Plan Review Details - Permit 99070921
Plan Review Stops For Permit 99070921
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By ndenmark Date 1999-08-03 Time 14:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-07-19 Cont ID  
Sent By ndenmark Date 1999-07-19 Time 10:59 Rev Time 0.25
Received By ndenmark Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-07-19 Cont ID  
Sent By ndenmark Date 1999-07-19 Time 10:59 Rev Time 0.50
Received By ndenmark Date 1999-07-19 Time 10:59 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1) EXHAUST HOOD TERMINATION TO BE MIN.
 40" ABOVE ROOF.
 2) MINIMUM SLOPE FOR EXHAUST DUCT TO BE
 1 INCH PER FOOT PER 1994 SMC 505.4
 3) CLEANOUTS TO BE PER 1994 SMC 505.5.1
 4) CLEARANCE TO INSIDE OF ENCLOSURE FROM
 DUCT TO BE MIN. 6" PER 1994 SMC 505.9