Plan Review Details - Permit 99070990
Plan Review Stops For Permit 99070990
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 1999-11-02 Cont ID  
Sent By hpiskura Date 1999-11-02 Time 10:40 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 1999-09-01 Cont ID  
Sent By hpiskura Date 1999-09-01 Time 12:18 Rev Time 16.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-01-30 Cont ID  
Sent By dpalmer Date 2001-01-30 Time 08:53 Rev Time 0.00
Received By dpalmer Date 2001-01-30 Time 08:52 Sent To  
Notes
2001-01-30 00:00:00OK FOR WATER SCHEMATIC DRAWING.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-10-17 Cont ID  
Sent By dpalmer Date 2000-10-17 Time 10:51 Rev Time 0.00
Received By dpalmer Date 2000-10-17 Time 10:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-07-31 Cont ID  
Sent By dpalmer Date 2000-07-31 Time 07:58 Rev Time 0.00
Received By dpalmer Date 2000-07-31 Time 07:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-11-02 Cont ID  
Sent By hpiskura Date 1999-11-02 Time 10:44 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 1999-12-01 Cont ID  
Sent By hpiskura Date 1999-12-01 Time 09:07 Rev Time 0.00
Received By dlauderm Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO: ENGINEER MUST PROVIDE SIGNED
 AND SEALED HYDRAULIC CALCULATIONS AND
 FOR THE IMPERVIOUS AREA. THIS IS A TEST

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-11-02 Cont ID  
Sent By hpiskura Date 1999-11-02 Time 10:41 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-02-05 Cont ID  
Sent By ndenmark Date 2001-02-05 Time 11:42 Rev Time 0.33
Received By ndenmark Date 2001-02-05 Time 11:42 Sent To  
Notes
2001-02-05 00:00:00SUBMITTED AFTER ALL WORK DONE AT SITE
 CONDITIONAL C.O. PENDING HOOD FINAL
 ALREADY EXISTS

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-07-27 Cont ID  
Sent By cthirben Date 2000-07-27 Time 07:36 Rev Time 1.00
Received By cthirben Date 2000-07-27 Time 07:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-11-03 Cont ID  
Sent By ndenmark Date 1999-11-03 Time 07:32 Rev Time 0.33
Received By ndenmark Date 1999-11-03 Time 07:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-11-03 Cont ID  
Sent By ndenmark Date 1999-08-16 Time 14:26 Rev Time 0.50
Received By ndenmark Date 1999-08-16 Time 14:26 Sent To  
Notes
2001-01-08 00:00:00CORRECTED BY REVISION
 1) SHOW TERMINATION OF FUME HOOD EXHAUST
 2) PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 3) FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 REQUIRED WITH NOTIFICATION BY BLDG. FIRE
 ALARM SYSTEM
 4) BATHROOM EXHAUST TERMINATION TO BE
 MINIMUM 10' FROM WINDOWS, DOORS, AND OUT
 SIDE AIR INTAKE. PROVIDE DETAILS FOR OUT
 SIDE AIR INTAKE AND EXHAUST FAN TERMINA-
 TION

Review Stop P PLUMBING
Rev No 8 Status F Date 2000-10-20 Cont ID  
Sent By tlarge Date 2000-10-20 Time 08:49 Rev Time 0.50
Received By tlarge Date 2000-10-20 Time 08:49 Sent To  
Notes
2001-01-08 00:00:001)LP BRANCH LINE TO LABORATORY SHALL BE
 EQUIPPED W/S.O.V.
  
 2)SHOW LOCATION OF 2ND.STAGE REGULATOR.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 7 Status P Date 2000-09-16 Cont ID  
Sent By pschmitz Date 2000-09-16 Time 15:07 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEWPROVISO
 (1) SEE ATTACHED SHT FOR L-P GAS TANK &
 LINES,SHOWING REGULATOR 1ST & 2ND STAGE
 LOCATION.
 (2) GAS PIPING IS UNDER BUILDING NOT
 SLAB.
 (3) A SEPERATE PERMIT IS REQUIRED FOR
 TANK RELOCATION AND INSTALLATION.
 (4) SEPERATE PERMIT FOR THE PIPING FROM
 THE BUILDING TO THE TANK IF NOT DONE
 BY GAS CO.AND LICENSED FOR L-P GAS.
 END OF COMMENTSPAUL SCHMITZ

Review Stop P PLUMBING
Rev No 6 Status P Date 2000-09-05 Cont ID  
Sent By tlarge Date 2000-09-05 Time 18:25 Rev Time 1.00
Received By pschmitz Date 2000-09-05 Time 17:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2000-08-22 Cont ID  
Sent By tlarge Date 2000-08-22 Time 16:01 Rev Time 0.50
Received By pschmitz Date 2000-08-22 Time 16:01 Sent To  
Notes
2001-01-08 00:00:00SUBMIT PLANS THAT CLEARLY REFLECT ALL
 THE CHANGES TO THE PLUMBING AND GAS
 SYSTEMS.THERE ARE TOO MANY NOTATIONS AND
 DELETIONS TO PERFORM A PROPER REVIEW.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 CALL 561-659-8096 EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 4 Status F Date 2000-08-04 Cont ID  
Sent By pschmitz Date 2000-08-04 Time 10:17 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVISION DATED 07-19-2000 PLUMBING
 (1) NOT APPROVED,DOES NOT SHOW AS BUILT.
 (2) EACH BUILDING HAS A SEPERATE SANITAR
 SEWER LATERIAL.
 (3) GAS PIPING IS INSTALLED UNDER THE
 BUILDING,NOT ABOVE CEILING AS PLANS
 SHOW.
 (3) SHT P2.03 LAW ENFORCEMENT BUILDING,
 RM #137 MOP SINK LOCATION ?
 (4) MAIN WATER SUPPLY, SHOW WHERE PIPE
 SIZES CHANGE.
 (5) WATER HEATERS TO BE READLY ACCESSIBL
 SPC 94 SEC 501.7, IF LOCATED ABOVE 1ST
 FLOOR, A FIXED SHIPS LADDER WITH A
 WORKING PLATFORM IS REQUIRED.
 END OF COMMENTS

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-11-08 Cont ID  
Sent By tlarge Date 1999-11-08 Time 09:59 Rev Time 2.00
Received By tlarge Date 1999-11-08 Time 09:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 1999-11-02 Cont ID  
Sent By tlarge Date 1999-11-02 Time 15:15 Rev Time 2.00
Received By tlarge Date 1999-11-02 Time 15:14 Sent To  
Notes
2001-01-08 00:00:00NUMBER OF REQD.SANITARY FACILITIES SHALL
 COMPLY W/SPC TABLE 407.
  
 CAPACITY OF LP TANK,TYPE OF PIPING,AND
 SOURCES OF IGNITION IN PROXIMITY TO LP
 TANK SHALL BE SHOWN ON THE PLANS PER
 NFPA 58.
  
 SANITARY SYSTEM FOR ADMIN.BLDG.TO COMPLY
 W/COUNTYWIDE AMENDMENTS TO STD.PLBG.CODE
 SEC.911.1.1.(ONLY FIXTURE DRAINS
 PERMITTED ON WET VENTS.)
  
 CLARIFY SIZE OF BLDG.SEWER.(CIVILS SHOW
 6" AND PLBG.DWGS.SHOW 4".)

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-07-31 Cont ID  
Sent By tlarge Date 1999-07-31 Time   Rev Time 3.50
Received By pschmitz Date 1999-07-31 Time 06:44 Sent To  
Notes
2001-01-08 00:00:00SUBMIT OCCUPANT LOAD OF EACH BUILDING
 TO ENSURE COMPLIANCE W/TABLE 407 FOR
 MINIMUM PLBG.FIXTURE REQ'S.
  
 CAPACITY AND E.F RATING OF WATER HEATERS
 ARE REQ'D.PER FLA.ENERGY CODE SEC.103.2
  
 FLOOR DRAINS ARE REQ'D. IN THE TOILET
 ROOMS PER SPC SEC.409.4.1.1.
  
 WALLS IN TOILET ROOMS SHALL COMPLY W/
 SBC SEC.1204.2
  
 KITCHEN /BREAKROOM SINKS IN EACH
 BUILDING SHALL COMPLY W/F.A.C.B.C.SEC.
 4.24.1-4.24.7.
  
 DRINKING FOUNTAINS ARE REQ'D.IN EACH
 BUILDING PER SPC TABLE 407.
  
 SHT.A5.04-CLEARLY SHOW ALL MOUNTING
 HEIGHT DIMENSIONS FOR HANDICAP FIXTURES.
 COMPLY W/F.A.C.B.C.
  
 SHOWER DIMENSIONS SHALL COMPLY W/
 F.A.C.B.C.SEC.4.21.2.
  
 CONTROLS IN HANDICAP SHOWERS SHALL
 COMPLY W/F.A.C.B.C.SEC.4.21.5.
  
 CIVIL DRAWINGS NOTE SANITARY SEWER AS 6"
 AND SHT.P2.01 NOTES 8".CLARIFY.
  
 FALL OF BUILDING DRAIN/SEWER SHALL
 COMPLY W/TABLE 714.1(MIN.SLOPE IS 1/8"
 PER FT.SEE SHT.P2.01.)
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 610.4.1, 610.4.2.
  
 MAX.TEMP.OF WATER TO RESTROOMS SHALL
 NOT EXCEED 110 DEGREES F.PER F.E.C. SEC.
 412.1ABCD.2.3.2.
  
  
  
  
  
 SUBMIT COMPLETE GAS DRAWING FOR REVIEW.
 INDICATE TYPE OF PIPING,BTU LOAD,
 LOCATION AND CAPACITY OF LP TANK,
 SOURCES OF IGNITION IN PROXIMITY TO TANK
 COMPLY W/STD.GAS CODE SEC.104.2.1,NFPA
 58.
  
 AN INTERCEPTOR SHALL BE INSTALLED ON THE
 DISCHARGE LINE FROM THE INDUSTRIAL DRAIN
 BY THE MAINTENANCE FACILITY PER SPC SEC.
 1004.1.CLARIFY NATURE OF EFFLUENT AND
 OPERATIONS PERFORMED IN THIS AREA.SPC
 104.2.1.
  
 SIZE THE WATER RISERS IN THEIR ENTIRETY.
 SPC 104.2.1. (MAX.OF 2 FIXTURES ON 1/2"
 C.W.& 4 FIXTURES ON 1/2" H.W.PER COUNTY-
 WIDE AMENDMENTS SEC.607.7.
  
 SIZE ALL SECTIONS SANITARY RISERS.SPC
 SEC.104.2.1.
  
 DRINKING FOUNTAIN IN ADMIN.BLDG. NOT
 PROPERLY VENTED.SPC SEC.901.2.SHT.P4.01
  
 SANITARY FOR FISH AND GAME BLDG.DOESN'T
 CONNECT TO DRAINAGE SYSTEM.SPC 104.2.1.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-11-02 Cont ID  
Sent By hpiskura Date 1999-11-02 Time 10:43 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***