Plan Review Details - Permit 99080096
| Plan Review Stops For Permit 99080096 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
1999-08-20 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
1999-08-20 |
Time |
07:53 |
Rev Time |
5.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | CHECK LIST ON PLANS |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
1999-08-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
1999-08-19 |
Time |
16:01 |
Rev Time |
1.50 |
| Received By |
dpalmer |
Date |
1999-08-19 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************DENIED***DENIED************* | | | | | | 1) NOTE;SHOW ALL ELECTRICAL LIGHTS, | | | RECEPTS,ETC. E-300 | | | 2)NOTE:NEED FIXTURE SCHEDULE OF FIX.TO | | | BE USED. | | | 3)NOTE:E-301 SHOW ALL ELECTRICAL WORK | | | LIGHTING,RECEPTS,EQUIPMENT BEING FED | | | ALL SIZES OF EQUIPMENT ETC. | | | 4)NOTE:E-600 RISER DIAGRAM TO BE | | | COMPLETE.!!!!!ARTS:215-5 110-9 | | | SHOW ALL WIRE SIZES,ALL CONDUIT SIZES, | | | GROUNDING ELECTRODE SYSTEM TO INCLUDE | | | GROUND RODS.BLDG.STEEL,CWP. | | | SHOW COMPLETE PANEL SCHEDULES WITH ALL | | | SIZES OF BRKS AND WIRE FEEDS. | | | AIC RATING OF ALL EQUIPMENT BEING USED | | | TO BE LISTED ON ALL PANEL SCHEDULES | | | FIGURED FROM FAULT CURRENT CALCULATIONS. | | | AIC RATING OF FUSES,BRKS. | | | SHOW ALL TRANSFORMERS AND THEIR RATINGS. | | | GIVE COMPLETE LOAD CALCULATIONS OF ALL | | | DETAILED LOADS. | | | | | | ALL THE ABOVE MUST BE SUBMITTED FOR | | | APPROVAL. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
1999-08-20 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
1999-08-20 |
Time |
07:53 |
Rev Time |
5.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SEE PLAN REVIEW NOTES ON PLANS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
1999-08-17 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-08-17 |
Time |
12:41 |
Rev Time |
1.50 |
| Received By |
bstaples |
Date |
1999-08-17 |
Time |
12:41 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED | | | 1)INFORMATION INSUFFICIENT TO REVIEW | | | FOR CODE COMPLIANCE | | | PROVIDE DETAILED PLANS FOR MECHANICAL | | | REVIEW |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
1999-08-18 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-08-18 |
Time |
14:40 |
Rev Time |
1.50 |
| Received By |
tlarge |
Date |
1999-08-18 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SUBMIT OCCUPANT LOAD AND # OF EMPLOYEES | | | PER SPC 407.1.3. | | | | | | SHTS.A1.2,A1.5,A5.0- THE TOILET ROOM | | | LAYOUTS DON'T CORRELATE W/ EA.OTHER | | | SPC 104.2.1. | | | | | | PROVIDE FULL DETAILS AND HEIGHT REQ.'S | | | FOR ALL HANDICAP FIXTURES AND | | | APPURTENANCES ON SHT.A5.COMPLY W/ | | | F.A.C.B.C.1997 ED. | | | | | | CLEARLY SHOW ALL HANDICAP STALL AND | | | STANDARD STALL DIMENSIONS.SPC 104.2.1. | | | F.A.C.B.C. | | | | | | DOORS ON HANDICAP STALLS SHALL NOT | | | SWING INTO CLEAR FLOOR SPACE OF ANY | | | FIXTURE PER F.A.C.B.C.SEC.4.17.5. | | | | | | SUBMIT ISOMETRIC DRAWINGS FOR SANITARY, | | | STORM,POTABLE WATER,AND CONDENSATE | | | SYSTEMS. SPC 104.2.1.(INCUDING ALL U/G). | | | | | | ALL SHEETS SHALL BE SIGNED AND SEALED | | | BY A DESIGN PROFESSIONAL REGISTERED IN | | | IN THE STATE OF FLA. SBC 104.2.3. | | | | | | TYPE AND AMOUNT OF PLBG. FIXTURES SHALL | | | COMPLY W/SPC TABLE 407. | | | | | | NOTE:THE SUBMITTED INFORMATION IS | | | INSUFFICIENT TO REVIEW FOR COMPLIANCE | | | W/CODE.DETAILED PLANS ARE REQUIRED. | | | SPC 104.2.1 |
|
|
|