Plan Review Details - Permit 99071179
Plan Review Stops For Permit 99071179
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-05-16 Cont ID  
Sent By dpalmer Date 2000-05-16 Time 17:17 Rev Time 0.00
Received By dpalmer Date 2000-05-16 Time 17:17 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: NEEDS TO HAVE ZONING APPROVAL
 FOR SECOND METER.
  
 2)NOTE: NEED TOHAVE THE BATH CIRCUIT
 LISTED ON PANEL SCHEDULE AS PER THE REQ`
 MENTS OF 210-11-C-3 NEEDS TO BE 20AMP
 AND #12.
  
 3)NOTE: NEED TO HAVE SMOKE DETECTORS
 INSTALLED PER NFPA-72 2-2.1.1.1
 INSIDE AND OUTSIDE BEDROOMS.
  
 4)NOTE;AS PER 250-50 NEED TO HAVE THE
 GROUNDING ELECTRODE CONDUCTOR GOING TO
 THE BLDG. STEEL OF NEW STRUCTURE.PLEASE
 SHOW THIS ON THE RISER DIAGRAM. PER 215-
 -5.YOU ALSO MUST GO TO ANY METALCOLD
 WATER PIPE FOR BOND.
  
 5)NOTE: YOU SHOW THE AIC RAITN FOR THE
 PANEL BUT NOT FOR THE MAIN DISCONNECT
 SHOWN?? PLEASE SUBMIT THE AIC RATING FOR
 MAIN DISC, PER 110-9/215-5.
  
 6)NOTE: PLEASE SHOW THE OUTSIDE RECEPT
 AS GFI AS REQ`D BY 210-8
  
 7)NOTE : NEED TO SUBMIT TWO SETS OF
 PLANS.
  
  
 NEED TO SUBMIT THE ABOVE INFORMATION FOR
 REVIEW . IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-05-19 Cont ID  
Sent By cthirben Date 2000-05-19 Time 11:18 Rev Time 1.00
Received By cthirben Date 2000-05-19 Time 11:14 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
 1. RETURN AIR TO BE SHOWN ON BASEMENT
 WHAT TYPE DOOR.
 2. INDICATE THE CONDENSATE LINE TO THE
 STRUCTURE.
 3. SECOND SET OF PLANS REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-05-19 Cont ID  
Sent By tlarge Date 2000-05-19 Time 06:45 Rev Time 0.30
Received By tlarge Date 2000-05-19 Time 06:45 Sent To  
Notes
2001-01-08 00:00:00MIN.2 SETS OF PLANS REQD.PER SPC 104.2.1

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-06-08 Cont ID  
Sent By rmcdouga Date 2000-06-08 Time 08:02 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED
  
 1)PROVIDE 2 SETS OF PLANS WITH ARCHITECT
 'S WET SIGNATURE,DATE AND EMBOSSED SEAL.
 1997 STANDARD BUILDING CODE SEC.104.2.1
 AND 104.2.3
  
 2)PROVIDE 2 SETS OF ENERGY CALCULATIONS
 INCLUDING MANUAL"J"CALCS. AS REQUIRED BY
 THE FL. ENERGY CODE.
  
 3)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR SPECIFIC
 EXTERIOR WINDOWS AND DOORS TO BE USED.
  
 4)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR STORM PANELS. PROVIDE 2
 COPIES OF KEY PLAN AND INSTALLATION
 SCHEDULE INDICATING SPECIFIC ANCHORS TO
 BE USED.
  
 5)SUBMIT WIND LOAD DESIGN CRITERIA BASED
 ON 1997 SBC SEC.1606.2 OR ASCE 7-95.
 SPECIFY MEAN ROOF HEIGHT OF STRUCTURE.
  
 6)PROVIDE DETAILS OF WATERPROOFING OR
 DAMPPROOFING AS REQUIRED. SEE SECTION
 1814 OF 1997 SBC.
  
 7)PROVIDE 2 COPIES OF SURVEY SHOWING
 LOCATION OF ADDITION.
  
 8)PROVIDE DETAILS SHOWING SIZE AND
 SPACING OF ANCHOR BOLTS USED TO ATTACH
 2X8 WOOD LEDGER TO TIE BEAM AT ROOF
 TRUSSES AND SPECIFY SPECIFIC ANCHORS
 USED TO SECURE ROOF TRUSSES TO LEDGER.
  
 9)EXTERIOR STAIRS FROM POOL DECK TO
 BASEMENT DO NOT COMPLY WITH 97SBC 1007.3
 PLEASE CORRECT.
  
 10)SPECIFY WINDOW AND DOOR BUCK
 CONNECTIONS FOR WIND LOAD RESISTANCE
 97SBC 1606 AND 104.2.2.
  
 11)PROVIDE SOIL BEARING TEST PRIOR TO
 FIRST INSPECTION.
  
 12)PALM BEACH COUNTY IMPACT FEES MUST
 BE PAID TO THE COUNTY,THE PLANS STAMPED
 BY THEM AND THE RECEIPT SUBMITTED TO THE
 CITY OF WPB BEFORE A PERMIT TO CONSTRUCT
 CAN BE ISSUED.

Review Stop Z ZONING
Rev No 1 Status F Date 1999-07-19 Cont ID  
Sent By gjoyce Date 1999-07-19 Time 10:53 Rev Time 1.00
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00MUST MEET HPB CONDITIONS!!!