Plan Review Details - Permit 99061417
Plan Review Stops For Permit 99061417
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-07-31 Cont ID  
Sent By hpiskura Date 1999-07-31 Time 08:55 Rev Time 2.00
Received By hpiskura Date   Time   Sent To Z
Notes
2001-01-08 00:00:00OWES IMPACT FEES & RADON

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-01-27 Cont ID  
Sent By jleahy Date 2000-01-27 Time 08:02 Rev Time 0.30
Received By jleahy Date 2000-01-27 Time 08:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-07-31 Cont ID  
Sent By hpiskura Date 1999-07-31 Time 08:57 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-07-31 Cont ID  
Sent By hpiskura Date 1999-07-31 Time 08:56 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2000-03-27 Cont ID  
Sent By cthirben Date 2000-03-27 Time 07:31 Rev Time 1.00
Received By cthirben Date 2000-03-27 Time 07:29 Sent To  
Notes
2001-01-08 00:00:00 
  
 ***********NOTES NOTES NOTES************
 RELOCATION OF OUTSIDE AIR
  
 EXTENSION OF COND. STAND LEGS ON ROOF

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2000-03-16 Cont ID  
Sent By cthirben Date 2000-03-16 Time 08:25 Rev Time 0.50
Received By cthirben Date 2000-03-16 Time 08:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-01-26 Cont ID  
Sent By ndenmark Date 2000-01-26 Time 08:17 Rev Time 0.25
Received By ndenmark Date 2000-01-26 Time 08:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-09-07 Cont ID  
Sent By ndenmark Date 1999-09-07 Time 12:31 Rev Time 0.25
Received By ndenmark Date 1999-09-07 Time 12:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-09-07 Cont ID  
Sent By ndenmark Date 1999-07-10 Time 12:40 Rev Time 0.50
Received By jleech Date 1999-07-10 Time 12:18 Sent To  
Notes
2001-01-08 00:00:00****************DENIED******************
 1) FIRE DAMPERS REQUIRED WHERE DUCT PEN-
 ETRATES RATED WALL CORRIDOR [124]
 2) CONDENSING UNITS TO BE MOUNTED ON
 STANDS PROVIDING MIN. 18" CLEARANCE BE-
 TWEEN FINISHED ROOF SURFACE AND BOTTOM
 OF STAND
 3) HORN AND STROBE REQUIRED FOR NOTIFI-
 CATION OF FAN SHUT DOWN BY DUCT SMOKE
 DETECTOR IF NOT TIED TO BLDG FIRE ALARM
 SYSTEM 1996 NFPA 90A 4-4.4.3

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-09-23 Cont ID  
Sent By tlarge Date 1999-09-23 Time 17:39 Rev Time 0.75
Received By tlarge Date 1999-09-23 Time 17:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-09-24 Cont ID  
Sent By tlarge Date 1999-09-04 Time 07:22 Rev Time 1.50
Received By tlarge Date 1999-09-04 Time 07:22 Sent To  
Notes
2001-01-08 00:00:00CURBS IN HANDICAP SHOWERS SHALL BE MAX.
 1/2" PER FACBC SEC.4.21.7.
  
 SHT.8.3-CLEAR FLOOR SPACE UNDER HANDICAP
 LAV.SHALL BE MIN.29" PER FACBC SEC.
 4.19.2.
  
 CIRCUIT AND LOOP VENTING SYSTEM FOR THE
 SANITARY SYSTEM SHALL COMPLY W/SPC SEC.
 914.1.(A RELIEF VENT,STACK VENT OR VENT
 STACK IS REQD.DOWNSTREAM OF FIRST HORIZ.
 FIXTURE CONNECTION.SPC SEC.914.1.
  
 A DRINKING FOUNTAIN IS REQD.ON THE 2ND
 FLOOR PER SPC TABLE 407 AND MUST COMPLY
 W/FACBC SEC.4.1.3.(10)(A),4.15.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-09-24 Cont ID  
Sent By tlarge Date 1999-07-11 Time 09:32 Rev Time 1.25
Received By tlarge Date 1999-07-11 Time 09:32 Sent To  
Notes
2001-01-08 00:00:00WOMEN'S RESTROOM-THE ACCESIBLE WATER
 CLOSET SHALL BE LOCATED IN THE CORNER,
 DIAGONAL TO DOOR.F.A.C.B.C.SEC.4.17.3.
  
 SINKS IN LOUNGE/BREAKROOM SHALL COMPLY
 W/F.A.C.B.C.SEC.4.1.1(A),4.24.1-4.24.7.
 (THESE AREAS ARE NOT CLASSED AS WORK
 AREAS.)
  
 SHT.8.3-CLEAR FLOOR SPACE UNDER H.C.LAV.
 SHALL COMPLY W/F.A.C.B.C.SEC.4.19.2.
  
 SIZE OF SHOWER STALLS SHALL COMPLY W/
 F.A.C.B.C. SEC.4.21.2-4.21.8 & FIGURES
 35(A)(B).
  
 H.C.DRINKING FOUNTAIN SHALL COMPLY W/
 F.A.C.B.C.SEC.4.1.3(10)(A).
  
 SUBMIT OCCUPANT LOAD FOR MINIMUM FIXTURE
 REQ'S.PER STD.PLBG.CODE TABLE 407.
  
 INDICATE SLOPE OF SANITARY SYSTEM ON
 PLAN PER STD.PLBG.CODE SEC.705.2,705.3.
  
 CIRCUIT AND LOOP SYSTEM SHALL COMPY
 W/STD.PLBG.CODE SEC.914.1-914.3.4.
  
 WATER TO APPLIANCES SHALL BE PROTECTED
 AGAINST BACKFLOW PER STD.PLBG.CODE SEC.
 606.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/
 STD.PLBG.CODE SEC.610.4.1,610.4.2.
  
 WATER PURIFICATION SYSTEM SHALL BE NSF
 APPROVED PER STD.PLBG.CODE SEC.615.1.
  
 MAX.OF 2 FIXTURES SHALL BE SUPPLIED BY
 1/2" C.W.& 4 FIXTURES BY 1/2"H.W.PER
 COUNTYWIDE AMENDMENTS TO STD.PLBG.CODE.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-09-24 Cont ID  
Sent By hpiskura Date 1999-07-31 Time 08:57 Rev Time 0.75
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEED LEVEL 1 SITE PLAN REVIEW