Plan Review Details - Permit 99071113
Plan Review Stops For Permit 99071113
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-07-28 Cont ID  
Sent By dpalmer Date 1999-07-28 Time 15:51 Rev Time 0.00
Received By dpalmer Date 1999-07-28 Time 15:51 Sent To P
Notes
2001-01-08 00:00:00***************PROVISO****************
  
 NEED TO SUBMIT AIC RATING OF EQUIP.
 BEFORE ROUGH INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-07-31 Cont ID  
Sent By jleech Date 1999-07-31 Time 09:59 Rev Time 0.50
Received By jleech Date 1999-07-31 Time 09:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-02-09 Cont ID  
Sent By tlarge Date 2000-02-09 Time 05:53 Rev Time 0.33
Received By tlarge Date 2000-02-09 Time 05:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-09-10 Cont ID  
Sent By tlarge Date 1999-09-10 Time 09:19 Rev Time 0.50
Received By tlarge Date 1999-09-10 Time 09:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-09-10 Cont ID  
Sent By dpalmer Date 1999-07-28 Time 15:51 Rev Time 0.65
Received By tlarge Date 1999-07-29 Time 16:44 Sent To  
Notes
2001-01-08 00:00:00 
 MAX.OF 2 WATER CLOSETS PERMITTED ON 3"
 BLDG.DRAIN.
  
 MIN.SIZE OF DRAINAGE PIPING UNDERGROUND
 SHALL BE 2".SPCSEC.714.4.
  
 FIXTURES DOWNSTREAM OF WATER CLOSETS
 SHALL BE VENTED PER SPC SEC.913.2.
  
 KIT.SINK AND LAV.ARE NOT VENTED.SPC .
 901.2.
  
 TUBS AND SHOWERS UPSTREAMOF WATER
 CLOSETS ARE NOT VENTED.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 1999-09-10 Cont ID  
Sent By jgomez Date 1999-09-10 Time 13:46 Rev Time 1.00
Received By jgomez Date 1999-09-10 Time 13:46 Sent To O
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-REAR ELEVATION EXCEEDS THE MAXIMUM
 PERCENTAGE OF OPENINGS ALLOWED. TABLE
 600 SBC 1997. REVISE AS REQUIRED.
 2-PROVIDE COMPLETE FRAMING DETAILS FOR
 BAY WINDOWS. SPECIFY ALL CONNECTORS AND
 FRAMING MEMBERS.SEC. 104.2.2 CITY AMEND
 3-PROVIDE PRODUCT APPROVALS FOR: ROOF
 TILE, OVAL WINDOWS, ENTRY DOORS, FIXED
 WINDOW ABOVE ENTRY DOORS.
 4-PROVIDE CEILING FANS AS REQUIRED FOR
 CREDIT TAKEN IN ENERGY CALCULATIONS.
 5-SPECIFY FOOTING FOR BEARING WALL
 BETWEEN GARAGE AND LAUNDRY AREA.
 SEC. 104.2.2 CITY AMENDMENTS.
 * WHAT IS THE WIDTH OF FOOTING A?
 * SPECIFY SIZE AND REINFORCEMENT OF
 CONCRETE EDGE AT REAR PORCH SLAB.
 6-SPECIFY LOCATION AND DRAFSTOPPING
 MATERIAL AT SECOND FLOOR. SEC. 2305.2
 7-PROVIDE COMPLETE DETAILS/SECTIONS THRU
 STAIRS. SPECIFY ALL FRAMING MEMBERS.
 SEC. SEC. 104.2.2 CITY AMENDMENTS.
 * SPECIFY THE RISER/TREAD RATIO. SEC.
 1007.3 SBC 1997.
 * PROVIDE FIREBLOCKING. SEC. 2304.1 SBC
 8-COMPLETELY SPECIFY THE CEILING
 CONSTRUCTION AT FRONT AND REAR PORCHES
 AS PER SEC.2504.2 SBC 1997 AND ASTM
 C926 AND ASTM C1063.
 9-SEE PLANS FOR ADDITIONAL COMMENTS.
 10-PROVIDE COMPLETE SPECIFICATIONS AND
 MOUNTING DETAILS FOR AHU'S. SPECIFY
 ALL FASTENERS. SEC. 104.2.2 CITY AMENDM
 11-PROVIDE COMPLETE SPECIFICATIONS AND
 SECTIONS/DETAILS FOR BUTT GLAZING AS
 PER SECTIONS 2405.3 AND 2406 SBC 1997.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-09-10 Cont ID  
Sent By jgomez Date 1999-09-07 Time 18:49 Rev Time 2.00
Received By jgomez Date   Time   Sent To O
Notes
2001-01-08 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO THE COUNTY.
 2-ARCHITECT OF RECORD TO SIGN AND SEAL
 ALL DRAWINGS. SEC. 104.2.3 OF CITY
 AMENDMENTS TO SBC 1997.
 3-PROVIDE COMPLETE FRAMING DETAILS FOR
 BAY WINDOWS. SPECIFY ALL CONNECTORS.
 4-PROVIDE PRODUCT APPROVAL FOR: ROOF
 TILE, OVAL WINDOWS, ENTRY DOORS, FIXED
 WINDOW ABOVE ENTRY DOORS.
 5-PROVIDE CEILING FANS AS REQUIRED BY
 CREDIT TAKEN IN ENERGY CALCULATIONS.
 6-*PROVIDE FOOTING FOR BEARING WALL
 BETWEEN GARAGE AND LAUNDRY AREA.
 *WHAT IS THE WIDTH OF FOOTING A?.
 *SPECIFY SIZE AND REINFORCEMENT OF
 CONCRETE EDGE AT REAR PORCH SLAB.
 7-PROVIDE DRAFSTOPPING AT SECOND FLOOR.
 SEC. 2305.2.2 SBC 1997.
 8-*PROVIDE COMPLETE DETAILS/SECTIONS
 THRU STAIRS. SPECIFY ALL FRAMING
 MEMBERS. SEC. 104.2.2 CITY AMENDMENTS.
 *SPECIFY THE RISER/TREAD RATIO.
 SEC. 1007.3 SBC 1997.
 *PROVIDE FIREBLOCKING. SEC. 2305.1
 SBC 1997.
 9-SPECIFY THE CEILING CONSTRUCTION AT
 FRONT AND REAR PORCHES. SEC. 2504.2
 SBC 1997 (ASTM C926 AND ASTM C1063).
 10-REVISE ENERGY CALCULATIONS. OWNER AND
 CONTRACTOR IS RJS BUILDER,NOT PAPARONE
 HOMES.
 *THE CLIMATE ZONE IS #8, NOT SOUTH.
 SOUTH IS REFERING TO THE REGION.
 11-SEE PLANS FOR ADDITIONAL COMMENTS.
 12-REAR ELEVATION EXCEEDS THE MAXIMUM
 PERCENTAGE OF OPENINGS ALLOWED. TABLE
 600 SBC 1997. REVISE OPENINGS AS
 REQUIRED.
 13-PROVIDE COMPLETE SPECIFICATIONS AND
 MOUNTING DETAILS FOR AT AHU ROOM.
 SEC. 104.2.2 CITY AMENDMENTS.
 14-PROVIDE COMPLETE SPECIFICATIONS AND
 SECTIONS/DETAILS FOR BUTT GLAZING AS
 PER SECTIONS 2405.3 AND 2406 SBC 1997.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-07-19 Cont ID  
Sent By gjoyce Date 1999-07-19 Time 08:13 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***