Plan Review Details - Permit 99070638
Plan Review Stops For Permit 99070638
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 1999-10-12 Cont ID  
Sent By hpiskura Date 1999-10-12 Time 15:32 Rev Time 0.00
Received By hpiskura Date   Time   Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 1999-08-02 Cont ID  
Sent By hpiskura Date 1999-08-02 Time 10:31 Rev Time 1.50
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 1999-10-07 Cont ID  
Sent By jleahy Date 1999-10-07 Time 09:45 Rev Time 0.45
Received By jleahy Date 1999-10-07 Time 09:23 Sent To  
Notes
2001-01-08 00:00:001) SUBMIT A RISER DIAGRAM (ELECTRICAL)
  
 2) PLEASE INDICATE THE 12-20 AMPERE CKTS
 THAT ARE BEING INSTALLED.SHOW
 LOCATIONS!
  
 3) SUBMIT PANEL SCHEDULE(S)!
  
 4) SHOW BRANCH CIRCUIT NUMBERS ON PLANS.
  
 5) IS THIS A SEPERATE TENNANT SPACE!!!!
 IF SO SHOW PANEL LOCATION AND MAIN!!

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-07-27 Cont ID  
Sent By lhatten Date 1999-07-27 Time 10:40 Rev Time 0.45
Received By lhatten Date 1999-07-27 Time 10:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-07-16 Cont ID  
Sent By hpiskura Date 1999-08-02 Time 10:32 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 1999-07-23 Cont ID  
Sent By ndenmark Date 1999-07-23 Time 08:46 Rev Time 0.25
Received By ndenmark Date 1999-07-23 Time 08:46 Sent To  
Notes
2001-01-08 00:00:00NO MECHANICAL, PROVIDE PLANS WITH MECH
 PERMIT APPLICATION

Review Stop P PLUMBING
Rev No 2 Status F Date 1999-10-02 Cont ID  
Sent By pschmitz Date 1999-10-02 Time 14:17 Rev Time 0.75
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00UNSAT PLUMBING PLAN REVIEW
 (1) SHT-3,SCOPE OF WORK,AS PER YOUR NOTE
 #5, CREATE A DRAWING OF EXACT
 LOCATION OF FUTURE PLUMBING.

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-07-19 Cont ID  
Sent By tlarge Date 1999-07-19 Time 14:42 Rev Time 1.25
Received By pschmitz Date 1999-07-19 Time 14:41 Sent To  
Notes
2001-01-08 00:00:00CLEARLY SHOW DIMENSIONS OF HANDICAP
 STALLS.COMPLY W/F.A.C.B.C.FOR MIN.CLEAR-
 ANCES FOR FIXTURES,HEIGHT REQ'S.,ETC.
 SEE SECS.4.17.3.(EXCEPTION:NEW
 CONSTRUCTION),4.16.3, 4.18.2, 4.19.2,
  
 WATER CLOSET IN WOMEN'S RESTROOM SHALL
 BE LOCATED IN CORNER,DIAGONAL TO THE
 DOOR PER F.A.C.B.C.SEC.4.17.3.
  
 WALLS AND FLOORS OF TOILET ROOMS SHALL
 COMPLY W/ STD.BLDG.CODE SEC.1204.2
  
 INDICATE OCCUPANT LOAD (INCLUDING
 EMPLOYEES)TO ENSURE COMPLIANCE FOR MIN.
 FIXTURE REQ'S PER SPC TABLE 407.
  
 A DRINKING FOUNTAIN IS REQ'D.PER SPC
 TABLE 407.
  
 FLOOR DRAINS SHALL BE EQUIPPED W/TRAP
 PRIMERS PER SPC SEC.409.4.1.1.
  
 SIZE ALL VENTS ON THE SAN.RISER & NOTE
 SLOPE OF PIPE. SPC TABLES 714.1, 714.2,
 920.2.

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By hpiskura Date 1999-10-12 Time 15:37 Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***