Plan Review Details - Permit 99061564
Plan Review Stops For Permit 99061564
Review Stop P PLUMBING
Rev No 1 Status P Date 1999-07-01 Cont ID  
Sent By tlarge Date 1999-06-28 Time 09:46 Rev Time 0.50
Received By tlarge Date 1999-06-28 Time 09:37 Sent To  
Notes
2001-01-08 00:00:00PIPING SHALL BE SIZED PER APPROPRIATE
 TABLE LISTED IN STANDARD GAS CODE.
 LIST CORRECT SIZING TABLE ON PLAN.
  
 SUBMIT APPROPRIATE EHD OF CSST PER TABLE
 305.4F OF STANDARD GAS CODE.
  
 INDICATE DELIVERY PRESSURE (PSI) ON PLAN
 PER STANDARD GAS CODE SEC.305.4