Plan Review Details - Permit 99071771
Plan Review Stops For Permit 99071771
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-09-03 Cont ID  
Sent By dpalmer Date 1999-09-03 Time 12:31 Rev Time 0.00
Received By dpalmer Date 1999-09-03 Time 12:31 Sent To  
Notes
2001-01-08 00:00:00*************PROVISO********************
  
 1)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1
 REQ.SMOKE DETECTORS INSIDE AND OUTSIDE
 ALL BEDROOMS IN NEW CONSTRUCTION HOMES.
 2)NOTE:AS PER ART 210--8-A-6 REQ. ALL
 RECEPTS. SERVING KITCHEN COUNTER SPACE
 TO BE GFI.
 3)NOTE AS PER ART:250-81 GROUNDING
 ELECTRODE CONDUCTOR REQ. TO BLDG.STEEL.
 4)NOTE:AS PER ART,210-52 LIVING ROOM
 REAR WALLS REQ.OUTLETS 2`,6`,12` RULE,
 PLEASE CORRECT.
 5) NOTE:AS PER ART 210-52E REQ`S OUTLETS
 AT THE FRONT AND REAR OF NEW HOUSES
 6)NOTE:AHU#1 IS SHOWN AT MASTER BEDROOM
 SIDE OF HOUSE,,NO COND.UNIT SHOWN,,
 PLEASE DRAW IN WITH DISC,AS REQ`D PER
 440-11 AND SHOW WP GFI AS PER 210-63
 7)NOTE:ELECTRICAL FOR SPA/WHIRLPOOL TUB
 IS TO BE GFI/GFI PROTECTED.
 8)NOTE:NEED TO SUBMIT AIC RATING OF ALL
 EQUIPMENT!!PANELS,DISC`S AND BREAKERS.
 AS PER ARTS;110-9 AND 215-5
 9)NOTE:AS PER ART;210-52G GARAGE GFI.
 REQ`D.
  
 ALL THE ABOVE NEEDS TO BE SUBMITTED
 AND APPROVED BEFORE FIRST ELECTRICAL
 ROUGH INSPECTION!!

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-08-07 Cont ID  
Sent By jleech Date 1999-08-07 Time 14:08 Rev Time 0.50
Received By jleech Date 1999-08-07 Time 14:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-08-09 Cont ID  
Sent By tlarge Date 1999-08-09 Time 11:40 Rev Time 0.50
Received By tlarge Date 1999-08-09 Time 11:06 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 1999-09-22 Cont ID  
Sent By fknapp Date 1999-09-22 Time 10:10 Rev Time 2.00
Received By fknapp Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO:
  
 1)PROVIDE 2 COPIES OF CURRENT PRODUCT
 APPROVAL FOR ARCH TRANSOMS.
  
 2)PROVIDE 2 COPIES OF CURRENT PRODUCT
 APPROVAL FOR BUTT GLASS.
  
 3)PROVIDE 2 COPIES OF CURRENT PRODUCT
 APPROVAL FOR GARAGE DOORS TO SATISFY
 DESIGN PRESSURES ON PLANS.
  
 4)PROVIDE STORM PANEL INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC
 MOUNTING AND ANCHORS TO BE USED.
  
 PLEASE SUBMIT PRIOR TO FIRST INSPECTION

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 1999-09-22 Cont ID  
Sent By fknapp Date 1999-09-21 Time 09:14 Rev Time 2.00
Received By fknapp Date 1999-09-13 Time 10:07 Sent To  
Notes
2001-01-08 00:00:00DENIED SEE CHECKLIST

Review Stop Z ZONING
Rev No 1 Status P Date 1999-08-02 Cont ID  
Sent By gjoyce Date 1999-08-02 Time 18:10 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***