| 2001-01-08 00:00:00 | DENIED |
| | |
| | 1)PROVIDE 2 SETS OF PLANS WITH ARCHITECT |
| | 'S WET SIGNATURE,DATE AND EMBOSSED SEAL. |
| | 1997 STANDARD BUILDING CODE SEC.104.2.1 |
| | AND 104.2.3 |
| | |
| | 2)PROVIDE 2 SETS OF ENERGY CALCULATIONS |
| | INCLUDING MANUAL"J"CALCS. AS REQUIRED BY |
| | THE FL. ENERGY CODE. |
| | |
| | 3)PROVIDE 2 CURRENT COPIES OF METRO-DADE |
| | OR SBCCI PRODUCT APPROVALS FOR SPECIFIC |
| | EXTERIOR WINDOWS AND DOORS TO BE USED. |
| | |
| | 4)PROVIDE 2 CURRENT COPIES OF PRODUCT |
| | APPROVALS FOR STORM PANELS. PROVIDE 2 |
| | COPIES OF KEY PLAN AND INSTALLATION |
| | SCHEDULE INDICATING SPECIFIC ANCHORS TO |
| | BE USED. |
| | |
| | 5)SUBMIT WIND LOAD DESIGN CRITERIA BASED |
| | ON 1997 SBC SEC.1606.2 OR ASCE 7-95. |
| | SPECIFY MEAN ROOF HEIGHT OF STRUCTURE. |
| | |
| | 6)PROVIDE DETAILS OF WATERPROOFING OR |
| | DAMPPROOFING AS REQUIRED. SEE SECTION |
| | 1814 OF 1997 SBC. |
| | |
| | 7)PROVIDE 2 COPIES OF SURVEY SHOWING |
| | LOCATION OF ADDITION. |
| | |
| | 8)PROVIDE DETAILS SHOWING SIZE AND |
| | SPACING OF ANCHOR BOLTS USED TO ATTACH |
| | 2X8 WOOD LEDGER TO TIE BEAM AT ROOF |
| | TRUSSES AND SPECIFY SPECIFIC ANCHORS |
| | USED TO SECURE ROOF TRUSSES TO LEDGER. |
| | |
| | 9)EXTERIOR STAIRS FROM POOL DECK TO |
| | BASEMENT DO NOT COMPLY WITH 97SBC 1007.3 |
| | PLEASE CORRECT. |
| | |
| | 10)SPECIFY WINDOW AND DOOR BUCK |
| | CONNECTIONS FOR WIND LOAD RESISTANCE |
| | 97SBC 1606 AND 104.2.2. |
| | |
| | 11)PROVIDE SOIL BEARING TEST PRIOR TO |
| | FIRST INSPECTION. |
| | |
| | 12)PALM BEACH COUNTY IMPACT FEES MUST |
| | BE PAID TO THE COUNTY,THE PLANS STAMPED |
| | BY THEM AND THE RECEIPT SUBMITTED TO THE |
| | CITY OF WPB BEFORE A PERMIT TO CONSTRUCT |
| | CAN BE ISSUED. |