Plan Review Details - Permit 99060870
Plan Review Stops For Permit 99060870
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-03-22 Cont ID  
Sent By hpiskura Date 2000-03-22 Time 09:17 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00REV FOR THIRD FLOOR OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-09-07 Cont ID  
Sent By lmartine Date 1999-07-27 Time 17:41 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-03-22 Cont ID  
Sent By dpalmer Date 2000-03-22 Time 07:14 Rev Time 0.00
Received By dpalmer Date 2000-03-22 Time 07:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-07-27 Cont ID  
Sent By lmartine Date 1999-07-27 Time 17:41 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-07-27 Cont ID  
Sent By lmartine Date 1999-07-27 Time 17:42 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-03-14 Cont ID  
Sent By ndenmark Date 2000-03-14 Time 13:52 Rev Time 0.32
Received By ndenmark Date 2000-03-14 Time 13:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-08-25 Cont ID  
Sent By ndenmark Date 1999-08-25 Time 15:39 Rev Time 0.33
Received By ndenmark Date 1999-08-25 Time 15:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-09-03 Cont ID  
Sent By ndenmark Date 1999-06-21 Time 10:45 Rev Time 1.00
Received By lmartine Date 1999-06-21 Time 10:45 Sent To  
Notes
2001-01-08 00:00:00*********DENIED*************************
  
 1) FIRE DAMPERS TO BE AT ALL RATED WALLS
 I.E. MECH RM 111AND 32X12 R/A OPENING
 ABOVE DOOR(112)
 2) DUCT DETECTOR IN RETURN AIR DUCT TO
 BE PRIOR TO ANY MIXING OF OUTSIDE AIR

Review Stop P PLUMBING
Rev No 5 Status P Date 2000-05-11 Cont ID  
Sent By tlarge Date 2000-05-11 Time 10:10 Rev Time 0.65
Received By tlarge Date 2000-05-11 Time 10:10 Sent To  
Notes
2001-01-08 00:00:00PLBG.REVISION-RUN CONDENSATE TO FLOOR
 SINK.

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-03-06 Cont ID  
Sent By tlarge Date 2000-03-06 Time 06:01 Rev Time 0.25
Received By tlarge Date 2000-03-06 Time 06:01 Sent To  
Notes
2001-01-08 00:00:00NO PLBG.THIS REVISION.

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-08-20 Cont ID  
Sent By pschmitz Date 1999-08-20 Time 09:49 Rev Time 0.75
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO: WTR HTR TO BE READLY
 ACCESSIBLE,SPC 94 SEC 501.7

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-08-20 Cont ID  
Sent By tlarge Date 1999-08-07 Time 08:37 Rev Time 1.25
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00****************2ND.FLOOR***************
 COMPLY W/ALL PREVIOUS COMMENTS DATED
 7/13/99.(COMENTS HAVE NOT BEEN PROPERLY
 ADDRESSED.)
  
 THE OCCUPANT LOAD SHALL BE CLEARLY NOTED
 ON THE PLANS.SPC 104.2.1.
  
 WALLS AND FLOORS OF PUBLIC RESTROOMS
 SHALL COMPLY W/SBC 1204.2.(SUBMIT MANUF.
 SHEETS FOR SEMI-GLOSS PAINT TO ENSURE
 COMPLIANCE W/CODE FOR "NON-ABSORBENT"
 MATERIAL.)
  
 WATER HEATER SHALL BE READILY
 ACCESSIBLE PER SPC SEC 501.7, SEC.202
 (DEFIN.)OF SBC.(SEE DEFIN.OF READILY
 ACCESIBLE.)
  
 PAN DRAIN AND RELIEF ARE STILL SHOWN AS
 BEING INTERCONNECTED.COMPLY W.SPC SEC.
 507.8.4.
  
 CLEARLY SHOW DIMENSIONS(LXW)OF HANDICAP
 TOILET STALL ON THE PLANS.COMPLY W/
 F.A.C.B.C. SEC.4.17.3.(SEE NEW
 CONSTRUCTION.-76" IS NOT WIDE ENOUGH.)
  
 DRINKING FOUNTAINS ARE NOT INDICATED ON
 THE PLBG.WATER OR SANITARY ISOMETTRICS.
 SHOW WATER SUPPLY CONTROL VALVES TO D.F.
 PER SPC 104.2.1.
 D.F'S ARE NOT SHOWN PLBG.FLOOR PLAN ON
 P-1.
 *****************3RD.FLOOR**************
 DRINKING FOUNTAIN IS REQ'D.PER TABLE 407
 OF SPC.
  
 WALLS & FLOORS OF TOILET ROOMS SHALL BE
 NON-ABSORBENT MATERIAL PER SBC SEC.
 1204.2(SUBMIT MANUF.SHEETS FOR PAINT.)
  
 FIXTURE CLEARANCE OF H.C.WATER CLOSET
 FROM WALL SHALL COMPLY W.F.A.C.B.C. SEC.
 4.17.2, FIGS.30(A)(B).
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7, 202.(SEE DEFIN.OF
 READILY ACCESSIBLE.)
  
 PAN DRAIN AND RELIEF VALVE DRAIN SHALL
 NOT BE INTERCONNECTED PER STD.PLBG.CODE
 SEC.507.8.4.
  
 CLEARLY SHOW DIMENSIONS OF HANDICAP
 STALL ON PLANS.COMPLY W/F.A.C.B.C.SEC.
 4.17.3-NEW CONSTRUCTION.(76" DOES NOT
 COMPLY.)
  
 SHOW HEIGHT OF SINK IN EMPLOYEE LOUNGE.
 COMPLY W/F.A.C.B.C. SECS.4.24.1- 4.24.7.
 (MAX.34" TO TOP OF CABINET.)
  
 FLOOR DRAINS SHALL NOT EXCEED DISTANCE
 FROM VENT AS SPECIFIED IN SPC TABLE 908.
  
 CLEARLY SHOW OCCUPANT LOAD ON PLANS.
 SPC 104.2.1.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-08-20 Cont ID  
Sent By tlarge Date 1999-07-13 Time 16:40 Rev Time 1.25
Received By pschmitz Date 1999-07-13 Time 16:40 Sent To  
Notes
2001-01-08 00:00:00SUBMIT OCCUPANT LOAD TO DETERMINE MIN.
 PLBG.FIXTURE REQ'S.PER STD.PLBG.CODE SEC
 407.1.3,TABLE 407.
  
 DRINKING FOUNTAIN IS REQ'D.PER TABLE 407
 OF STANDARD PLBG.CODE TABLE 407.
  
 WALLS &FLOORS OF TOILET ROOMS SHALL
 COMPLY W/STD.BLDG.CODE SEC.1204.2
  
 FIXTURE CLEARANCE OF H.C.WATER CLOSET
 FROM WALL SHALL COMPLY W/F.A.C.B.C.
 SEC.4.17.2 AND FIGS.30(A)(B)
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 FOR MAINTENANCE,SERVICING AND REPLACE-
 MENT PER STD.PLBG.CODE SEC.501.7, 202,
 (DEFIN.)AND SEC.507.8.
  
 PAN DRAIN AND RELIEFVALVE SHALL NOT BE
 INTERCONNECTED PER STD.PLBG.CODE SEC.
 507.8.4
  
 CLEARLY SHOW DIMENSIONS OF HANDICAP
 STALL ON ARCH.PLANS.COMPLY W/F.A.C.B.C.
 SSEC.4.17.3(SEE EXCEPION-NEW CONST.)
  
 EMPLOYEE LOUNGE SINK SHALL COMPLY
 W/F.A.C.B.C.SEC.4.24.1-4.24.7.(THE
 LOUNGE IS NOT CLASSED AS A WORK AREA.)
  
 FLOOR DRAINS SHALL NOT EXCEED DISTANCE
 FROM VENT AS SPECIFIED IN SPC TABLE 908.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-06-14 Cont ID  
Sent By gjoyce Date 1999-06-14 Time 13:19 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***