Plan Review Details - Permit 99061271
Plan Review Stops For Permit 99061271
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-06-23 Cont ID  
Sent By dpalmer Date 1999-06-23 Time 17:04 Rev Time 0.00
Received By dpalmer Date 1999-06-23 Time 17:04 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO******************
  
 NEED TO SUBMIT INFORMATION ON AIC RATING
 FROM FAULT CURRENT CACULATIONS,PLEASE
 HAVE DRAWN ON PANEL SCHD.
 ART.215-5
 NOTE: SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.
 NOTE:EQUIPMENT GROUNDING COND.REQ`D
 FROM MAIN DISC.TO PANEL.
  
 NEED THE ABOVE INFORMATION BEFORE ROUGH
 INSPECTION IS CALLED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-07-17 Cont ID  
Sent By jleech Date 1999-07-17 Time 09:06 Rev Time 0.50
Received By jleech Date 1999-07-17 Time 09:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-07-10 Cont ID  
Sent By pschmitz Date 1999-07-10 Time 12:14 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-08-09 Cont ID  
Sent By jgomez Date 1999-08-09 Time 18:50 Rev Time 2.00
Received By jgomez Date   Time   Sent To O
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE TRUSS DWGS SIGNED AND SEALED,
 INCLUDING THE TRUSS LAYOUT.SEC.104.2.2
 CITY AMENDMENTS.
 DESIGNER OF RECORD TO REVIEW ALL TRUSS
 DWGS PRIOR TO SUBMITTAL TO THIS OFFICE
 2-ENTRY DOOR TO HAVE 32"MIN.CLEAR OPEN'G
 TABLE 1004 SBC 1997.
 3-PROVIDE SAFETY GLASS AT GUEST BATH
 SEC. 2405.2 SBC 1997.
 4-GAS APPLIANCES IN GARAGE. SPECIFY HOW
 TO COMPLY WITH SEC. 402.7 SGC 1997.
 5-FOOTING F2 TO BE 16"MIN DEEP AS PER
 1804.1.3 SBC/97 & 1804.1.9 CITY AMENDM
 6-PROVIDE THE DESIGN PRESSURES AT ALL
 EXTERIOR OPENINGS.SEC 1606 SBC 1997.
 7-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS, HORIZONTAL WINDOWS,MULLIONS FOR
 TRANSOMS ABOVE SLIDING GLASS DOORS,
 ROUND WINDOWS.
 8-SEE PLANS FOR ADDITIONAL COMMENTS.
  
 NOTE:
 REVISE ORIGINAL DRAWINGS AS REQUIRED.
 ALSO, ALL NOTES AND SPECIFICATIONS NEED
 TO BE UPDATED TO 1997 SBC.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-06-21 Cont ID  
Sent By gjoyce Date 1999-06-21 Time 10:04 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***