Plan Review Details - Permit 99070232
Plan Review Stops For Permit 99070232
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-07-29 Cont ID  
Sent By hpiskura Date 1999-07-29 Time 07:55 Rev Time 1.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-01-05 Cont ID  
Sent By dpalmer Date 2000-01-05 Time 16:40 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00*******PANEL WAS INCREASED TO 200 AMPS
 AND AIC RATING WAS GIVEN.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 1999-12-28 Cont ID  
Sent By dpalmer Date 1999-12-28 Time 08:25 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00***************UNSAAT*****************
  
 1)NOTE: LOAD STILL EXCEEDS PANEL RATING.
 SEE ORIG. NOTES ATTACHED BY JAKE LEAHY.
 PLEASE INCREASE PANEL SIZE.
 2)SHOW AIC RATING OF PANEL AND LIST ON
 PANEL SCHEDULE.
  
 PLEASE SUBMIT FOR REVIEW AND APPROVAL.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 1999-11-10 Cont ID  
Sent By jleahy Date 1999-11-10 Time 12:37 Rev Time 0.45
Received By jleahy Date 1999-11-10 Time 12:35 Sent To  
Notes
2001-01-08 00:00:001-RISER DIAGRAM SHOWS 150 AMP MAIN AND
 PANEL AND LOAD CALCULATION SHOWS
 182 AMPS??????
  
 2-PLEASE CHANGE PANEL SIZE AND THE
 WIRE THAT GOES TO THIS PANEL!!!

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-07-27 Cont ID  
Sent By lhatten Date 1999-07-27 Time 10:43 Rev Time 0.30
Received By jleahy Date 1999-07-27 Time 10:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-07-13 Cont ID  
Sent By lsmith Date 1999-07-13 Time 11:28 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00PER FIRE DEPT SIGNED ON APPLICATION

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-08-02 Cont ID  
Sent By ndenmark Date 1999-08-02 Time 09:44 Rev Time 0.25
Received By jleech Date 1999-08-02 Time 09:44 Sent To  
Notes
2001-01-08 00:00:00ADDITIONAL PERMITS REQUIRED FOR HOOD,
 SUPPRESSION SYSTEM, AND WALK IN COOLER
 AND FREEZER SUBMIT PLANS W/PERMIT APPL

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-07-23 Cont ID  
Sent By ndenmark Date 1999-07-23 Time 08:38 Rev Time 0.33
Received By jleech Date 1999-07-23 Time 08:38 Sent To  
Notes
2001-01-08 00:00:00NOTE: ADDITION PERMIT REQUIRED FOR HOOD
 AND SUPPRESSION SYSTEM. SUBMIT PLANS AT
 TIME OF PERMIT APPLICATION FOR THESE

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-01-18 Cont ID  
Sent By tlarge Date 2000-01-07 Time 18:48 Rev Time 0.50
Received By pschmitz Date 2000-01-07 Time 18:48 Sent To  
Notes
2001-01-08 00:00:00SUBMIT ADDITIONAL INFORMATION ON POWER
 VENT FROM MANUFACTURER FOR INSTALLATION
 GUIDELINES PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1,104.2.2.
 01-18-00 SE ATTACHED INFO ON POWER VENT
 INSTALLATION. PES

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-08-26 Cont ID  
Sent By tlarge Date 1999-08-26 Time 12:34 Rev Time 0.33
Received By tlarge Date 1999-08-26 Time 12:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-08-07 Cont ID  
Sent By pschmitz Date 1999-08-07 Time 14:41 Rev Time 0.50
Received By pschmitz Date 1999-08-09 Time 11:30 Sent To  
Notes
2001-01-08 00:00:00UNSAT
 (1) SHT.3 HOTEL BUSINESS REGULATION
 BEFORE PLUMBING PLAN REVIEW 954-958-5520
 (2) SHT 3.DISHWASHER TO SANITARY SEWER.
 (3) SHT 3.FOOD PREP ( VEGITABLE SINK )
 TO BE INDIRECTLY CONNECTED THRU A FS.
 (4) SHT 3.ICE MACHINE WASTE TO DRY
 WELL WITH AIR GAP.
 (5) SHT 3.BACKFLOW PREVENTER ON WATER
 SRVICE REQUIRED.
 END OF COMMENTS