Plan Review Details - Permit 99071415
Plan Review Stops For Permit 99071415
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-09-20 Cont ID  
Sent By bstaples Date 1999-08-17 Time 09:50 Rev Time 1.75
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00PRODUCT APPROVAL INFORMATION FOR WIND
 LOADS AND IMPACT PROTECTION OF ALL
 GLAZED OPEANINGS.
 WIND LOADS FOR ALLEXTERIOR DOORS OR
 OPEANINGS NOT GLAZED.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-09-20 Cont ID  
Sent By bstaples Date 1999-09-20 Time 07:38 Rev Time 0.50
Received By bstaples Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-09-20 Cont ID  
Sent By bstaples Date 1999-09-20 Time 07:39 Rev Time 0.50
Received By bstaples Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-09-03 Cont ID  
Sent By ndenmark Date 1999-09-03 Time 11:09 Rev Time 0.33
Received By ndenmark Date 1999-09-03 Time 11:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-09-03 Cont ID  
Sent By ndenmark Date 1999-08-13 Time 14:56 Rev Time 1.00
Received By ndenmark Date 1999-08-13 Time 14:56 Sent To  
Notes
2001-01-08 00:00:00****************FAILED******************
 1) NO A/C INFORMATION FOR SPACE
 2) NO INFORMATION ON EXHAUST FANS REQUIR
 ED FOR BATHROOMS
 3) PROVIDE INFORMATION ON ABOVE

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-09-04 Cont ID  
Sent By tlarge Date 1999-09-04 Time 08:43 Rev Time 1.00
Received By tlarge Date 1999-09-04 Time 08:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-09-20 Cont ID  
Sent By tlarge Date 1999-08-07 Time 13:02 Rev Time 2.50
Received By bstaples Date 1999-08-07 Time 13:02 Sent To  
Notes
2001-01-08 00:00:00SHT.A-4.-SIZE THE WATER RISER TO THE
 TOILET ROOMS.COMPLY W/SPC SEC.607.1
  
 FLOOR SINK IS NOT INDICATED ON THE WATER
 RISER ON SHT.A-4.
  
 CLEARLY SHOW TOTAL LINEAL FEET TO MOST
 REMOTE OUTLET ON GAS SYSTEM PER STD.GAS
 CODE SEC.305.4
  
 INDICATE TYPE OF MATERIAL TO BE UTILIZED
 FOR THE GAS PIPING SYSTEM.STD.GAS CODE
 SEC.306.
  
 INDICATE GAS SUPPLY PRESSURE ON PLANS
 AND DISTANCE OF METER FROM BUILDING PER
 STD.GAS CODE SEC. 305.2
  
 SHT.A-5-GAS LINE SHALL BE SIZED PER STD.
 GAS CODE SEC.305.4A.(TABLE DOESN'T SHOW
 3 1/2"PIPE)
  
 DRINKING FOUNTAIN SHALL COMPLY W/
 F.A.C.B.C. SEC.4.1.3(10)(A).
  
 PRIVATE TOILET ROOM SHALL BE H.C.
 ADAPTABLE PER F.A.C.B.C. SEC.4.1.3(11).
  
 SUBMIT MANUF.SHEETS FOR EPOXY PAINT TO
 ENSURE COMPLIANCE W/SBC SEC.1204.2(NON-
 ABSORBENT.)
  
 CALCULATIONS FOR COMBUSTION AIR SHALL BE
 DETERMINED FROM STD.GAS CODE SEC. 402.