Plan Review Details - Permit 99080075
| Plan Review Stops For Permit 99080075 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
1999-09-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
1999-09-07 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
1999-09-07 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************PROVISO******************* | | | | | | 1)NOTE:AS PER 110-9 AND 215-5,,NEED TO | | | SUBMIT AIC RATING OF ALL EQUIPMENT | | | AND BREAKERS ON RISER DIAGRAM. | | | 2) NOTE:AS PER ART 210-8-A-6 ALL RECEPTS | | | SERVING KITCHEN COUNTER SPACE ARE TO BE | | | GFI/GFI PROTECTED. | | | 3)NOTE:GROUNDING ELECTRODE CONDUCTOR | | | TO GO TO BLDG.STEEL ALSO AS PER 250-81 | | | 4)NOTE:MASTER BEDROOM OUTLETS AS REQ`D | | | PER 210-52 | | | 5)NOTE:AS PER 1996 NFPA-72 SMOKE | | | DETECTORS ARE REQ`D INSIDE AND OUTSIDE | | | BEDROOMS. | | | | | | PLEASE HAVE THE ABOVE SUBMITTED AND | | | APPROVED BEFORE FIRST ROUGH ELECTRICAL | | | INSPECTION. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
1999-08-18 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
1999-08-18 |
Time |
11:16 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
1999-08-18 |
Time |
11:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
1999-08-21 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
1999-08-21 |
Time |
10:14 |
Rev Time |
0.25 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | GAS ISOMETRIC APPR. PES |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
1999-08-21 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
1999-08-21 |
Time |
10:11 |
Rev Time |
0.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: SHT.A6 ALL FIXTURES DOWN OF W/C | | | TO BE VENTED SEC.913.2 PES |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
1999-09-17 |
|
|
Cont ID |
|
| Sent By |
jcaloger |
Date |
1999-09-17 |
Time |
16:52 |
Rev Time |
2.00 |
| Received By |
jcaloger |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
1999-08-06 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
1999-08-06 |
Time |
08:40 |
Rev Time |
0.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|