Plan Review Details - Permit 99060896
| Plan Review Stops For Permit 99060896 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
1999-06-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
1999-06-23 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
1999-06-23 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************PROVISO******************* | | | | | | NEED TO SUBMIT AIC RATING FROM FAULT | | | CURRENT CALCS. | | | GRND, AND GRND.OF EQUIP. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
1999-07-10 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
1999-07-10 |
Time |
12:53 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
1999-07-10 |
Time |
12:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
1999-07-10 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
1999-07-10 |
Time |
09:18 |
Rev Time |
0.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
1999-09-28 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
1999-09-28 |
Time |
13:39 |
Rev Time |
2.00 |
| Received By |
jgomez |
Date |
1999-09-28 |
Time |
13:39 |
Sent To |
O |
|
| Notes |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | | 1*ARCHITECT SPECIFIED GIRDER TRUSS AT | | | FRONT PORCH. PROVIDE COMPLETE DETAIL | | | AND SPECIFY ALL CONNECTORS. | | | *PROVIDE COMPLETE SPECIFICATIONS AND | | | SIZES FOR FOR DETAIL B-6. | | | *REVISE CONNECTOR C-A6 AS REQUIRED TO | | | RESIST THE UPLIFT LOADS CALCULATED ON | | | ENGINEERED TRUSSES. | | | 2-ENGINEERED TRUSS LAYOUT DOESN'T SHOW | | | GIRDER TRUSS AT FRONT PORCH. REVISE AND | | | PROVIDE ENGINEERING AS REQUIRED. | | | -TRUSS DRAWINGS NEED TO BE UPDATED TO | | | ASCE 7-95. | | | CUTTING, PASTING AND COPYING OF ALL | | | ENGINEERED TRUSSES WILL NOT BE ACCEPTED | | | 3-REVISE ALL ORIGINAL DRAWINGS SHOWING | | | ALL CORRECTIONS/CLARIFICATIONS. | | | 4-PROVIDE PRODUCT APPROVAL FOR SLIDING | | | GLASS DOORS WITH TRANSOM ABOVE ASSEMBLY | | | 5-MINIMUM CLEAR OPENING AT BEDROOM #2 TO | | | BE 5 S.F. SEC. 1005.4.4 SBC 1997. | | | PROVIDE THE EXACT DIMENSIONS FOR SUCH | | | WINDOWS PRIOR TO INSTALLATION. | | | 6-PROVIDE PRODUCT APPROVAL FOR ENTRY | | | DOORS PRIOR TO INSTALLATION. | | | 7-GARAGE DOOR PRODUCT APPROVAL DOESN'T | | | MEET THE DESIGN PRESSURES CALCULATED BY | | | THE ARCHITECT. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
1999-07-20 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
1999-07-20 |
Time |
17:12 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
|
Time |
|
Sent To |
D |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
1999-06-15 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
1999-06-15 |
Time |
09:12 |
Rev Time |
|
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|