Plan Review Details - Permit 99070649
Plan Review Stops For Permit 99070649
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-08-11 Cont ID  
Sent By hpiskura Date 1999-08-11 Time 11:36 Rev Time 2.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-07-19 Cont ID  
Sent By lsmith Date 1999-09-27 Time 14:50 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00PER JL PRIVISO SEE PLANS

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-07-26 Cont ID  
Sent By lsmith Date 1999-09-27 Time 14:51 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00PER MEC PROVISO 7/26/99

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-08-02 Cont ID  
Sent By ndenmark Date 1999-08-02 Time 15:11 Rev Time 0.33
Received By ndenmark Date 1999-08-02 Time 15:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-09-25 Cont ID  
Sent By tlarge Date 1999-09-25 Time 09:25 Rev Time 1.00
Received By tlarge Date 1999-09-25 Time 09:25 Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO****************
 NUMBER OF REQD.SANITARY FACILITIES SHALL
 COMPLY W/SPC TABLE 407 PENDING APPEAL
 DECISION.COPY OF BOARD DECISION REQD.
 PRIOR TO RGH.PLBG.INSP.SPC108.4.1
  
 A LETTER FROM THE MANUF.OF THE PROCESSOR
 IS REQD.STATING PH OF EFFLUENT IS WITHIN
 ACCEPTABLE RANGE OF 5-10.SPC SEC.801.4

Review Stop P PLUMBING
Rev No 2 Status F Date 1999-07-20 Cont ID  
Sent By tlarge Date 1999-07-20 Time 12:46 Rev Time 2.50
Received By tlarge Date 1999-07-20 Time 12:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-08-27 Cont ID  
Sent By tlarge Date 1999-08-27 Time 11:23 Rev Time 1.50
Received By tlarge Date 1999-08-27 Time 11:23 Sent To  
Notes
2001-01-08 00:00:00CLEARLY SHOW THAT WALLS AND FLOORS OF
 TOILET ROOMS COMPLY W/STD.BLDG.CODE SEC.
 1204.2.
  
 EFFLUENT FROM PROCESSOR SHALL BE
 RENDERED INNOCUOUS PRIOR TO DISCHARGE TO
 SANITARY SEWER.SUBMIT VERIFICATION FROM
 MANUFACTURER OF PH RANGE.(ACCEPTABLE
 RANGE IS BETWEEN 5-10.)SPC 801.4.
  
 SHT.A-3.CLEARANCE TO BOTTOM OF LAV.FROM
 F.F.SHALL COMPLY W/F.A.C.B.C.SEC.4.19.2.
  
 HANDICAP DRINKING FOUNTAIN SHALL COMPLY
 W/F.A.C.B.C.SEC.4.1.3(10)(A).
  
 THE MINIMUM FIXTURE REQS.FOR THE
 OCCUPANT LOAD SHALL COMPLY W/TABLE 407
 OF SPC.
  
 CLEARLY SIZE ALL VENTS ON THE SANITARY
 SYSTEM.COMPLY W/TABLES 920.2,920.4 OF
 SPC.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 610.4.1 ,610.4.2.
  
 OVER 4 FIXTURES ARE CONNECTED TO 1/2"
 H.W.PER COUNTYWIDE AMENDMENTS SEC.607.7
  
 SHT.A-4.BREAKROOM SINK SHALL COMPLY W/
 F.A.C.B.C.SEC.4.24.1 -4.24.7.