Plan Review Details - Permit 99051241
Plan Review Stops For Permit 99051241
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-07-19 Cont ID  
Sent By dpalmer Date 1999-06-25 Time 17:54 Rev Time 0.50
Received By dpalmer Date 1999-06-25 Time 17:54 Sent To  
Notes
2001-01-08 00:00:00OK`D 7/19/99*DENIED*******************
  
 NEED TO SUBMIT LOAD CACULATIONS FOR
 EXISTING SERVICE.ART.220-3-D-1
 PLEASE SHOW RISER DIAGRAM WITH METER,
 PANEL,WIRE SIZES.
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.
 NOTE:OUTLET SPACING 210-52A
 NOTE:EXISTING PANEL MUST HAVE SUFFICENT
 SPACE TO SERVE NEW CIRCUTS INCLUDING
 ART.21-52D BATH RECEPTS.ON 20A CIRCUT.
  
 NEED TO RESUBMIT
  
 OK`D 7/19/99

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-07-19 Cont ID  
Sent By ndenmark Date 1999-07-19 Time 14:03 Rev Time 0.25
Received By ndenmark Date 1999-07-19 Time 14:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-07-20 Cont ID  
Sent By jleech Date 1999-06-26 Time 10:04 Rev Time 0.50
Received By fknapp Date 1999-06-26 Time 10:04 Sent To  
Notes
2001-01-08 00:00:00PROVIDE;
 1. SIZE OF EXISTING A/C UNIT.
 2. SQ. FT. OF EXISTING HOUSE.
 3. SIZE OF DUCT NEW DROPS WILLBE CUT
 INTO.
 4. SEER RATING OF EXISTING A/C UNIT.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-06-26 Cont ID  
Sent By tlarge Date 1999-06-26 Time 09:43 Rev Time 0.50
Received By tlarge Date 1999-06-26 Time 09:43 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-07-20 Cont ID  
Sent By fknapp Date 1999-07-06 Time 15:48 Rev Time 3.00
Received By fknapp Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE ATTACHED CHECKLIST

Review Stop Z ZONING
Rev No 1 Status P Date 1999-07-20 Cont ID  
Sent By gjoyce Date 1999-07-20 Time 14:09 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***