| Plan Review Stops For Permit 99070843 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2002-07-30 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-07-30 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-07-30 00:00:00 | BLD REVISION DATED 4/2/02 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2001-05-15 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-05-15 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-05-15 00:00:00 | FOR WALL TYPE REVISIONS 5/1/01 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2001-02-20 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-02-20 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-02-20 00:00:00 | REVISIONS DATED 1/5/01 | | | THE SMALL MEETING ROOM SHOWN ON SHEET | | | A201.4 DOES NOT HAVE THE EXIT DOORS A | | | DISTANCE APART EQUAL TO OR GREATER THAN | | | 1/2 THE DIAGONAL DISTANCE OF THE ROOM | | | AS REQUIRED BY SBC 1004.1.4.PLEASE | | | REVISE AS NECESSARY. | | | | | | SECTION 3/A505.SHOW THE DESIGN LOADS | | | FOR THE CATWALK.SEE SBC 1604.8. | | | | | | THE DOOR SCHEDULES DO NOT SHOW RATED | | | ENTRANCE DOORS FOR THE APARTMENTS.SEE | | | SBC 704.1.1 AND SBC 705.1.2 | | | | | | SHEET A203 DOES NOT CLEARLY SHOW THE | | | AISLE AND SEATING DIMENSIONS, OR | | | PLACEMENT OF HANDRAILS TO DETERMINE | | | COMPLIANCE WITH SBC 1019.9 AND SBC | | | 1019.10. | | | | | | THE RISER MOUNTED SEATING MUST COMPLY | | | WITH SBC 1019.10.3.2. FOR ROWS HAVING > | | | 14 SEATS. | | | | | | SEE SBC 1007.5.7 FOR THE HANDRAIL | | | SPACING REQUIREMENTS ON THE VOMITORY | | | STAIRS. | | | | | | PERMIT FEES MUST BE PAID TO THE CITY FOR | | | THE NEW AND ADDED WORK. | | | | | | HAROLD PISKURA |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-03-08 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-03-08 |
Time |
09:41 |
Rev Time |
99.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
1999-10-22 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
1999-10-22 |
Time |
13:02 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
1999-08-18 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
1999-08-12 |
Time |
09:36 |
Rev Time |
99.00 |
| Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NOTES | | | AS PER HAROLD P. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
P |
Date |
2002-10-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-10-31 |
Time |
14:09 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2002-10-31 |
Time |
14:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
F |
Date |
2002-10-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-10-24 |
Time |
08:55 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2002-10-24 |
Time |
08:55 |
Sent To |
|
|
| Notes |
| 2002-10-24 00:00:00 | ************** UNSAT *********** | | | | | | 1)NOTE: PLEASE NOTE LRU-DIST IS SHOWN | | | AS MLO. PLEASE NOTE THAT PER 240-21 | | | MUST TERMINATE IN A SINGLE OCP DEVICE. | | | IT IS NOTED THAT OTHER PANELS WERE | | | CHANGED TO HAVE MCB. | | | | | | 2)NOTE: PLEASE NOTE PLANS HAVE BEEN | | | COMPLETELY PRINTED OUT FOR REVIEW AND | | | PANEL "SS" IS MISSING FROM PANEL SCHED- | | | -ULES? PLEASE SUBMIT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMAITON FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
F |
Date |
2002-10-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-10-18 |
Time |
07:26 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-10-18 |
Time |
07:26 |
Sent To |
|
|
| Notes |
| 2002-10-18 00:00:00 | ************ ON HOLD *********** | | | | | | WAITING FOR PAID BZ. TO PROCESS PLANS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2002-06-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-06-17 |
Time |
06:37 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-06-14 |
Time |
05:58 |
Sent To |
|
|
| Notes |
| 2002-06-17 00:00:00 | ******************* UNSAT ************* | | | 1)NOTE: PLEASE NOTE THAT PLANS SUBMITTED | | | AS "AS-BUILTS" ARE NOT COMPLETE. | | | PLEASE NOTE PANEL SCHEDULE THAT ARE NOT | | | COMPLETE. | | | PLEASE NOTE RISER DIAGRAM IS SUBMITTED | | | AS COMPLETE AND THERE IS A MISSING SEC | | | THAT GOES WITH E 902? PLEASE NOTE THAT | | | THE ONE- LINE SHOWN ON E902.1 IS MISSING | | | SOME ITEMS THAT ARE SHOW ON OTHER RISER | | | PLEASE CORRELATE AND COMPLETE PLANS FOR | | | SUFFICENT ELECTRICAL REVIEW. | | | | | | 2)NOTE: PLEASE NOTE THAT THERE ARE SOME | | | PANELS/DIST PANELS ON THE LOAD SIDE | | | OF TRANSFORMERS THAT HAVE NO MAINS | | | SHOWN? PLEASE SEE 240-21 FOR TERMINATION | | | IN A SINGLE SET OF OCP. | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2001-04-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-04-17 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-16 |
Time |
22:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2001-02-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-02-14 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-02-14 |
Time |
12:17 |
Sent To |
|
|
| Notes |
| 2001-02-14 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SUBMIT A RISER SHEET | | | WITHCORRELATING INFORMATION SHOWING | | | CLARIFICATION ON LOCATIONS OF | | | TRANSFORMERS. | | | WE NEED CLARIFICATION ON HOW FAR AWAY | | | PANELS/ AND DISCONNECTS ARE. THIS IS | | | NEEDED FOR SECONDARY(S) OF ALL | | | TRANSFORMERS IN THE BLDG. ALL MUST MEET | | | 240-21-C 2&3 | | | | | | 2)NOTE: PLEASE NOTE, ON SHEET E902 YOU | | | ARE SHOWING TWO LOCATIONS WHERE | | | TRANSFORMERS ARE BEING TAPPED AND GOING | | | TO GUTTERS AND BEING TAPPED AGAIN, | | | PLEASE NOTE | | | THAT THIS VIOLATES 240-21. | | | | | | PLEASE NOTE THAT ALL THE REQUIREMENTS | | | FOR TAPPED CONDUCTORS NEED TO BE MET. | | | FOR 10` AND 25` | | | CONDUCTORS FEEDING "LRU" DIST. PANEL | | | ARERATED FOR LEESTHAN THE 600A RATED | | | BOARD. | | | | | | 3)NOTE: ALSO PLEASE NOTE THAT ALL THE | | | REQUIREMENTS FOR 110-26 AND 384-7 NEED T | | | O BE MET. PANELS AND TRANSFORMERS ARE | | | SHOWN IN STORAGE AND CLEANING CLOSETS. | | | THIS IS VIOLATES THE ABOVE MENTIONED ART | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS PLEAS | | | E CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | OR | | | JAKE LEAHY | | | CHEIF ELECTRICAL INSPECTOR | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-02-02 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2000-02-02 |
Time |
13:24 |
Rev Time |
1.00 |
| Received By |
jleahy |
Date |
2000-02-02 |
Time |
13:11 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1- DISCONNECT NEEDED FOR TRANSFER SWITCH | | | IF IT IS REMOTE FROM THE GENERATOR. | | | ONLY ON THE EMERGENCY SIDE, NORMAL | | | HAS ONE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
1999-10-18 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
1999-10-18 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2000-02-02 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)NEED LOAD CALCULATIONS ON PANELS TO | | | REFLECT CONTIN LDS,MOST OF THE | | | PANELS SHOW 4 TO 8 AMPERES FOR THE | | | LIGHTING IN EACH PANEL.THIS CAN,T | | | BE CORRECT WHEN THERE IS LARGE | | | LIGHTING LOADS IN THESE PANELS | | | | | | 2)PANEL LPL-8SHOW 8.32 AMPS FOR THE | | | CONTINUOUS LOAD FACTOR WHEN THERE | | | IS 15,600VA WORTH OF LOAD3900 | | | VA CONTINUOUS LOAD CONTRIBUTION | | | COMES OUT AT 16.25 AMPSPLEASE | | | CHECK ALL PANEL SCHEDULES FOR THE | | | CORRECT LOADS! | | | | | | 3)NEW MAIN 3000 AMPERES SHOW LOAD | | | CALCULATION FOR THIS SWITCH. | | | | | | 4)AT NEWTRANSFER SWITCH YOU NEED A | | | DISCONNECT FOR THE LINE SIDE OF THE | | | EMERGENCY FEED AT TRANSFER SWITCH!! | | | | | | 5)NOTE #5 WAS LISTED ON THE ORIGINAL | | | CHECK LIST!YOUR RISER DOES NOT | | | REFLECT THIS 225-8, 230-72 | | | | | | 6)THE CITY NEEDS A ONE LINE DIAGRAM | | | FOR THE RISER THAT WILL BE USED | | | SHOW WHAT THE FINISHED RISER WILL | | | LOOK LIKE. | | | | | | 7)ACCORDING TO THE PLANS YOU SHOW AN | | | EXISTING RISER WITH THE NOTE TO BE | | | REMOVED UNLESS NOTED,DPP1 SHOULD BE | | | REMOVED BUT SHOWS UP ON NEW RISER | | | PLEASE FIXSEE NOTE #6 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2002-12-18 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-12-18 |
Time |
19:57 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-12-18 |
Time |
19:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2002-07-16 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-10 |
Time |
18:46 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-07-16 |
Time |
14:43 |
Sent To |
|
|
| Notes |
| 2002-07-16 00:00:00 | 1) KNOX-BOXES WILL BE REQUIRED AT | | | VEHICULAR GATES. | | | | | | 2) OPENINGS THRU SECURITY GATES MUST | | | BE AT LEAST TWENTY (20) FEET IN CLEAR | | | WIDTH IN WHICH FIRE RESCUE VEHICLES | | | ARE EXPECTED TO PASS THRU. | | | | | | 3) BUILDING ADDRESS IS REQUIRED WITH | | | AT LEAST SIX (6) INCH HIGH NUMERALS. | | | YARD SIGN SHOULD DISPLAY ADDRESS SINCE | | | THE BUILDING SITS SO FAR OFF THE ROAD | | | UNLESS AN ALTERNATIVE LOCATION IS | | | AGREED UPON. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2001-08-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-06 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-06 |
Time |
15:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2001-05-02 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-05-02 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-05-02 |
Time |
15:48 |
Sent To |
|
|
| Notes |
| 2001-05-02 00:00:00 | 1) DUCT SMOKE DETECTORS REQUIRED IN ALL | | | AIR HANDLING SYSTEMS OVER 2000 CFM AND | | | SERVING MEANS OF EGRESS AREAS. WHEN | | | ACTIVATED, THE AIR HANDLING EQUIPMENT | | | IS TO SHUT DOWN AND CAUSE THE FIRE | | | ALARM SYSTEM TO ACTIVATE. | | | 2) PROVISIONS ARE TO BE MADE FOR AT | | | LEAST TWO HANDICAPPED PERSONS. | | | 3) GAS INSTALLATION TO COMPLY WITH | | | NFPA 54. | | | 4) FIRE DAMPERS TO COMPLY WITH UL 555. | | | ALL FIRE DAMPERS ARE TO BE DROP TESTED | | | AFTER INSTALLATION. | | | 5) SEATING INSTALLATION SUBJECT TO THE | | | APPROVAL OF THE FIRE PREVENTION BUREAU. | | | 6) DOORS SUBJECT TO AN OCCUPANCY OF 100 | | | OR MORE PERSONS SHALL BE EQUIPPED WITH | | | PANIC HARDWARE. FIRE DOORS SHALL BE | | | EQUIPPED WITH FIRE EXIT PANIC HARDWARE. | | | 7) PLEASE CONTACT THIS OFFICE TO DISCUSS | | | SEATING ARRANGEMENT ON THE MAIN FLOOR | | | OF THE BUILDING. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-02-08 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-02-08 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-02-08 |
Time |
14:28 |
Sent To |
|
|
| Notes |
| 2001-02-08 00:00:00 | 1) NEW BRICK PAVERS ON EXISTING CONCRETE | | | STEPS ARE TO BE SLIP RESISTANT. | | | 2) PLEASE DEFINE BABY ROOM 1617. WHAT | | | WILL IT BE USED FOR. | | | 3) BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWINGS. BUILDING ADDRESS TO | | | COMPLY WITH CITY CODE REQUIREMENTS. | | | 4) ALL EXIT DOORS IN THE REQUIRED MEANS | | | OF EGRESS SUBJECT TO AN OCCUPANCY OF | | | 100 OR MORE PERSONS SHALL BE EQUIPPED | | | WITH PANIC HARDWARE. | | | 5) SUFFICIENT EMERGENCY LIGHTING AND | | | ILLUMINATED EXIT SIGNS ARE TO BE PRESENT | | | WITHIN THE BUILDING. | | | 6) PLEASE PROVIDE MORE DETAILS ON | | | FIXED SEATING PLANNED FOR THE GROUND | | | FLOOR. | | | 7) DUCT SMOKE DETECTION REQUIRED IN ALL | | | AIR HANDLING SYSTEMS. | | | | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-03-08 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-03-08 |
Time |
09:44 |
Rev Time |
99.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO ON PLANS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-12-10 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-10 |
Time |
18:46 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-12-10 |
Time |
18:46 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
P |
Date |
2002-06-11 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-11 |
Time |
15:08 |
Rev Time |
1.30 |
| Received By |
pkrauss |
Date |
2002-06-11 |
Time |
15:08 |
Sent To |
|
|
| Notes |
| 2002-06-11 00:00:00 | AS BUILTSMECH PERMIT 99070895 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2002-01-16 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-01-16 |
Time |
13:19 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-01-16 |
Time |
12:56 |
Sent To |
|
|
| Notes |
| 2002-01-16 00:00:00 | | | | PROVISO: | | | | | | DUCT SHALL HAVE SMOOTH INTERIOR FINISH | | | WITH JOINTS RUNNING IN THE DIRECTION OF | | | THE AIR FLOW. | | | | | | NO SCREWS SHALL PENETRATE INTERIOR. | | | | | | COMPLY WITH 1997 SMC 509 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2001-07-30 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-07-30 |
Time |
11:17 |
Rev Time |
1.20 |
| Received By |
pkrauss |
Date |
2001-07-30 |
Time |
11:17 |
Sent To |
|
|
| Notes |
| 2001-07-30 00:00:00 | *******************PROVISO************** | | | | | | | | | HOW IS GAS FIRED POOL HEATER BEING | | | SUPPLIED.PLEASE INDICATE ON PLANS | | | WHAT SIZE PIPE IS SUPPLYING POOL HEATER. | | | | | | PLEASE SUBMIT MANUFACTURER DATA ON POOL | | | HEATER. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2001-05-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-05-21 |
Time |
13:33 |
Rev Time |
2.00 |
| Received By |
pkrauss |
Date |
2001-05-21 |
Time |
13:33 |
Sent To |
|
|
| Notes |
| 2001-05-21 00:00:00 | ********************PROVISO************* | | | | | | | | | PLEASE PROVIDE CALCULATIONS FOR O.A. IN | | | THE BOILER ROOM (DID THEY CHANGE BY | | | ADDING ANOTHER BOILER?) | | | | | | ANY EXISTING FIRE DAMPERS NEED TO BE | | | IDENTIFIED ON PLAN AND WILL BE | | | INSPECTED/TESTED. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-01-28 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-01-28 |
Time |
08:05 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-01-28 |
Time |
08:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
1999-10-13 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-10-13 |
Time |
11:14 |
Rev Time |
2.00 |
| Received By |
ndenmark |
Date |
1999-10-13 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | 1) ALL DUCTS PENETRATING RATED WALLS TO | | | BE PROTECTED BY FIRE DAMPERS | | | 2)INCLUDE CALCULATIONS FOR BOILER COMB- | | | USTION AIR IN APPROVED DOCUMENTS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
1999-10-13 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-08-03 |
Time |
12:52 |
Rev Time |
5.00 |
| Received By |
ndenmark |
Date |
1999-08-03 |
Time |
12:52 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************CORRECTED******************* | | | | | | 1) AIR BALANCE SCHEDULE INDICATES RETURN | | | AIR CFM = SUPPLY AIR CFM, THAT LEAVES NO | | | ROOM FOR REQUIRED CFM OF OUTSIDE AIR FOR | | | AHU 1-4 | | | 2) LINE 44 SHOWS EXHAUST OUTLET WITHIN | | | 10' OF OUTSIDE AIR INTAKE | | | 3) KITCHEN HOOD AND EXHAUST TO COMPLY W/ | | | 1997 SMC 504 AND NFPA 96 SEPARATE PERMIT | | | AND PLANS TO BE SUBMITTED WITH PERMIT AP | | | 4) MEN'S AND WOMEN'S TOILET ROOMS DO NOT | | | SHOW BALANCE BETWEEN EXHAUST AIR AND | | | SUPPLY AIR PER 1997 SMC 501.2 | | | 5) STORAGE ROOMS TO BE VENTILATED PER | | | 1997 SMC 403 | | | 6)NO OUTSIDE AIR FOR BATHROOMS PER | | | ASHRAE 62-89 | | | 7) ROOMS WITH GREATER THAN 300CFM SUPPLY | | | AIR TO HAVE RETURN FROM AREA PER SMC 501 | | | .2 | | | 8) EXHAUST FAN TERMINATION FOR EF#7 SHAL | | | NOT BE WITHIN 10' OF OUTSIDE AIR INTAKE | | | FOR FC-1F PER SMC 506.1 | | | 9) FC-1T SHOWS EQUAL SUPPLY AIR AND | | | RETURN TO UNIT, WHERE IS OUTSIDE AIR | | | BALANCE IN CALCULATIONS | | | 10)WHAT UNIT SUPPLYS OFFICES BETWEEN | | | LINE 21 AND 23 ON M-5 (FC-1H)? | | | 11) EXHAUST FAN IN TOILET RM BY LINE 14 | | | NOT LABELED OFFICE BY SAME LINE NOT VENT | | | ILATED | | | 12) BOILER ROOM NOT VENTILATED | | | 13) NO COMBUSTION AIR SHOWN FOR BOILER, | | | SHOW CACULATIONS ON REQUIRED AMOUNT | | | 14) NO INFORMATION ON DRYER VENTING | | | 15) SHOW OUTSIDE AIR TO EXISTING FCU IN | | | MECH RM | | | 16) NO VENTILATION SHOWN FOR SWITCHGEAR | | | ROOM | | | 17) LINE 5 SHOWS OUTSIDE AIR INTAKE LOUV | | | ER WITHIN 10' OF EXHAUST AIR LOUVER | | | 18) BALANCE BETWEEN EXHAUST AIR AND | | | SUPPLY AIR AND OUTSIDE AIR NOT PER SMC | | | 501.2 | | | 19) WHERE DO EXHAUST FANS #8'S AND #10'S | | | TERMINATE? (M-6) | | | 20) HALL ROOF EXHAUST SHOWN ON M-1 AIR | | | BALANCE ARE NOT SHOWN ON PLANS OR EF | | | SCHEDULE. WHERE DO THEY TERMINATE. | | | PROVIDE AIR BALANCE SCHEDULE TO COMPLY | | | WITH SMC 501.2 | | | 21)ALL DUCTS PENETRATING RATED WALLS TO | | | HAVE FIRE DAMPERS PER SMC 610 SHOW ON | | | PLAN | | | 22) NO INFORMATION SHOWN ON FAN SHUT | | | DOWN BY DUCT SMOKE DETECTORS. SHOW COMP- | | | LIANCE WITH SMC 406 AND NFPA 90A 4-4.4.2 | | | 23) AHU RMS TO BE VENTILATED PER SMC 403 | | | | | | NOTE: PRELIMINARY REVIEW. INSUFFICIENT | | | IFORMATION TO DETERMINE CODE COMPLIANCE | | | AS PRESENTED |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
P |
Date |
2002-10-23 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2002-10-23 |
Time |
14:55 |
Rev Time |
2.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-10-23 00:00:00 | AS BUILT DRWGS, APPR, PES. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
F |
Date |
2002-06-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-06-27 |
Time |
16:55 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-06-27 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2002-06-27 00:00:00 | REVISION | | | REFERENCE: SPC-94 | | | | | | 1) SHT P201.2 SANITARY 3" TIED INTO 2" | | | POOL LINE. | | | 2) SHT P201.3 VARIOUS INSTANCES FITTINGS | | | BACKWARDS IN DRAIN LINE SANT. SHOW ALL | | | TIE-INS TO BLDG DRAIN. | | | 3) SHT P401.4 SANT. RISER DIAGRAM DOES | | | NOT REFLECT SANT. DRAINS SHOWN ON SHT | | | P201.3. ALSO SANT RISER DIAGRAM REFERS | | | TO SHT P401.3.2 FOR CONT. BUT THAT SHEET | | | NOT SUBMITTED. | | | 4) SHTS P201.2 & P201.3 SANT LINES AND | | | FIXTURES HARD TO SEE ON PLANS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2001-04-28 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-04-28 |
Time |
07:34 |
Rev Time |
3.00 |
| Received By |
jleech |
Date |
2001-04-28 |
Time |
07:34 |
Sent To |
|
|
| Notes |
| 2001-04-28 00:00:00 | PROVISO; | | | | | | 1.P401.4 ELEVATOR SUMP PUMP MUST GO TO | | | A HOLDING TANK. DISCHARGE MUST STAY ON | | | PROPERTY. NOT PERMITED TO TIE INTO | | | SANITARY. | | | | | | 2.IF ROOF DRAINS AND RAIN LEADERS ARE | | | TO BE REDONE SUBMIT CALKULATIONS TO | | | COMPLY TO CHAPTER 11 OF THE 94 SPC. | | | | | | PLUMBING PLAN REVIEW BY | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2001-02-28 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-02-28 |
Time |
15:03 |
Rev Time |
8.00 |
| Received By |
jleech |
Date |
2001-02-28 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2001-02-28 00:00:00 | DENIED; | | | | | | 1.P100.1 (AIR CHAMBER DETAIL) SHALL | | | COMPLY WITH 94 SPC 607.8.2 AND 607.8.3 | | | ENGINEERED AIR CHAMBERS MUST BE SIZED | | | AND ACCESSIBLE. PROVIDE MANUFACTOR | | | SPECIFICATIONS. | | | 2.WATER SERVICE DETAIL; REDUCED PRESSURE | | | DEVICE IS REQUIRED BY WPB WATER DEPART | | | MENT. CONTACT ORVAL POLK FOR LOCATION. | | | | | | 3.GREASE INTERCEPTOR P101.2 SALL BE | | | REVIEWED BY RODNEY COMPO 835-7423 | | | WASTE ORD.#2938-96. | | | 4.(TRAP RESEAL DIAGRAM) NOTE 3. SUPPLY | | | MANUFACTORS CUT SHEET WITH INFORMATION | | | ON TRAP PRIMERS TO BE USED. | | | 5.BOTTOM FED WATER HEATER SHALL HAVE A | | | VACUUM RELIEF VALVE INSTALLED. SPC | | | 507.1.2. | | | 6.UNIONS ON WATER HEATER DETAIL MUST BE | | | DIELECTRIC. | | | 7.P401.4 ELEVATOR SUMP PUMP MUST GO TO A | | | HOLDING TANK. DISCHARGE MUST STAY ON | | | PROPERTY. NOT PERMITED TO TIE INTO | | | SANITARY. | | | 8.LENGTH OF SANITARY VENT SYSTEM IS | | | LONGER THAN ALLOWED BY TABLE 920.2. | | | 9.ROOF DRAIN PIPING DETAIL AND ISOMETRIC | | | DIAGRAM REQUIRED, TO COMPLY WITH SPC | | | CHAPTER 11. SHOW SQ. FT. PER DOWN | | | SPOUT. | | | 10.(A702) FIRST AID DEPARTMENT; BATHROOM | | | DOORS ARE NOT PERMITED TO OPEN INTO | | | THE CLEAR FLOOR SPACE OF A HANDICAP | | | FIXTURE. FACBC 4.17.5 | | | 11.WOMANS GANG BATHROOMS MUST COMPLY | | | WITH FACBC 4.22.4. OUTWARD SWING DOOR | | | AND GRAB BARS ON AN ADDITIONAL STALL | | | OVER 6. | | | 12.HANDICAP DRESSING ROOMS SHALL COMPLY | | | WITH FACBC 4.35 THRU 4.35.5.SHOW | | | DETAIL DRAWING. | | | 13.BACKFLOW PROTECTION REQUIRED FOR | | | DOMESTIC WATER AT POOL AND FOUNTAINS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2000-01-25 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-01-25 |
Time |
16:00 |
Rev Time |
4.00 |
| Received By |
tlarge |
Date |
2000-01-25 |
Time |
16:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
N |
Date |
2000-01-25 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-10-12 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
tlarge |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | CONTINUATION OF PLAN REVIEW NOTES OF | | | REV.2- 10/12/99. | | | | | | LINE SIZES FOR BLDG.DRAIN AND BLDG.SEWER | | | DON'T CORRELATE BETWEEN SHTS.P-8 & P-2. | | | AND DRAIN LINES ON P-8 DON'T MATCH P-5. | | | | | | SIZE ALL SECTIONS OF THE SANITARY | | | ISOMETRIC.SPC 104.2.1. | | | | | | MAX.4 FIXTURES PERMITTED TO BE CONNECTED | | | TO 1/2" H.W.-COUNTYWIDE AMENDMENTS SEC. | | | 607.7 . | | | | | | FLOOR DRAINS SHALL BE EQUIPPED W/ TRAP | | | PRIMERS.SPC 409.4.1.4. | | | | | | AN APPROVED BACKFLOW PREVENTER SHALL BE | | | INSTALLED ON THE BYPASS ON THE WATER | | | SERVICE AND ON THE FEED WATER LINE TO | | | THE BOILER PER SPC SEC.606.1,606.3.5. | | | | | | SUBMIT A LEGIBLE COPY OF THE MANUF.SHEET | | | FOR THE GREASE INTERCEPTOR.SPC 1004.2. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2000-01-25 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-10-12 |
Time |
11:23 |
Rev Time |
7.00 |
| Received By |
tlarge |
Date |
1999-10-12 |
Time |
11:23 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NUMBER OF REQUIRED DRINKING FOUNTAINS | | | SHALL COMPLY W/SPC TABLE 407.(A TOTAL OF | | | 17 ARE REQD.) | | | | | | CLEARLY SHOW THAT FLOORS AND WALLS ARE | | | NON-ABSORBENT TO A HEIGHT OF 4'PER SBC | | | SEC.1204.2 | | | | | | AN ADDITIONAL HANDICAP STALL COMPLYING | | | W/FACBC SEC.4.22.4 SHALL BE REQUIRED | | | IN CORE RESTROOMS OF 6 STALLS OR MORE. | | | | | | TOILET ROOMS OTHER THAN THOSE | | | LOCATED IN PUBLIC AND COMMON USE AREAS | | | SHALL BE HANDICAPADAPTABLE PER FACBC | | | SEC.4.1.3(11). | | | | | | HANDICAP STALLS LOCATED IN CORE REST- | | | ROOMS SHALL COMPLY W/FACBC SEC.4.17.3. | | | (SEE EXCEPTION: NEW CONSTRUCTION). | | | | | | DOORS IN HANDICAP TOILET ROOMS AND | | | STALLS SHALL NOT SWING INTO CLEAR FLOOR | | | FLOOR SPACE FOR ANY FIXTURE PER FACBC. | | | | | | HANDICAP STALL IN MEN'S DRESSING ROOM | | | SHALL COMPLY W/FACBC SEC.4.17.3 | | | | | | CLEARLY SHOW THE DIMENSIONS OF THE | | | HANDICAP SHOWERS.COMPLY W/FACBC SEC. | | | 4.21.2. | | | | | | SHOW TYPICAL FIXTURE CLEARANCE OF | | | URINALS ON THE PLANS.SPC SEC.403.4. | | | | | | HANDICAP TOILET STALLS AND TOILET ROOMS | | | SHALL HAVE 60" CLEAR TURNING SPACE PER | | | FACBC SECTION 4.2.3.(WATER CLOSET | | | INFRINGES ON TURNING SPACE IN SOME ROOMS | | | CHECK ALL STALLS AND ROOMS.) | | | | | | SEATS IN HANDICAP SHOWERS SHALL COMPLY | | | W/FACBC SEC.4.21.3(REQD.IN 36"X 36"STALL | | | | | | CLEAR FLOOR SPACE UNDER H.C.LAVATORIES | | | SHALL BE A MIN.OF 29" PER FACBC SEC. | | | 4.19.2. | | | | | | CLEARLY SHOW THE REQD.HEIGHT OF THE H.C. | | | WATER ON SHT.A204.(17"-19".)PER FACBC | | | SEC.4.16.3. | | | | | | GRAB BARS BEHIND WATER CLOSETS SHALL BE | | | 36"LONG PER FACBC SEC.4.16.4,4.17.6.(SEE | | | SHT.A204.) | | | | | | SHOWER VALVES SHALL COMPLY W/SPC SEC.613 | | | NOTE ON PLANS. | | | | | | DORMITORY ROOMS SHALL COMPLY W/FEDERAL | | | FAIR HOUSING ACT. | | | | | | SHT.A105 SHOWS A CLEANING/STORAGE AREA | | | W/WASHER & DRYER.WASHERS ARE ALSO SHOWN | | | IN THE DORMS.THIS IS A COMMERCIAL | | | FACILITY AND REQS.AN INTERCEPTOR PER | | | SPC SEC.1004.1,1004.10.1.1. | | | AND CLEANING /STORAGE AREA SHALL BE | | | EQUIPPED W/A FLOOR DRAIN.SPC SEC.409.4.5 | | | | | | SHT.A204-SHOWER FLOOR SHALL BE DRAINED | | | SO THAT NO WASTE WATER FROM ANY SHOWER | | | HEAD WILL PASS OVER FLOOR AREAS OCCUPIED | | | BY OTHER BATHERS.SPC SEC.409.8.3. | | | | | | CONTACT RODNEY COMPO AT CITY OF W.P.B. | | | REGIONAL WASTEWATER TREATMENT PLANT FOR | | | REQS./SIZE OF GREASE TRAP.(561)835-7423 | | | | | | THE SUBMITTED GAS DRAWING LACKS THE | | | NECESSARY INFORMATION TO PERFORM A | | | PROPER REVIEW.SHOW TYPE OF MATERIAL FOR | | | PIPING,DISTANCE TO MOST REMOTE OUTLET, | | | CUT SECTIONS OF PIPE,ETC.COMPLY W/STD. | | | GAS CODE SEC.302,305.2,305.3.2,306,ETC. | | | INDICATE TYPE OF GAS-NATURAL OR LP. | | | | | | SHT.A211-CLEARLY SHOW TERMINATION PT.OF | | | TRUCK WELL DRAIN.SPC 104.2.1. | | | | | | SUBMIT MANUF. SHEETS FOR GAS EQUIP.PER | | | STD.GAS CODE SEC.402.1 | | | | | | THE SUBMITTED SANITARY RISER HAS TOO | | | MANY CODE VIOLATIONS TO LIST.SUBMIT A | | | SANITARY RISER THAT COMPLIES W/THE STD. | | | PLBG.CODE. | | | | | | THE SANITARY ISOMETRIC DOESN'T CORRELATE | | | W/THE BUILDING FLOOR PLAN.SPC 104.2.1. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2000-01-25 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-07-24 |
Time |
10:29 |
Rev Time |
8.00 |
| Received By |
tlarge |
Date |
1999-07-24 |
Time |
11:21 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SUBMIT OCCUPANT LOAD PER STD.PLBG.CODE | | | SEC.407.1.1, 407.1.3 TO ENSURE | | | COMPLIANCE FOR MINIMUM FIXTURE REQ'S. | | | FIXTURE REQ'S.SHALL BE BASED ON EQUAL | | | NUMBER OF MALES AND FEMALES. | | | | | | FIXTURE REQ'S.SHALL COMPLY W/FLA.STATUTE | | | 553.141.(POTTY PARITY.). | | | | | | HANDICAP DRINKING FOUNTAINS SHALL COMPLY | | | W/F.A.C.B.C.SEC.4.1.3(10)(A)(B). | | | | | | HANDICAP TOILET STALLS IN DRESSING ROOMS | | | AND COMMON RESTROOMS SHALL COMPLY W/FLA. | | | ACCESS.CODE SECS.4.17.3(SEE EXCEPTION: | | | NEW CONSTTRUCTION.) | | | | | | HANDICAP TOILET/STALLS SHALL HAVE 60" | | | CLEAR TURNING SPACE PER F.A.C.B.C. SEC. | | | 4.2.3.(WATER CLOSET INFRINGES ON TURNING | | | SPACE IN SOME ROMMS -CHECK ALL STALLS | | | AND TOILET ROOMS AND REVISE). | | | | | | SEATS IN HANDICAP SHOWERS SHALL COMPLY | | | W/F.A.C.B.C. SEC.4.21.3. | | | | | | CLEARLY SHOW ALL DIMENSIONS OF HANDICAP | | | SHOWER STALLS.COMPLY W/F.A.C.B.C.SEC. | | | 4.21.2. | | | | | | EACH PUBLIC OR COMMON USE TOILET | | | FACILITY SHALL COMPLY W/F.A.C.B.C. SEC. | | | 4.22.(SEE SEC.4.1.2.(6). | | | | | | CLEAR FLOOR SPACE UNDER H.C.LAVS.SHALL | | | COMPLY W/F.A.C.B.C.SEC.4.19.2. | | | | | | HEIGHT OF H.C.WATER CLOSETS SHALL COMPLY | | | W/F.A.C.B.C.SEC.4.16.3. | | | | | | AN ADDITIONAL H.C STALL IS REQ'D.IN THE | | | RESTROOMS PER F.A.C.B.C.SEC.4.22.4 | | | | | | DORMITORY ROOMS SHALL COMPLY W/FLA. | | | ACESS.CODE SEC.9.1 THRU 9.1.5, 9.2.1 - | | | 9.2. | | | | | | GANG SHOWERS SHALL COMPLY W/STD. PLBG. | | | CODE SEC.409.8.3. | | | | | | SHOWER VALVES SHALL COMPLY W/STD.PLBG. | | | CODE SEC.613.1.(NOTE ON PLANS.). | | | | | | SHOW TYPICAL SPACING FOR URINALS PER | | | STD.PLBG.CODE SEC.403.4. | | | | | | HANDICAP SHOWERS SHALL BE EQUIPPED W/ | | | SPRAY UNITS PER F.A.C.B.C.SEC.4.21.6. | | | | | | LINT INTERCEPTORS ARE REQ'D.FOR THE | | | COMMON LAUNDRY AREAS PER STD.PLBG.CODE | | | SEC.1004.1,1004.10.1.1. | | | | | | LAUNDRY ROOMS SHALL BE EQUIPPED W/FLOOR | | | DRAINS PER STD.PLBG.CODE SEC.409.4.5. | | | | | | SUBMIT A COMPLETE GAS RISER DIAGRAM | | | SHOWING TYPE OF MATERIAL,APPLIANCES,BTU | | | LOAD OF EA.APPLIANCE,TOTAL BTU LOAD OF | | | THE SYSTEM,ETC.COMPLY W/STANDARD GAS | | | CODE SECS.302, 305.2,305.3.2,306,ETC. | | | | | | SUBMIT A WATER AND SANITARY ISOMETRIC | | | THAT CLEARLY REFLECTS THE ENTIRE SCOPE | | | OF PLUMBING WORK TO BE PERFORMED.SPC | | | SEC 104.2.1.(INCLUDE ALL INDIRECT WASTE) | | | | | | SPACING OF CLEANOUTS IN THE DRAINAGE | | | SYSTEM SHALL COMPLY W/SPC SEC.710.2.1 | | | THRU SEC.712.2. | | | | | | FLOOR DRAINS SHALL NOT EXCEED ALLOWABLE | | | DISTANCES FROM VENT PER TABLE 908.1 OF | | | SPC. | | | | | | SHT.P-5-SHOWS FLOOR DRAIN IN STORAGE | | | ROOM.DETAIL TYPE OF MATERIALS TO BE | | | STORED IN THIS ROOM. | | | | | | SHT.A 206-SHOWS DRAIN IN TRUCKWELL AREA. | | | INDICATE TERMINATION PT.OF DRAIN. | | | | | | LOCATION OF GREASE INTERCEPTORS SHALL | | | COMPLY W/STD.PLBG.CODE SEC.1004.8 AND | | | STATE OF FLA.DEPT.OF HEALTH REQ'S. | | | | | | SUBMIT DETAIL OF GREASE INTERCEPTOR FOR | | | REVIEW.SPC 104.2.1. | | | --PLANS SHALL BE ROUTED TO PALM BEACH | | | COUNTY HEALTH UNIT.(561)355-3018. |
|
|