Plan Review Details - Permit 99051209
Plan Review Stops For Permit 99051209
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-02-28 Cont ID  
Sent By dpalmer Date 2000-02-28 Time 06:15 Rev Time 0.00
Received By dpalmer Date 2000-02-28 Time 06:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2000-01-21 Cont ID  
Sent By dpalmer Date 2000-01-21 Time 16:17 Rev Time 0.00
Received By dpalmer Date 2000-01-21 Time 16:17 Sent To  
Notes
2001-01-08 00:00:00************ UNSAT ********************
  
 1) NOTE: NEED PLANS USED FOR FINAL TO
 HAVE ALL CODECORRECTIONS DONE AND ALL
 ASBUILTS SUBMITTED ON PLANS. 215-5
  
 2) NOTE: SMOKE DETECTORS INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS AS REQ`D BY
 1993/1996 NFPA-72 2-2.1.1.1
  
 3)NOTE: PLEASE INCLUDE BOTH PANEL SCHED-
 ULES TO IN BATH(S) CIRCUT(S) AS REQ`D
 BY210-52D/215-5
  
 4)NOTE: PLEAS EHAVE AIC RATING LISTED
 ON THE TOP OF PANEL SCHEDULES.230-65/
 110-9/215-5
  
 PLEASE HAVE THE ABOVE INFORMATION
 SUBMITTED FOR REVIEW AND APPROVAL BEFORE
 FINAL ELECTRICAL INSPECTION IS CALLED IN
 IF THERE ARE ANY QUESTIONS PLEASE CALL;
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status   Date   Cont ID  
Sent By jleahy Date 1999-11-19 Time 14:29 Rev Time 0.45
Received By jleahy Date 1999-11-19 Time 14:29 Sent To  
Notes
2001-01-08 00:00:001- NEED NEW PANEL SHEDULE FOR OLD PANEL
 AND ONE FOR NEW PANEL
 2- SUBMIT BEFORE FINAL ELECTRICAL INSP.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-06-15 Cont ID  
Sent By dpalmer Date 1999-06-15 Time 15:01 Rev Time 0.00
Received By dpalmer Date 1999-06-15 Time 15:01 Sent To  
Notes
2001-01-08 00:00:00*************PROVISO*******************
  
 NEED FAULT CURRENT CALCULATIONS AND
 AIC RATING TO BE DRAWN ON PANEL SCHEDULE
 AS PER ART.215-5
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.
 NOTE:2`6`12`RULE 210-52A OUTLET
 REQ`MENTS/SPACING.
  
 PLEASE HAVE FIRST TWO SUBMITTED BEFORE
 ROUGH INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-06-26 Cont ID  
Sent By jleech Date 1999-06-26 Time 14:19 Rev Time 0.50
Received By jleech Date 1999-06-26 Time 14:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-07-31 Cont ID  
Sent By tlarge Date 1999-07-31 Time 09:01 Rev Time 0.33
Received By tlarge Date 1999-07-31 Time 09:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-07-31 Cont ID  
Sent By tlarge Date 1999-06-30 Time 14:31 Rev Time 0.65
Received By tlarge Date 1999-06-30 Time 14:31 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SANITARY RISER THAT COMPLIES W/
 THE STANDARD PLBG.CODE. SEC.104.2.1,
 104.3.1.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-07-26 Cont ID  
Sent By jcaloger Date 1999-07-26 Time 08:36 Rev Time 0.00
Received By jcaloger Date 1999-08-03 Time 10:53 Sent To  
Notes
2001-01-08 00:00:00REVIEWED BY T MOORE

Review Stop Z ZONING
Rev No 1 Status P Date 1999-06-02 Cont ID  
Sent By gjoyce Date 1999-06-02 Time 11:20 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***