Plan Review Details - Permit 99070655
Plan Review Stops For Permit 99070655
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 1999-09-01 Cont ID  
Sent By hpiskura Date 1999-09-01 Time 14:19 Rev Time 2.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 1999-08-12 Cont ID  
Sent By hpiskura Date 1999-08-12 Time 08:39 Rev Time 3.50
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-08-12 Cont ID  
Sent By jleahy Date 1999-08-12 Time 09:48 Rev Time 1.00
Received By jleahy Date 1999-08-12 Time 09:47 Sent To  
Notes
2001-01-08 00:00:00POWER FROM ONE BUILDING NOT TO ENTER THE
 OTHER BUILDING WITHOUT SETTING A DISC.
 IN THE MAIN ELECTRICAL ROOM OF OTHER BLD

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-09-01 Cont ID  
Sent By hpiskura Date 1999-09-01 Time 14:20 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-07-27 Cont ID  
Sent By ndenmark Date 1999-07-27 Time 12:51 Rev Time 0.33
Received By ndenmark Date 1999-07-27 Time 12:51 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 FIRE DAMPERS REQUIRED AT ALL DUCTS
 PENETRATING RATED WALLS SEE M-1 AND M-3

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-08-27 Cont ID  
Sent By tlarge Date 1999-08-17 Time 14:40 Rev Time 0.10
Received By tlarge Date 1999-07-20 Time 16:05 Sent To  
Notes
2001-01-08 00:00:00 
  
  
  
  
  
  
  
  
  
 SUBMIT DETAIL FOR WATER AND SANITARY
 CONNECTIONS TO X-RAY PROCESSOR.(IF
 APPLICABLE.SEE ABOVE COMMENT.)SPC 104.2.
  
 BREAKROOM SINK SHALL COMPLY W/F.A.C.B.C.
 SECS.4.24.1.-4.24.7.
 0 /
 SHT.A-3-CLEARANCE TO BOTTOM OF LAV.FROM
 F.F.SHALL COMPLY W/F.A.C.B.C.SEC.4.19.2
  
 HANDICAP DRINKING FOUNTAIN SHALL COMPLY
 W/F.A.C.B.C. SEC.4.1.3 (10)(A).
  
 SHT.P-2 - RELIEF LINE AND PAN DRAIN
 SHALL NOT BE INTERCONNECTED PER SPC
 SEC.507.8.3.,507.8.4.
  
 SUBMIT A COMPLETE WATER ISOMETRIC THAT
 REFLECTS ENTIRE SCOPE OF WORK TO BE
 PERFORMED.WATER SUPPLY CONTROL SHALL
 COMPLY W/SPC 610.4.1, 610.4.2.
  
 SIZE ALL SECTIONS OF THE SANITARY RISER
 AND NOTE SLOPE OF PIPE PER SPC SEC.714.1
 714.2.
  
 INDICATE OCCUPANT LOAD ON PLANS TO
 ENSURE COMPLIANCE W/ SPC TABLE 407.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-07-12 Cont ID  
Sent By gjoyce Date 1999-07-12 Time 15:24 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***