Plan Review Details - Permit 99060624
Plan Review Stops For Permit 99060624
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 1999-07-12 Cont ID  
Sent By lmartine Date 1999-07-12 Time 17:50 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-07-01 Cont ID  
Sent By bprusiec Date 1999-07-01 Time 15:28 Rev Time 0.00
Received By bprusiec Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 1999-06-14 Cont ID  
Sent By ndenmark Date 1999-06-14 Time 11:11 Rev Time 0.00
Received By jleech Date 1999-09-16 Time 13:20 Sent To  
Notes
2001-01-08 00:00:00****************DENIED******************
  
 1) OUTSIDE AIR CALCULATIONS REQUIRED PER
 ASHRAE 62-89
 2) OUTSIDE AIR ON M-2 =450CFM M-3 = 300
 CFMCAN UNIT SPECIFIED DO 450CFM O/A?
 3) CONDENSATE DRAIN SHALL TERMINATE IN
 STORM SEWER OR FRENCH DRAIN, NOT SANI-
 TARY SEWER
 4) BACKROOM WITH 400 CFM SHALL RETURN
 AIR PATH TO RETURN AIR OF AHU-1

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-06-26 Cont ID  
Sent By pschmitz Date 1999-06-26 Time 09:58 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00UNSAT: WATER HEATER TO BE READLY
 ACCESSIBLE SPC SEC 501.7 PES

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***