Plan Review Details - Permit 99061451
| Plan Review Stops For Permit 99061451 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
1999-09-21 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
1999-09-21 |
Time |
16:26 |
Rev Time |
2.00 |
| Received By |
fknapp |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | BLDG DENIED SEE CHECKLIST |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
1999-07-09 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
1999-07-09 |
Time |
16:05 |
Rev Time |
1.00 |
| Received By |
fknapp |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED NEED ARCHITECT |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
1999-07-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
1999-07-07 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
1999-07-07 |
Time |
16:29 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ELECTRICAL WORK TO BE DONE IN BATHS | | | ONLY AS PER CONVERSATION W/ARTHUR- | | | PATTERSON. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
1999-07-08 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-07-08 |
Time |
11:08 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
1999-07-08 |
Time |
11:08 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NO MECHANICAL SHOWN ON PLAN PROVIDE PLAN | | | WITH MECHANICAL PERMIT APPLICATION, BATH | | | ROOMS AND UTILITY ROOM TO HAVE EXHAUST | | | FANS PER 1994 SMC. KITCHEN HOOD TO COMP- | | | LY WITH 1994 SMC AND NFPA 96. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
1999-08-05 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-08-05 |
Time |
14:05 |
Rev Time |
0.75 |
| Received By |
tlarge |
Date |
1999-08-05 |
Time |
14:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
1999-08-05 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-07-08 |
Time |
07:48 |
Rev Time |
1.00 |
| Received By |
tlarge |
Date |
1999-07-08 |
Time |
07:48 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | CLEARLY DETAIL ON THE PLANS ALL NEW AND | | | EXISTING PLUMBING AND SUBMIT A SANITARY | | | AND WATER ISOMETRIC FOR ALL NEW WORK. | | | SPC 104.2.1. | | | | | | SHOW ALL FIXTURE CLEARANCES PER STANDARD | | | PLUMBING CODE SEC.403 AND FLA.ACCESS. | | | CODE FOR BUILDING CONSTRUCTION. | | | | | | CLEARLY SHOW OCCUPANT LOAD ON PLANS TO | | | ENSURE COMPLIANCE W/SPC SEC.407.1.3 & | | | TABLE 407 FOR MIN.FIXTURE REQ'S. | | | | | | PLANS SHOW KITCHEN-DETAIL TYPE OF FOOD | | | PREPARATION TO BE DONE.A GREASE | | | INTERCEPTOR MAY BE REQ'D.PER SPC SEC. | | | 1004.1 THRU 1004.4,1004.7,1004.8. | | | (SIZE AND TYPE TO BE APPROVED BY CITY | | | UTILITY DEPT.) |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
1999-07-20 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
1999-06-24 |
Time |
08:17 |
Rev Time |
0.50 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|