Plan Review Details - Permit 99060267
Plan Review Stops For Permit 99060267
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-06-18 Cont ID  
Sent By dpalmer Date 1999-06-18 Time 15:25 Rev Time 0.00
Received By dpalmer Date 1999-06-18 Time 15:25 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO*******************
  
 NOTE:RECEPTS.SERVING KITCHEN COUNTER-
 SPACE ARE TO BE GFI/GFI PROTECTED.
 ART21-8-A-6
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.
 NOTE:GFI RECEPTS.REQ`D FRONT OF HOUSE
 ART.210-52E
 NOTE:RECEPT.REQ`D FOR A/C EQUIPMENT.
 ART.210-63
 NEED TO SUBMIT FAULT CURRENT/AIC
 RATING.TO BE LISTED ON PANEL SCHED.
 ART.215-5
 NOTE:GROUNDING ELECTRODE CONDUCTOR
 TO BLDG. STEEL ALSO.
  
 NEED THE ABOVE DRAWN ON PLANS AND
 SUBMITTED BEFORE ROUGH INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-08-13 Cont ID  
Sent By jleech Date 1999-08-13 Time 08:16 Rev Time 0.50
Received By jleech Date 1999-08-13 Time 08:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-08-16 Cont ID  
Sent By jleech Date 1999-07-10 Time 13:23 Rev Time 0.50
Received By jcaloger Date 1999-07-10 Time 13:23 Sent To  
Notes
2001-01-08 00:00:00NO A/C PLAN.
 RESUB 8/11 WITH PLAN

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-12-07 Cont ID  
Sent By tlarge Date 1999-12-07 Time 16:00 Rev Time 0.30
Received By tlarge Date 1999-12-07 Time 16:00 Sent To  
Notes
2001-01-08 00:00:00 
 REVISED SANITARY RISER.

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-08-13 Cont ID  
Sent By tlarge Date 1999-08-13 Time 07:13 Rev Time 0.50
Received By tlarge Date 1999-08-13 Time 07:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-08-13 Cont ID  
Sent By tlarge Date 1999-07-02 Time 14:36 Rev Time 0.50
Received By tlarge Date 1999-07-02 Time 14:36 Sent To  
Notes
2001-01-08 00:00:00SANITARY ISOMETRIC SHALL CORRELATE W/
 FLOOR PLAN. SPC SEC.104.2.1.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-08-16 Cont ID  
Sent By jcaloger Date 1999-08-04 Time 12:11 Rev Time 1.50
Received By jcaloger Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED SEE CHECK LIST

Review Stop Z ZONING
Rev No 1 Status P Date 1999-07-12 Cont ID  
Sent By gjoyce Date 1999-06-07 Time 16:55 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00NO SURVEY, ROOF ENCROACHMENT