Review Stop E ELECTRICAL
Rev No 2 Status F Date 1999-10-14 Cont ID  
Sent By dpalmer Date 1999-10-14 Time 07:30 Rev Time 0.00
Received By dpalmer Date 1999-10-14 Time 07:30 Sent To  
Notes
2001-01-08 00:00:00***********2ND REVIEWPROVISO DENIED**
  
 1)NOTE: STILL NEED TO SUBMIT AIC RATING
 OF EQUIPMENT BEING INSTALLED.!!
 AIC RATINGS CAN BE FIGURED FROM DOING
 FAULT CURRENT CALCULATIONS,AS PER ARTS:
 110-9/215-5
 2)NOTE:ON ELECTRICAL RISER DIAGRAM YOU
 SHOW EQUIPMENT GROUND BEING INSTALLED
 FROM METER TO DISC..EQUIPMENT GROUNDING
 CONDUCTOR IS ONLY TO BE INSTALLED AFTER
 FIRST MEANS OF DISC.
  
 NEED TO HAVE THE ABOVE SUBMITTED FOR
 REVIEW AND APPROVAL BEFORE FIRST ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-08-16 Cont ID  
Sent By dpalmer Date 1999-08-16 Time 10:29 Rev Time 0.00
Received By dpalmer Date 1999-08-16 Time 10:29 Sent To  
Notes
2001-01-08 00:00:00*************PROVISO*******************
  
 1) NOTE:NEED TO SUBMIT AIC RATING OF
 EQUIPMENT FROM FAULT CURRENT
 CALCULATIONS.
 2) NOTE:SMOKE DETECTORS REQ`D INSIDE
 AND OUTSIDE BEDROOMS NFPA-72
  
 NEED TO HAVE SUBMITTED AND APPROVED
 BEFORE ELECTRICAL ROUGH INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-09-02 Cont ID  
Sent By jleech Date 1999-09-02 Time 10:01 Rev Time 0.50
Received By jleech Date 1999-09-02 Time 10:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-10-07 Cont ID  
Sent By tlarge Date 1999-10-07 Time 08:48 Rev Time 0.33
Received By tlarge Date 1999-10-07 Time 08:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-08-07 Cont ID  
Sent By pschmitz Date 1999-08-07 Time 10:13 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 1999-10-21 Cont ID  
Sent By jgomez Date 1999-10-21 Time 14:29 Rev Time 1.50
Received By jgomez Date 1999-10-21 Time 14:29 Sent To  
Notes
2001-01-08 00:00:00 
  
  
 CHECKLIST FOR PROVISO SUBMITTAL:
  
 1-ENTRY EGRESS DOOR TO HAVE 32" MINIMUM
 CLEAR OPENING. TABLE 1004 SBC 1997.
 2-PROVIDE PRODUCT APPROVAL AND COMPLETE
 INSTALLATION DETAILS AND SPECIFICATIONS
 FOR FRAME AND BUTT GLAZING WINDOW.
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97.
 3-PROVIDE THE DESIGN PRESSURES AT ALL
 EXTERIOR OPENINGS. SEC. 1606 SBC 1997.
 4-REVISE THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM. MEAN
 ROOF HEIGHT IS NOT CORRECT.
 5-STRUCTURAL ENGINEER OF RECORD TO SIGN
 SEAL AND DATE THE REVISED STRUCTURAL
 DRAWINGS. SEC 104.2 CITY AMENDMENTS.
 6-PROVIDE COMPLETE INSTALLATION/DETAIL
 FOR AHU'S. COMPLETELY SPECIFY ALL
 HANGERS AND CONNECTORS. SEC 104.2.2
 CITY AMENDMENTS.
 7-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS WITH SIDELITES ASSEMBLY, ROUND
 AND OVAL WINDOWS, BUTT GLAZING.
 8-20"X20"X24"HIGH CONCRETE BLOCK
 PLATFORM IS ACCEPTABLE FOR PROTECTION
 OF GWH IN GARAGE BUT NEED TO SPECIFY
 THAT CONCRETE BLOCK CELLS NEED TO BE
 FILLED (SPECIFY HOW TO BE FILLED).
 9- SEE PLANS FOR ADDITIONAL COMMENTS BY
 BUILDING PLAN REVIEWER AND THE OTHER
 TRADES COMMENTS.
 10-ENGINEERED TRUSS DRAWINGS NEED TO
 BE DESIGNED USING SBC 1997 OR ASCE 7-95
 -UPDATE ALL DETAILS AND LETTERS PACKAGE
 SUBMITTED. CITY HAS ADOPTED 1997 SBC.
 -ENGINEER TO DATE THE DAY HE SIGNS AND
 SEALS THE DOCUMENTS.
  
 NOTE: PLEASE RETURN THE REVIEWED SET OF
 DRAWINGS IN ORDER TO EXPEDITE THE
 REVIEW PROCESS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-09-02 Cont ID  
Sent By jgomez Date 1999-09-02 Time 15:19 Rev Time 3.00
Received By jgomez Date   Time   Sent To O
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-REVISE ALL ORIGINAL DRAWINGS WITH ALL
 THE CORRECTIONS.SEE PLANS FOR COMMENTS
 2-FOOTING F2 TO BE 16"MIN. DEEP AS PER
 SEC 1804.1.3 SBC 1997 AND SEC 1804.1.9
 OF CITY AMENDMENTS.
 3-SPECIFY HOW TO COMPLY WITH SECTION
 402.7 SGC 1997, REGARDING PROTECTION
 OF GAS APPLIANCES IN GARAGE.
 4-ENTRY DOOR TO HAVE 32" MINIMUM CLEAR
 OPENING.TABLE 1004 SBC 1997.
 5-PROVIDE SAFETY GLASS WHERE REQUIRED.
 SEC. 2405.2 SBC 1997.
 6-PROVIDE PRODUCT APPROVAL FOR ROUND
 WINDOWS, OVAL WINDOW, BUTT GLAZING,
 6'X7' GARAGE DOOR.
 7-STORM PANELS:
 PROVIDE COMPLETE INSTALLATION SCHEDULE
 AND KEY PLAN.
 HIGHLIGHT SPECIFIC MOUNTING DETAILS
 AND ANCHORS TO BE USED.
 8-ARCHITECT/ENGINEER TO PROVIDE THE
 DESIGN PRESSURES AT ALL EXTERIOR
 OPENINGS.
 9-SPECIFY CONSTRUCTION AT FRONT AND REAR
 PORCH CEILINGS AS PER SEC 2504.2 SBC
 1997.
 10-PROVIDE TWO COPIES OF ENGINEERED ROOF
 TRUSSES SIGNED AND SEALED.
 NOTE:TRUSS LAYOUT NEEDS TO BE SIGNED
 AND SEALED BY TRUSS ENGINEER TOO.