Plan Review Details - Permit 99061270
Plan Review Stops For Permit 99061270
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-06-28 Cont ID  
Sent By dpalmer Date 1999-06-28 Time 19:09 Rev Time 0.50
Received By dpalmer Date 1999-06-28 Time 19:09 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO******************
  
 NEED TO SUBMIT AIC RATING FROM FAULT
 CURRENT CALCULATIONS.PLEASE SHOW ON
 PLANS ON PANEL SCHED.215-5
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.
 NOTE:EQUIPMENT GROUNDING CONDUCTOR
 REQ`D FROM MAIN DISCONNECT TO PANEL.
 ART'S.250-92/250-95
  
 PLEASE RESUBMIT BEFORE ROUGH INSPECTION
 IS CALLED IN.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-07-17 Cont ID  
Sent By jleech Date 1999-07-17 Time 09:03 Rev Time 0.50
Received By jleech Date 1999-07-17 Time 09:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-08-10 Cont ID  
Sent By jgomez Date 1999-08-10 Time 11:06 Rev Time 0.25
Received By jgomez Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-08-09 Cont ID  
Sent By jgomez Date 1999-08-09 Time 18:18 Rev Time 2.00
Received By jgomez Date   Time   Sent To O
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE TRUSS DWGS SIGNED AND SEALED,
 INCLUDING THE TRUSS LAYOUT.SEC 104.2.2
 CITY AMENDMENTS.
 DESIGNER OF RECORD TO REVIEW ALL TRUSS
 DWGS PRIOR TO SUBMITTAL TO THIS OFFICE
 2-ENTRY DOOR TO HAVE 32"MIN.CLEAR OPEN'G
 TABLE 1004 SBC 1997.
 3-PROVIDE SAFETY GLASS AT GUEST BATH
 SEC. 2405.2 SBC 1997.
 4-GAS APPLIANCES IN GARAGE: SPECIFY HOW
 TO COMPLY WITH SEC. 402.7 SGC 1997.
 5-FOOTING F2 TO BE 16" MIN. DEEP AS PER
 1804.1.3 SBC/97 & 1804.1.9 CITY AMENDM
 6-PROVIDE THE DESIGN PRESSURES AT ALL
 EXTERIOR OPENINGS.SEC. 1606 SBC 1997.
 7-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS, HORIZONTAL WINDOWS,MULLIONS FOR
 TRANSOMS ABOVE SLIDING GLASS DOORS,
 ROUND WINDOWS.
 8-SEE PLANS FOR ADDITIONAL COMMENTS.
  
 NOTES:
 A-REVISE ORIGINAL DRAWINGS AS REQUIRED.
 ALSO, ALL NOTES AND SPECIFICATIONS
 NEED TO BE UPDATED TO 1997 SBC.
 B-GENERAL NOTES ON SHEET A-7 ARE NOT
 LEGIBLE.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-06-21 Cont ID  
Sent By gjoyce Date 1999-06-21 Time 09:59 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved