Plan Review Details - Permit 99060891
| Plan Review Stops For Permit 99060891 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
1999-06-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
1999-06-25 |
Time |
20:41 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
1999-06-25 |
Time |
20:41 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************PROVISO****************** | | | | | | NEED TO SUBMIT PLANS WITH AIC RATING | | | DRAWN ON PANEL SCHED.ART.215-5 | | | NOTE:SMOKE DETECTORS REQ`D INSIDE AND | | | OUTSIDE BEDROOMS. | | | NOTE:EQUIPMENT GROUNDING CONDUCTOR | | | REQ`D FROM MAIN DISC.TO PANEL. | | | ART.250-92/250-95 | | | | | | NEED THE ABOVE INFORMATION SUBMITTED | | | BEFORE ROUGH INSPECTION IS CALLED IN. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
1999-07-10 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
1999-07-10 |
Time |
14:20 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
1999-07-10 |
Time |
14:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
1999-07-10 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
1999-07-10 |
Time |
09:48 |
Rev Time |
0.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
1999-08-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
1999-08-09 |
Time |
10:01 |
Rev Time |
2.00 |
| Received By |
jgomez |
Date |
|
Time |
|
Sent To |
O |
|
| Notes |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | | 1-PROVIDE TRUSS DWGS SIGNED AND SEALED, | | | INCLUDING THE TRUSS LAYOUT. | | | DESIGNER OF RECORD TO REVIEW ALL TRUSS | | | DWGS PRIOR TO SUBMITTAL TO THIS OFFICE | | | 2-ENTRY DOOR TO HAVE 32"MIN.CLEAR OPEN'G | | | TABLE 1004 SBC 1997 | | | 3-PROVIDE SAFETY GLASS AT GUEST BATH | | | SEC 2405.2 SBC 1997 | | | 4-GAS APPLIANCES IN GARAGE. SPECIFY HOW | | | TO COMPLY WITH SEC 402.7 SGC 1997 | | | 5-FOOTING F2 TO BE 16" MIN. DEEP. AS PER | | | 1804.1.3 SBC/97 & 1804.1.9 CITY AMENDM | | | 6-PROVIDE THE DESIGN PRESSURES AT ALL | | | EXTERIOR OPENINGS. SEC 1606 SBC 1997 | | | 7.PROVIDE PRODUCT APPROVAL FOR ENTRY | | | DOORS,HORIZONTAL WINDOWS, MULLIONS FOR | | | TRANSOMS ABOVE SLIDING GLASS DOORS, | | | ROUND WINDOWS. | | | 8-SEE PLANS FOR ADDITIONAL COMMENTS |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
1999-06-15 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
1999-06-15 |
Time |
09:23 |
Rev Time |
|
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|