Plan Review Details - Permit 99071192
Plan Review Stops For Permit 99071192
Review Stop E ELECTRICAL
Rev No 2 Status P Date 1999-09-22 Cont ID  
Sent By dpalmer Date 1999-09-22 Time 18:52 Rev Time 0.00
Received By dpalmer Date 1999-09-22 Time 18:52 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-07-30 Cont ID  
Sent By dpalmer Date 1999-07-30 Time 14:48 Rev Time 0.00
Received By dpalmer Date 1999-07-30 Time 14:47 Sent To  
Notes
2001-01-08 00:00:00****************************************
  
 NOTE:MISSING OUTLETS AS PER 210-52A
 2`6`12` RULE.
 NOTE:ALL RECEPTS. SERVING KITCHEN
 COUNTER ARE TO BE GFI/GFI PROTECTED.
 ART:210-8-A-6
 ******NOTE:SWITCHES REQ`D AS PER ART:
 210-70 FOR MEANS OF EGRESS LIGHTING IN
 LIVING ROOM/DINING ROOM.!!!
  
  
 NOTE:ALL ASBUILTS ARE TO BE SUBMITTED
 AND APPROVED BEFORE FINAL.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-04-19 Cont ID  
Sent By cthirben Date 2000-04-19 Time 10:28 Rev Time 1.00
Received By cthirben Date 2000-04-19 Time 10:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-07-31 Cont ID  
Sent By jleech Date 1999-07-31 Time 11:16 Rev Time 0.50
Received By jleech Date 1999-07-31 Time 11:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 6 Status P Date 2000-04-17 Cont ID  
Sent By tlarge Date 2000-04-17 Time 09:03 Rev Time 0.50
Received By tlarge Date 2000-04-17 Time 09:02 Sent To  
Notes
2001-01-08 00:00:00REVISED GAS DRAWING.

Review Stop P PLUMBING
Rev No 5 Status P Date 2000-03-08 Cont ID  
Sent By pschmitz Date 2000-03-08 Time 13:50 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 1999-11-17 Cont ID  
Sent By tlarge Date 1999-11-17 Time 10:32 Rev Time 0.50
Received By tlarge Date 1999-11-17 Time 10:32 Sent To  
Notes
2001-01-08 00:00:00REVISED SANITARY RISER:FIXTURE DRAINS
 DOWNSTREAM OF WATER CLOSETS SHALL BE
 VENTED PER SPC SEC.913.2.
  
 REVISION SHALL BE SIGNED AND SEALED PER
 COUNTYWIDE AMENDMENTS TO STANDRD PLBG.
 CODE SEC.104.2.3.
  
 THE SUBMITTED RISER DIAGRAM DOESN'T
 MATCH THE DIAGRAM ON THE APPROVED PLANS.

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-09-25 Cont ID  
Sent By tlarge Date 1999-09-25 Time 08:31 Rev Time 0.65
Received By tlarge Date 1999-09-25 Time 08:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-07-31 Cont ID  
Sent By dpalmer Date 1999-09-22 Time 18:52 Rev Time 0.50
Received By tlarge Date 1999-07-31 Time 09:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-07-31 Cont ID  
Sent By tlarge Date 1999-07-24 Time 08:31 Rev Time 0.65
Received By tlarge Date 1999-07-24 Time 08:31 Sent To  
Notes
2001-01-08 00:00:00ALL FIXTURES DOWNSTREAM OF WATER CLOSETS
 SHALL BE VENTED PER SPC SEC.913.2.
  
 LAYOUT OF FIXTURES IN 1ST.FLR.POWDER
 BATH ON RISER DOESN'T MATCH ARCH.FLOOR
 PLAN.SPC 104.2.1.
  
 INDICATE TYPE OF PIPE USED FOR GAS
 SYSTEM,DISTANCE TO MOST REMOTE OUTLET,
 BTU LOAD OF EACH APPLIANCE & TOTAL BTU
 LOAD ON THE SYSTEM PER STD. GAS CODE
 SEC.302, 305.2,305.4.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-09-29 Cont ID  
Sent By bstaples Date 1999-08-23 Time 17:13 Rev Time 2.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00ENGINEERING FOR ATTIC AND AIR HANDLERS
 IN TRUSSES.
 DESIGN REVIEW SIGN OFF FOR TRUSSES.
 GLAZING PROTECTION INFORMATION FOR
 WINDOWS AND DOORS.
 ENERGY SHEETS NOT SIGNED BY OWNER/AGENT.
 PROVIDE ENGINEERING DESIGN FOR
 STRUCTURAL MULLION DINING ROOM AND
 LIVING ROOM.
 NOTE: FIRE PLACE REQUIRES SEPERATE
 PERMIT.
 PROVIDE PRODUCT APPROVAL INFORMATION ON
 ROOF COVERING.
 PROVIDE PRODUCT APPROVAL INFORMATION
 FOR WIND LOADING OF WINDOWS AND DOORS.
 BBQ REQUIRES SEPERATE PERMIT.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-07-21 Cont ID  
Sent By gjoyce Date 1999-07-21 Time 08:17 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEEDS TO PAY CONCURRENCY EXEPT.