Plan Review Details - Permit 99070843
Plan Review Stops For Permit 99070843
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2002-07-30 Cont ID  
Sent By hpiskura Date 2002-07-30 Time 14:24 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-07-30 00:00:00BLD REVISION DATED 4/2/02

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2001-05-15 Cont ID  
Sent By hpiskura Date 2001-05-15 Time 09:06 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-05-15 00:00:00FOR WALL TYPE REVISIONS 5/1/01

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2001-02-20 Cont ID  
Sent By hpiskura Date 2001-02-20 Time 11:09 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-02-20 00:00:00REVISIONS DATED 1/5/01
 THE SMALL MEETING ROOM SHOWN ON SHEET
 A201.4 DOES NOT HAVE THE EXIT DOORS A
 DISTANCE APART EQUAL TO OR GREATER THAN
 1/2 THE DIAGONAL DISTANCE OF THE ROOM
 AS REQUIRED BY SBC 1004.1.4.PLEASE
 REVISE AS NECESSARY.
  
 SECTION 3/A505.SHOW THE DESIGN LOADS
 FOR THE CATWALK.SEE SBC 1604.8.
  
 THE DOOR SCHEDULES DO NOT SHOW RATED
 ENTRANCE DOORS FOR THE APARTMENTS.SEE
 SBC 704.1.1 AND SBC 705.1.2
  
 SHEET A203 DOES NOT CLEARLY SHOW THE
 AISLE AND SEATING DIMENSIONS, OR
 PLACEMENT OF HANDRAILS TO DETERMINE
 COMPLIANCE WITH SBC 1019.9 AND SBC
 1019.10.
  
 THE RISER MOUNTED SEATING MUST COMPLY
 WITH SBC 1019.10.3.2. FOR ROWS HAVING >
 14 SEATS.
  
 SEE SBC 1007.5.7 FOR THE HANDRAIL
 SPACING REQUIREMENTS ON THE VOMITORY
 STAIRS.
  
 PERMIT FEES MUST BE PAID TO THE CITY FOR
 THE NEW AND ADDED WORK.
  
 HAROLD PISKURA

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-03-08 Cont ID  
Sent By hpiskura Date 2000-03-08 Time 09:41 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 1999-10-22 Cont ID  
Sent By hpiskura Date 1999-10-22 Time 13:02 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 1999-08-18 Cont ID  
Sent By hpiskura Date 1999-08-12 Time 09:36 Rev Time 99.00
Received By dpalmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00NOTES
 AS PER HAROLD P.

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2002-10-31 Cont ID  
Sent By dpalmer Date 2002-10-31 Time 14:09 Rev Time 0.50
Received By dpalmer Date 2002-10-31 Time 14:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2002-10-24 Cont ID  
Sent By dpalmer Date 2002-10-24 Time 08:55 Rev Time 1.00
Received By dpalmer Date 2002-10-24 Time 08:55 Sent To  
Notes
2002-10-24 00:00:00************** UNSAT ***********
  
 1)NOTE: PLEASE NOTE LRU-DIST IS SHOWN
 AS MLO. PLEASE NOTE THAT PER 240-21
 MUST TERMINATE IN A SINGLE OCP DEVICE.
 IT IS NOTED THAT OTHER PANELS WERE
 CHANGED TO HAVE MCB.
  
 2)NOTE: PLEASE NOTE PLANS HAVE BEEN
 COMPLETELY PRINTED OUT FOR REVIEW AND
 PANEL "SS" IS MISSING FROM PANEL SCHED-
 -ULES? PLEASE SUBMIT.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2002-10-18 Cont ID  
Sent By dpalmer Date 2002-10-18 Time 07:26 Rev Time 0.00
Received By dpalmer Date 2002-10-18 Time 07:26 Sent To  
Notes
2002-10-18 00:00:00************ ON HOLD ***********
  
 WAITING FOR PAID BZ. TO PROCESS PLANS.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2002-06-17 Cont ID  
Sent By dpalmer Date 2002-06-17 Time 06:37 Rev Time 0.00
Received By dpalmer Date 2002-06-14 Time 05:58 Sent To  
Notes
2002-06-17 00:00:00******************* UNSAT *************
 1)NOTE: PLEASE NOTE THAT PLANS SUBMITTED
 AS "AS-BUILTS" ARE NOT COMPLETE.
 PLEASE NOTE PANEL SCHEDULE THAT ARE NOT
 COMPLETE.
 PLEASE NOTE RISER DIAGRAM IS SUBMITTED
 AS COMPLETE AND THERE IS A MISSING SEC
 THAT GOES WITH E 902? PLEASE NOTE THAT
 THE ONE- LINE SHOWN ON E902.1 IS MISSING
 SOME ITEMS THAT ARE SHOW ON OTHER RISER
 PLEASE CORRELATE AND COMPLETE PLANS FOR
 SUFFICENT ELECTRICAL REVIEW.
  
 2)NOTE: PLEASE NOTE THAT THERE ARE SOME
 PANELS/DIST PANELS ON THE LOAD SIDE
 OF TRANSFORMERS THAT HAVE NO MAINS
 SHOWN? PLEASE SEE 240-21 FOR TERMINATION
 IN A SINGLE SET OF OCP.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-04-17 Cont ID  
Sent By dpalmer Date 2001-04-17 Time 14:33 Rev Time 0.00
Received By dpalmer Date 2001-04-16 Time 22:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-02-14 Cont ID  
Sent By dpalmer Date 2001-02-14 Time 11:41 Rev Time 0.00
Received By dpalmer Date 2001-02-14 Time 12:17 Sent To  
Notes
2001-02-14 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT A RISER SHEET
 WITHCORRELATING INFORMATION SHOWING
 CLARIFICATION ON LOCATIONS OF
 TRANSFORMERS.
 WE NEED CLARIFICATION ON HOW FAR AWAY
 PANELS/ AND DISCONNECTS ARE. THIS IS
 NEEDED FOR SECONDARY(S) OF ALL
 TRANSFORMERS IN THE BLDG. ALL MUST MEET
 240-21-C 2&3
  
 2)NOTE: PLEASE NOTE, ON SHEET E902 YOU
 ARE SHOWING TWO LOCATIONS WHERE
 TRANSFORMERS ARE BEING TAPPED AND GOING
 TO GUTTERS AND BEING TAPPED AGAIN,
 PLEASE NOTE
 THAT THIS VIOLATES 240-21.
  
 PLEASE NOTE THAT ALL THE REQUIREMENTS
 FOR TAPPED CONDUCTORS NEED TO BE MET.
 FOR 10` AND 25`
 CONDUCTORS FEEDING "LRU" DIST. PANEL
 ARERATED FOR LEESTHAN THE 600A RATED
 BOARD.
  
 3)NOTE: ALSO PLEASE NOTE THAT ALL THE
 REQUIREMENTS FOR 110-26 AND 384-7 NEED T
 O BE MET. PANELS AND TRANSFORMERS ARE
 SHOWN IN STORAGE AND CLEANING CLOSETS.
 THIS IS VIOLATES THE ABOVE MENTIONED ART
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS PLEAS
 E CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 OR
 JAKE LEAHY
 CHEIF ELECTRICAL INSPECTOR
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-02-02 Cont ID  
Sent By jleahy Date 2000-02-02 Time 13:24 Rev Time 1.00
Received By jleahy Date 2000-02-02 Time 13:11 Sent To  
Notes
2001-01-08 00:00:001- DISCONNECT NEEDED FOR TRANSFER SWITCH
 IF IT IS REMOTE FROM THE GENERATOR.
 ONLY ON THE EMERGENCY SIDE, NORMAL
 HAS ONE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 1999-10-18 Cont ID  
Sent By jleahy Date 1999-10-18 Time 13:23 Rev Time 0.00
Received By jleahy Date 2000-02-02 Time 13:10 Sent To  
Notes
2001-01-08 00:00:001)NEED LOAD CALCULATIONS ON PANELS TO
 REFLECT CONTIN LDS,MOST OF THE
 PANELS SHOW 4 TO 8 AMPERES FOR THE
 LIGHTING IN EACH PANEL.THIS CAN,T
 BE CORRECT WHEN THERE IS LARGE
 LIGHTING LOADS IN THESE PANELS
  
 2)PANEL LPL-8SHOW 8.32 AMPS FOR THE
 CONTINUOUS LOAD FACTOR WHEN THERE
 IS 15,600VA WORTH OF LOAD3900
 VA CONTINUOUS LOAD CONTRIBUTION
 COMES OUT AT 16.25 AMPSPLEASE
 CHECK ALL PANEL SCHEDULES FOR THE
 CORRECT LOADS!
  
 3)NEW MAIN 3000 AMPERES SHOW LOAD
 CALCULATION FOR THIS SWITCH.
  
 4)AT NEWTRANSFER SWITCH YOU NEED A
 DISCONNECT FOR THE LINE SIDE OF THE
 EMERGENCY FEED AT TRANSFER SWITCH!!
  
 5)NOTE #5 WAS LISTED ON THE ORIGINAL
 CHECK LIST!YOUR RISER DOES NOT
 REFLECT THIS 225-8, 230-72
  
 6)THE CITY NEEDS A ONE LINE DIAGRAM
 FOR THE RISER THAT WILL BE USED
 SHOW WHAT THE FINISHED RISER WILL
 LOOK LIKE.
  
 7)ACCORDING TO THE PLANS YOU SHOW AN
 EXISTING RISER WITH THE NOTE TO BE
 REMOVED UNLESS NOTED,DPP1 SHOULD BE
 REMOVED BUT SHOWS UP ON NEW RISER
 PLEASE FIXSEE NOTE #6

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2002-12-18 Cont ID  
Sent By mcarsill Date 2002-12-18 Time 19:57 Rev Time 0.00
Received By mcarsill Date 2002-12-18 Time 19:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2002-07-16 Cont ID  
Sent By btrobaug Date 2002-12-10 Time 18:46 Rev Time 0.00
Received By mcarsill Date 2002-07-16 Time 14:43 Sent To  
Notes
2002-07-16 00:00:001) KNOX-BOXES WILL BE REQUIRED AT
 VEHICULAR GATES.
  
 2) OPENINGS THRU SECURITY GATES MUST
 BE AT LEAST TWENTY (20) FEET IN CLEAR
 WIDTH IN WHICH FIRE RESCUE VEHICLES
 ARE EXPECTED TO PASS THRU.
  
 3) BUILDING ADDRESS IS REQUIRED WITH
 AT LEAST SIX (6) INCH HIGH NUMERALS.
 YARD SIGN SHOULD DISPLAY ADDRESS SINCE
 THE BUILDING SITS SO FAR OFF THE ROAD
 UNLESS AN ALTERNATIVE LOCATION IS
 AGREED UPON.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-08-06 Cont ID  
Sent By mcarsill Date 2001-08-06 Time 15:04 Rev Time 0.00
Received By mcarsill Date 2001-08-06 Time 15:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2001-05-02 Cont ID  
Sent By mcarsill Date 2001-05-02 Time 15:48 Rev Time 0.00
Received By mcarsill Date 2001-05-02 Time 15:48 Sent To  
Notes
2001-05-02 00:00:001) DUCT SMOKE DETECTORS REQUIRED IN ALL
 AIR HANDLING SYSTEMS OVER 2000 CFM AND
 SERVING MEANS OF EGRESS AREAS. WHEN
 ACTIVATED, THE AIR HANDLING EQUIPMENT
 IS TO SHUT DOWN AND CAUSE THE FIRE
 ALARM SYSTEM TO ACTIVATE.
 2) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 3) GAS INSTALLATION TO COMPLY WITH
 NFPA 54.
 4) FIRE DAMPERS TO COMPLY WITH UL 555.
 ALL FIRE DAMPERS ARE TO BE DROP TESTED
 AFTER INSTALLATION.
 5) SEATING INSTALLATION SUBJECT TO THE
 APPROVAL OF THE FIRE PREVENTION BUREAU.
 6) DOORS SUBJECT TO AN OCCUPANCY OF 100
 OR MORE PERSONS SHALL BE EQUIPPED WITH
 PANIC HARDWARE. FIRE DOORS SHALL BE
 EQUIPPED WITH FIRE EXIT PANIC HARDWARE.
 7) PLEASE CONTACT THIS OFFICE TO DISCUSS
 SEATING ARRANGEMENT ON THE MAIN FLOOR
 OF THE BUILDING.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-02-08 Cont ID  
Sent By mcarsill Date 2001-02-08 Time 14:28 Rev Time 0.00
Received By mcarsill Date 2001-02-08 Time 14:28 Sent To  
Notes
2001-02-08 00:00:001) NEW BRICK PAVERS ON EXISTING CONCRETE
 STEPS ARE TO BE SLIP RESISTANT.
 2) PLEASE DEFINE BABY ROOM 1617. WHAT
 WILL IT BE USED FOR.
 3) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS TO
 COMPLY WITH CITY CODE REQUIREMENTS.
 4) ALL EXIT DOORS IN THE REQUIRED MEANS
 OF EGRESS SUBJECT TO AN OCCUPANCY OF
 100 OR MORE PERSONS SHALL BE EQUIPPED
 WITH PANIC HARDWARE.
 5) SUFFICIENT EMERGENCY LIGHTING AND
 ILLUMINATED EXIT SIGNS ARE TO BE PRESENT
 WITHIN THE BUILDING.
 6) PLEASE PROVIDE MORE DETAILS ON
 FIXED SEATING PLANNED FOR THE GROUND
 FLOOR.
 7) DUCT SMOKE DETECTION REQUIRED IN ALL
 AIR HANDLING SYSTEMS.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-03-08 Cont ID  
Sent By hpiskura Date 2000-03-08 Time 09:44 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO ON PLANS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-10 Cont ID  
Sent By btrobaug Date 2002-12-10 Time 18:46 Rev Time 0.00
Received By btrobaug Date 2002-12-10 Time 18:46 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2002-06-11 Cont ID  
Sent By pkrauss Date 2002-06-11 Time 15:08 Rev Time 1.30
Received By pkrauss Date 2002-06-11 Time 15:08 Sent To  
Notes
2002-06-11 00:00:00AS BUILTSMECH PERMIT 99070895

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2002-01-16 Cont ID  
Sent By pkrauss Date 2002-01-16 Time 13:19 Rev Time 0.40
Received By pkrauss Date 2002-01-16 Time 12:56 Sent To  
Notes
2002-01-16 00:00:00 
 PROVISO:
  
 DUCT SHALL HAVE SMOOTH INTERIOR FINISH
 WITH JOINTS RUNNING IN THE DIRECTION OF
 THE AIR FLOW.
  
 NO SCREWS SHALL PENETRATE INTERIOR.
  
 COMPLY WITH 1997 SMC 509
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT 8388.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2001-07-30 Cont ID  
Sent By pkrauss Date 2001-07-30 Time 11:17 Rev Time 1.20
Received By pkrauss Date 2001-07-30 Time 11:17 Sent To  
Notes
2001-07-30 00:00:00*******************PROVISO**************
  
  
 HOW IS GAS FIRED POOL HEATER BEING
 SUPPLIED.PLEASE INDICATE ON PLANS
 WHAT SIZE PIPE IS SUPPLYING POOL HEATER.
  
 PLEASE SUBMIT MANUFACTURER DATA ON POOL
 HEATER.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-05-21 Cont ID  
Sent By pkrauss Date 2001-05-21 Time 13:33 Rev Time 2.00
Received By pkrauss Date 2001-05-21 Time 13:33 Sent To  
Notes
2001-05-21 00:00:00********************PROVISO*************
  
  
 PLEASE PROVIDE CALCULATIONS FOR O.A. IN
 THE BOILER ROOM (DID THEY CHANGE BY
 ADDING ANOTHER BOILER?)
  
 ANY EXISTING FIRE DAMPERS NEED TO BE
 IDENTIFIED ON PLAN AND WILL BE
 INSPECTED/TESTED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-01-28 Cont ID  
Sent By ndenmark Date 2000-01-28 Time 08:05 Rev Time 1.00
Received By ndenmark Date 2000-01-28 Time 08:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-10-13 Cont ID  
Sent By ndenmark Date 1999-10-13 Time 11:14 Rev Time 2.00
Received By ndenmark Date 1999-10-13 Time 11:14 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1) ALL DUCTS PENETRATING RATED WALLS TO
 BE PROTECTED BY FIRE DAMPERS
 2)INCLUDE CALCULATIONS FOR BOILER COMB-
 USTION AIR IN APPROVED DOCUMENTS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-10-13 Cont ID  
Sent By ndenmark Date 1999-08-03 Time 12:52 Rev Time 5.00
Received By ndenmark Date 1999-08-03 Time 12:52 Sent To  
Notes
2001-01-08 00:00:00************CORRECTED*******************
  
 1) AIR BALANCE SCHEDULE INDICATES RETURN
 AIR CFM = SUPPLY AIR CFM, THAT LEAVES NO
 ROOM FOR REQUIRED CFM OF OUTSIDE AIR FOR
 AHU 1-4
 2) LINE 44 SHOWS EXHAUST OUTLET WITHIN
 10' OF OUTSIDE AIR INTAKE
 3) KITCHEN HOOD AND EXHAUST TO COMPLY W/
 1997 SMC 504 AND NFPA 96 SEPARATE PERMIT
 AND PLANS TO BE SUBMITTED WITH PERMIT AP
 4) MEN'S AND WOMEN'S TOILET ROOMS DO NOT
 SHOW BALANCE BETWEEN EXHAUST AIR AND
 SUPPLY AIR PER 1997 SMC 501.2
 5) STORAGE ROOMS TO BE VENTILATED PER
 1997 SMC 403
 6)NO OUTSIDE AIR FOR BATHROOMS PER
 ASHRAE 62-89
 7) ROOMS WITH GREATER THAN 300CFM SUPPLY
 AIR TO HAVE RETURN FROM AREA PER SMC 501
 .2
 8) EXHAUST FAN TERMINATION FOR EF#7 SHAL
 NOT BE WITHIN 10' OF OUTSIDE AIR INTAKE
 FOR FC-1F PER SMC 506.1
 9) FC-1T SHOWS EQUAL SUPPLY AIR AND
 RETURN TO UNIT, WHERE IS OUTSIDE AIR
 BALANCE IN CALCULATIONS
 10)WHAT UNIT SUPPLYS OFFICES BETWEEN
 LINE 21 AND 23 ON M-5 (FC-1H)?
 11) EXHAUST FAN IN TOILET RM BY LINE 14
 NOT LABELED OFFICE BY SAME LINE NOT VENT
 ILATED
 12) BOILER ROOM NOT VENTILATED
 13) NO COMBUSTION AIR SHOWN FOR BOILER,
 SHOW CACULATIONS ON REQUIRED AMOUNT
 14) NO INFORMATION ON DRYER VENTING
 15) SHOW OUTSIDE AIR TO EXISTING FCU IN
 MECH RM
 16) NO VENTILATION SHOWN FOR SWITCHGEAR
 ROOM
 17) LINE 5 SHOWS OUTSIDE AIR INTAKE LOUV
 ER WITHIN 10' OF EXHAUST AIR LOUVER
 18) BALANCE BETWEEN EXHAUST AIR AND
 SUPPLY AIR AND OUTSIDE AIR NOT PER SMC
 501.2
 19) WHERE DO EXHAUST FANS #8'S AND #10'S
 TERMINATE? (M-6)
 20) HALL ROOF EXHAUST SHOWN ON M-1 AIR
 BALANCE ARE NOT SHOWN ON PLANS OR EF
 SCHEDULE. WHERE DO THEY TERMINATE.
 PROVIDE AIR BALANCE SCHEDULE TO COMPLY
 WITH SMC 501.2
 21)ALL DUCTS PENETRATING RATED WALLS TO
 HAVE FIRE DAMPERS PER SMC 610 SHOW ON
 PLAN
 22) NO INFORMATION SHOWN ON FAN SHUT
 DOWN BY DUCT SMOKE DETECTORS. SHOW COMP-
 LIANCE WITH SMC 406 AND NFPA 90A 4-4.4.2
 23) AHU RMS TO BE VENTILATED PER SMC 403
  
 NOTE: PRELIMINARY REVIEW. INSUFFICIENT
 IFORMATION TO DETERMINE CODE COMPLIANCE
 AS PRESENTED

Review Stop P PLUMBING
Rev No 8 Status P Date 2002-10-23 Cont ID  
Sent By pschmitz Date 2002-10-23 Time 14:55 Rev Time 2.50
Received By pschmitz Date   Time   Sent To  
Notes
2002-10-23 00:00:00AS BUILT DRWGS, APPR, PES.

Review Stop P PLUMBING
Rev No 7 Status F Date 2002-06-27 Cont ID  
Sent By kstevens Date 2002-06-27 Time 16:55 Rev Time 0.00
Received By kstevens Date 2002-06-27 Time 16:55 Sent To  
Notes
2002-06-27 00:00:00REVISION
 REFERENCE: SPC-94
  
 1) SHT P201.2 SANITARY 3" TIED INTO 2"
 POOL LINE.
 2) SHT P201.3 VARIOUS INSTANCES FITTINGS
 BACKWARDS IN DRAIN LINE SANT. SHOW ALL
 TIE-INS TO BLDG DRAIN.
 3) SHT P401.4 SANT. RISER DIAGRAM DOES
 NOT REFLECT SANT. DRAINS SHOWN ON SHT
 P201.3. ALSO SANT RISER DIAGRAM REFERS
 TO SHT P401.3.2 FOR CONT. BUT THAT SHEET
 NOT SUBMITTED.
 4) SHTS P201.2 & P201.3 SANT LINES AND
 FIXTURES HARD TO SEE ON PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 6 Status P Date 2001-04-28 Cont ID  
Sent By jleech Date 2001-04-28 Time 07:34 Rev Time 3.00
Received By jleech Date 2001-04-28 Time 07:34 Sent To  
Notes
2001-04-28 00:00:00PROVISO;
  
 1.P401.4 ELEVATOR SUMP PUMP MUST GO TO
 A HOLDING TANK. DISCHARGE MUST STAY ON
 PROPERTY. NOT PERMITED TO TIE INTO
 SANITARY.
  
 2.IF ROOF DRAINS AND RAIN LEADERS ARE
 TO BE REDONE SUBMIT CALKULATIONS TO
 COMPLY TO CHAPTER 11 OF THE 94 SPC.
  
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop P PLUMBING
Rev No 5 Status F Date 2001-02-28 Cont ID  
Sent By jleech Date 2001-02-28 Time 15:03 Rev Time 8.00
Received By jleech Date 2001-02-28 Time 15:03 Sent To  
Notes
2001-02-28 00:00:00DENIED;
  
 1.P100.1 (AIR CHAMBER DETAIL) SHALL
 COMPLY WITH 94 SPC 607.8.2 AND 607.8.3
 ENGINEERED AIR CHAMBERS MUST BE SIZED
 AND ACCESSIBLE. PROVIDE MANUFACTOR
 SPECIFICATIONS.
 2.WATER SERVICE DETAIL; REDUCED PRESSURE
 DEVICE IS REQUIRED BY WPB WATER DEPART
 MENT. CONTACT ORVAL POLK FOR LOCATION.
  
 3.GREASE INTERCEPTOR P101.2 SALL BE
 REVIEWED BY RODNEY COMPO 835-7423
 WASTE ORD.#2938-96.
 4.(TRAP RESEAL DIAGRAM) NOTE 3. SUPPLY
 MANUFACTORS CUT SHEET WITH INFORMATION
 ON TRAP PRIMERS TO BE USED.
 5.BOTTOM FED WATER HEATER SHALL HAVE A
 VACUUM RELIEF VALVE INSTALLED. SPC
 507.1.2.
 6.UNIONS ON WATER HEATER DETAIL MUST BE
 DIELECTRIC.
 7.P401.4 ELEVATOR SUMP PUMP MUST GO TO A
 HOLDING TANK. DISCHARGE MUST STAY ON
 PROPERTY. NOT PERMITED TO TIE INTO
 SANITARY.
 8.LENGTH OF SANITARY VENT SYSTEM IS
 LONGER THAN ALLOWED BY TABLE 920.2.
 9.ROOF DRAIN PIPING DETAIL AND ISOMETRIC
 DIAGRAM REQUIRED, TO COMPLY WITH SPC
 CHAPTER 11. SHOW SQ. FT. PER DOWN
 SPOUT.
 10.(A702) FIRST AID DEPARTMENT; BATHROOM
 DOORS ARE NOT PERMITED TO OPEN INTO
 THE CLEAR FLOOR SPACE OF A HANDICAP
 FIXTURE. FACBC 4.17.5
 11.WOMANS GANG BATHROOMS MUST COMPLY
 WITH FACBC 4.22.4. OUTWARD SWING DOOR
 AND GRAB BARS ON AN ADDITIONAL STALL
 OVER 6.
 12.HANDICAP DRESSING ROOMS SHALL COMPLY
 WITH FACBC 4.35 THRU 4.35.5.SHOW
 DETAIL DRAWING.
 13.BACKFLOW PROTECTION REQUIRED FOR
 DOMESTIC WATER AT POOL AND FOUNTAINS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-01-25 Cont ID  
Sent By tlarge Date 2000-01-25 Time 16:00 Rev Time 4.00
Received By tlarge Date 2000-01-25 Time 16:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2000-01-25 Cont ID  
Sent By tlarge Date 1999-10-12 Time 15:37 Rev Time 0.00
Received By tlarge Date   Time   Sent To  
Notes
2001-01-08 00:00:00CONTINUATION OF PLAN REVIEW NOTES OF
 REV.2- 10/12/99.
  
 LINE SIZES FOR BLDG.DRAIN AND BLDG.SEWER
 DON'T CORRELATE BETWEEN SHTS.P-8 & P-2.
 AND DRAIN LINES ON P-8 DON'T MATCH P-5.
  
 SIZE ALL SECTIONS OF THE SANITARY
 ISOMETRIC.SPC 104.2.1.
  
 MAX.4 FIXTURES PERMITTED TO BE CONNECTED
 TO 1/2" H.W.-COUNTYWIDE AMENDMENTS SEC.
 607.7 .
  
 FLOOR DRAINS SHALL BE EQUIPPED W/ TRAP
 PRIMERS.SPC 409.4.1.4.
  
 AN APPROVED BACKFLOW PREVENTER SHALL BE
 INSTALLED ON THE BYPASS ON THE WATER
 SERVICE AND ON THE FEED WATER LINE TO
 THE BOILER PER SPC SEC.606.1,606.3.5.
  
 SUBMIT A LEGIBLE COPY OF THE MANUF.SHEET
 FOR THE GREASE INTERCEPTOR.SPC 1004.2.

Review Stop P PLUMBING
Rev No 2 Status N Date 2000-01-25 Cont ID  
Sent By tlarge Date 1999-10-12 Time 11:23 Rev Time 7.00
Received By tlarge Date 1999-10-12 Time 11:23 Sent To  
Notes
2001-01-08 00:00:00NUMBER OF REQUIRED DRINKING FOUNTAINS
 SHALL COMPLY W/SPC TABLE 407.(A TOTAL OF
 17 ARE REQD.)
  
 CLEARLY SHOW THAT FLOORS AND WALLS ARE
 NON-ABSORBENT TO A HEIGHT OF 4'PER SBC
 SEC.1204.2
  
 AN ADDITIONAL HANDICAP STALL COMPLYING
 W/FACBC SEC.4.22.4 SHALL BE REQUIRED
 IN CORE RESTROOMS OF 6 STALLS OR MORE.
  
 TOILET ROOMS OTHER THAN THOSE
 LOCATED IN PUBLIC AND COMMON USE AREAS
 SHALL BE HANDICAPADAPTABLE PER FACBC
 SEC.4.1.3(11).
  
 HANDICAP STALLS LOCATED IN CORE REST-
 ROOMS SHALL COMPLY W/FACBC SEC.4.17.3.
 (SEE EXCEPTION: NEW CONSTRUCTION).
  
 DOORS IN HANDICAP TOILET ROOMS AND
 STALLS SHALL NOT SWING INTO CLEAR FLOOR
 FLOOR SPACE FOR ANY FIXTURE PER FACBC.
  
 HANDICAP STALL IN MEN'S DRESSING ROOM
 SHALL COMPLY W/FACBC SEC.4.17.3
  
 CLEARLY SHOW THE DIMENSIONS OF THE
 HANDICAP SHOWERS.COMPLY W/FACBC SEC.
 4.21.2.
  
 SHOW TYPICAL FIXTURE CLEARANCE OF
 URINALS ON THE PLANS.SPC SEC.403.4.
  
 HANDICAP TOILET STALLS AND TOILET ROOMS
 SHALL HAVE 60" CLEAR TURNING SPACE PER
 FACBC SECTION 4.2.3.(WATER CLOSET
 INFRINGES ON TURNING SPACE IN SOME ROOMS
 CHECK ALL STALLS AND ROOMS.)
  
 SEATS IN HANDICAP SHOWERS SHALL COMPLY
 W/FACBC SEC.4.21.3(REQD.IN 36"X 36"STALL
  
 CLEAR FLOOR SPACE UNDER H.C.LAVATORIES
 SHALL BE A MIN.OF 29" PER FACBC SEC.
 4.19.2.
  
 CLEARLY SHOW THE REQD.HEIGHT OF THE H.C.
 WATER ON SHT.A204.(17"-19".)PER FACBC
 SEC.4.16.3.
  
 GRAB BARS BEHIND WATER CLOSETS SHALL BE
 36"LONG PER FACBC SEC.4.16.4,4.17.6.(SEE
 SHT.A204.)
  
 SHOWER VALVES SHALL COMPLY W/SPC SEC.613
 NOTE ON PLANS.
  
 DORMITORY ROOMS SHALL COMPLY W/FEDERAL
 FAIR HOUSING ACT.
  
 SHT.A105 SHOWS A CLEANING/STORAGE AREA
 W/WASHER & DRYER.WASHERS ARE ALSO SHOWN
 IN THE DORMS.THIS IS A COMMERCIAL
 FACILITY AND REQS.AN INTERCEPTOR PER
 SPC SEC.1004.1,1004.10.1.1.
 AND CLEANING /STORAGE AREA SHALL BE
 EQUIPPED W/A FLOOR DRAIN.SPC SEC.409.4.5
  
 SHT.A204-SHOWER FLOOR SHALL BE DRAINED
 SO THAT NO WASTE WATER FROM ANY SHOWER
 HEAD WILL PASS OVER FLOOR AREAS OCCUPIED
 BY OTHER BATHERS.SPC SEC.409.8.3.
  
 CONTACT RODNEY COMPO AT CITY OF W.P.B.
 REGIONAL WASTEWATER TREATMENT PLANT FOR
 REQS./SIZE OF GREASE TRAP.(561)835-7423
  
 THE SUBMITTED GAS DRAWING LACKS THE
 NECESSARY INFORMATION TO PERFORM A
 PROPER REVIEW.SHOW TYPE OF MATERIAL FOR
 PIPING,DISTANCE TO MOST REMOTE OUTLET,
 CUT SECTIONS OF PIPE,ETC.COMPLY W/STD.
 GAS CODE SEC.302,305.2,305.3.2,306,ETC.
 INDICATE TYPE OF GAS-NATURAL OR LP.
  
 SHT.A211-CLEARLY SHOW TERMINATION PT.OF
 TRUCK WELL DRAIN.SPC 104.2.1.
  
 SUBMIT MANUF. SHEETS FOR GAS EQUIP.PER
 STD.GAS CODE SEC.402.1
  
 THE SUBMITTED SANITARY RISER HAS TOO
 MANY CODE VIOLATIONS TO LIST.SUBMIT A
 SANITARY RISER THAT COMPLIES W/THE STD.
 PLBG.CODE.
  
 THE SANITARY ISOMETRIC DOESN'T CORRELATE
 W/THE BUILDING FLOOR PLAN.SPC 104.2.1.

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-01-25 Cont ID  
Sent By tlarge Date 1999-07-24 Time 10:29 Rev Time 8.00
Received By tlarge Date 1999-07-24 Time 11:21 Sent To  
Notes
2001-01-08 00:00:00SUBMIT OCCUPANT LOAD PER STD.PLBG.CODE
 SEC.407.1.1, 407.1.3 TO ENSURE
 COMPLIANCE FOR MINIMUM FIXTURE REQ'S.
 FIXTURE REQ'S.SHALL BE BASED ON EQUAL
 NUMBER OF MALES AND FEMALES.
  
 FIXTURE REQ'S.SHALL COMPLY W/FLA.STATUTE
 553.141.(POTTY PARITY.).
  
 HANDICAP DRINKING FOUNTAINS SHALL COMPLY
 W/F.A.C.B.C.SEC.4.1.3(10)(A)(B).
  
 HANDICAP TOILET STALLS IN DRESSING ROOMS
 AND COMMON RESTROOMS SHALL COMPLY W/FLA.
 ACCESS.CODE SECS.4.17.3(SEE EXCEPTION:
 NEW CONSTTRUCTION.)
  
 HANDICAP TOILET/STALLS SHALL HAVE 60"
 CLEAR TURNING SPACE PER F.A.C.B.C. SEC.
 4.2.3.(WATER CLOSET INFRINGES ON TURNING
 SPACE IN SOME ROMMS -CHECK ALL STALLS
 AND TOILET ROOMS AND REVISE).
  
 SEATS IN HANDICAP SHOWERS SHALL COMPLY
 W/F.A.C.B.C. SEC.4.21.3.
  
 CLEARLY SHOW ALL DIMENSIONS OF HANDICAP
 SHOWER STALLS.COMPLY W/F.A.C.B.C.SEC.
 4.21.2.
  
 EACH PUBLIC OR COMMON USE TOILET
 FACILITY SHALL COMPLY W/F.A.C.B.C. SEC.
 4.22.(SEE SEC.4.1.2.(6).
  
 CLEAR FLOOR SPACE UNDER H.C.LAVS.SHALL
 COMPLY W/F.A.C.B.C.SEC.4.19.2.
  
 HEIGHT OF H.C.WATER CLOSETS SHALL COMPLY
 W/F.A.C.B.C.SEC.4.16.3.
  
 AN ADDITIONAL H.C STALL IS REQ'D.IN THE
 RESTROOMS PER F.A.C.B.C.SEC.4.22.4
  
 DORMITORY ROOMS SHALL COMPLY W/FLA.
 ACESS.CODE SEC.9.1 THRU 9.1.5, 9.2.1 -
 9.2.
  
 GANG SHOWERS SHALL COMPLY W/STD. PLBG.
 CODE SEC.409.8.3.
  
 SHOWER VALVES SHALL COMPLY W/STD.PLBG.
 CODE SEC.613.1.(NOTE ON PLANS.).
  
 SHOW TYPICAL SPACING FOR URINALS PER
 STD.PLBG.CODE SEC.403.4.
  
 HANDICAP SHOWERS SHALL BE EQUIPPED W/
 SPRAY UNITS PER F.A.C.B.C.SEC.4.21.6.
  
 LINT INTERCEPTORS ARE REQ'D.FOR THE
 COMMON LAUNDRY AREAS PER STD.PLBG.CODE
 SEC.1004.1,1004.10.1.1.
  
 LAUNDRY ROOMS SHALL BE EQUIPPED W/FLOOR
 DRAINS PER STD.PLBG.CODE SEC.409.4.5.
  
 SUBMIT A COMPLETE GAS RISER DIAGRAM
 SHOWING TYPE OF MATERIAL,APPLIANCES,BTU
 LOAD OF EA.APPLIANCE,TOTAL BTU LOAD OF
 THE SYSTEM,ETC.COMPLY W/STANDARD GAS
 CODE SECS.302, 305.2,305.3.2,306,ETC.
  
 SUBMIT A WATER AND SANITARY ISOMETRIC
 THAT CLEARLY REFLECTS THE ENTIRE SCOPE
 OF PLUMBING WORK TO BE PERFORMED.SPC
 SEC 104.2.1.(INCLUDE ALL INDIRECT WASTE)
  
 SPACING OF CLEANOUTS IN THE DRAINAGE
 SYSTEM SHALL COMPLY W/SPC SEC.710.2.1
 THRU SEC.712.2.
  
 FLOOR DRAINS SHALL NOT EXCEED ALLOWABLE
 DISTANCES FROM VENT PER TABLE 908.1 OF
 SPC.
  
 SHT.P-5-SHOWS FLOOR DRAIN IN STORAGE
 ROOM.DETAIL TYPE OF MATERIALS TO BE
 STORED IN THIS ROOM.
  
 SHT.A 206-SHOWS DRAIN IN TRUCKWELL AREA.
 INDICATE TERMINATION PT.OF DRAIN.
  
 LOCATION OF GREASE INTERCEPTORS SHALL
 COMPLY W/STD.PLBG.CODE SEC.1004.8 AND
 STATE OF FLA.DEPT.OF HEALTH REQ'S.
  
 SUBMIT DETAIL OF GREASE INTERCEPTOR FOR
 REVIEW.SPC 104.2.1.
 --PLANS SHALL BE ROUTED TO PALM BEACH
 COUNTY HEALTH UNIT.(561)355-3018.


Account Summary | Usage Policy | Privacy Policy