAM TO BE
 COMPLETE.!!!!!ARTS:215-5 110-9
 SHOW ALL WIRE SIZES,ALL CONDUIT SIZES,
 GROUNDING ELECTRODE SYSTEM TO INCLUDE
 GROUND RODS.BLDG.STEEL,CWP.
 SHOW COMPLETE PANEL SCHEDULES WITH ALL
 SIZES OF BRKS AND WIRE FEEDS.
 AIC RATING OF ALL EQUIPMENT BEING USED
 TO BE LISTED ON ALL PANEL SCHEDULES
 FIGURED FROM FAULT CURRENT CALCULATIONS.
 AIC RATING OF FUSES,BRKS.
 SHOW ALL TRANSFORMERS AND THEIR RATINGS.
 GIVE COMPLETE LOAD CALCULATIONS OF ALL
 DETAILED LOADS.
  
 ALL THE ABOVE MUST BE SUBMITTED FOR
 APPROVAL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-08-20 Cont ID  
Sent By bstaples Date 1999-08-20 Time 07:53 Rev Time 5.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE PLAN REVIEW NOTES ON PLANS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 1999-08-17 Cont ID  
Sent By ndenmark Date 1999-08-17 Time 12:41 Rev Time 1.50
Received By bstaples Date 1999-08-17 Time 12:41 Sent To  
Notes
2001-01-08 00:00:00DENIED
 1)INFORMATION INSUFFICIENT TO REVIEW
 FOR CODE COMPLIANCE
 PROVIDE DETAILED PLANS FOR MECHANICAL
 REVIEW

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-08-18 Cont ID  
Sent By tlarge Date 1999-08-18 Time 14:40 Rev Time 1.50
Received By tlarge Date 1999-08-18 Time 14:39 Sent To  
Notes
2001-01-08 00:00:00SUBMIT OCCUPANT LOAD AND # OF EMPLOYEES
 PER SPC 407.1.3.
  
 SHTS.A1.2,A1.5,A5.0- THE TOILET ROOM
 LAYOUTS DON'T CORRELATE W/ EA.OTHER
 SPC 104.2.1.
  
 PROVIDE FULL DETAILS AND HEIGHT REQ.'S
 FOR ALL HANDICAP FIXTURES AND
 APPURTENANCES ON SHT.A5.COMPLY W/
 F.A.C.B.C.1997 ED.
  
 CLEARLY SHOW ALL HANDICAP STALL AND
 STANDARD STALL DIMENSIONS.SPC 104.2.1.
 F.A.C.B.C.
  
 DOORS ON HANDICAP STALLS SHALL NOT
 SWING INTO CLEAR FLOOR SPACE OF ANY
 FIXTURE PER F.A.C.B.C.SEC.4.17.5.
  
 SUBMIT ISOMETRIC DRAWINGS FOR SANITARY,
 STORM,POTABLE WATER,AND CONDENSATE
 SYSTEMS. SPC 104.2.1.(INCUDING ALL U/G).
  
 ALL SHEETS SHALL BE SIGNED AND SEALED
 BY A DESIGN PROFESSIONAL REGISTERED IN
 IN THE STATE OF FLA. SBC 104.2.3.
  
 TYPE AND AMOUNT OF PLBG. FIXTURES SHALL
 COMPLY W/SPC TABLE 407.
  
 NOTE:THE SUBMITTED INFORMATION IS
 INSUFFICIENT TO REVIEW FOR COMPLIANCE
 W/CODE.DETAILED PLANS ARE REQUIRED.
 SPC 104.2.1