Plan Review Details - Permit 99060275
Plan Review Stops For Permit 99060275
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-06-16 Cont ID  
Sent By dpalmer Date 1999-06-16 Time 15:22 Rev Time 0.00
Received By dpalmer Date 1999-06-16 Time 15:22 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO*******************
  
 NEED:SUBMIT FAULT CURRENT CALCULATIONS
 AND AIC RATING DRAWN ON PLANS WITH
 PANEL SCHEDULE.ART.215-5
 NOTE:EQUIPMENT GROUNDING CONDUCTOR
 REQ`D FROM MAIN TO PANEL.
 NOTE:SMOKE DETECTORS REQ`D INSIDE
 AND OUTSIDE BEDROOMS.
 NOTE:GROUNDING ELECTRODE SYSTEM TO
 INCLUDE BLDG.STEEL.
  
 HAVE THE ABOVE INFORMATION SUBMITTED
 BEFORE ROUGH INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-07-10 Cont ID  
Sent By jleech Date 1999-07-10 Time 07:47 Rev Time 0.50
Received By jleech Date 1999-07-10 Time 07:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-08-05 Cont ID  
Sent By tlarge Date 1999-08-05 Time 09:03 Rev Time 0.33
Received By tlarge Date 1999-08-05 Time 09:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-08-05 Cont ID  
Sent By tlarge Date 1999-07-02 Time 15:25 Rev Time 0.50
Received By tlarge Date 1999-07-02 Time 15:25 Sent To  
Notes
2001-01-08 00:00:00SANITARY RISER DOESN'T MATCH FLOOR PLAN
 SPC SEC.104.2.1,104.3.1.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-08-03 Cont ID  
Sent By jcaloger Date 1999-08-03 Time 16:20 Rev Time 2.00
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-06-07 Cont ID  
Sent By gjoyce Date 1999-06-07 Time 17:13 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***