| Plan Review Stops For Permit 99051186 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
1999-09-03 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
1999-09-03 |
Time |
08:18 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
1999-08-23 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
1999-08-23 |
Time |
10:29 |
Rev Time |
3.50 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
1999-07-31 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
1999-07-31 |
Time |
13:07 |
Rev Time |
3.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
1999-07-09 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
1999-07-09 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
1999-06-29 |
Time |
10:02 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
14 |
Status |
F |
Date |
2000-10-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-24 |
Time |
21:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-24 |
Time |
21:53 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SEE LOAD CALCULATIONS FOR | | | PANEL "B" LOAD SHOWN FOR PANEL"G" DOES | | | NOT CORRELATE WITH WHAT IS SHOWN ON "B" | | | SCHEDULE. PLEASE NOTE THAT THE LOADS | | | TOTALLED FROM ALL PANELS EXCEED RATING | | | OF 3000 AMP MAIN. THIS WAS A CONCERN | | | WHEN DOING PLAN REVIEWS IN THE BEGINING | | | AND THOSE LOADS WERE TAKEN OFF. NOW | | | LOAD EXCEEDS MAIN SERVICE SIZE. | | | | | | PLEASE NOTE THAT ALL LOAD CALCULATIONS | | | WILL NEED TO BE SUBMITTEDAND SHOWN. | | | ALL LOAD CALCULATIONS ARE TO BE DONE | | | ACCORDING NEC AND IF SERVICE IS NOT OF | | | SUFF. SIZE THEN SERVICE WILL NEED TO BE | | | INCREASED. ALSO PLEASE NOTE THAT A MEET- | | | -ING IS GOING TO BE REQUESTED FOR ANY | | | INCREASE IN SERVICE AND FOR ANY QUESTION | | | -S AND/OR VERIFICATION OF LOAD CALCS. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMAITON | | | SIGNED AND SEALED BY ENGINEER OF RECORD | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | JAKE LEAHY | | | CHEIF ELECTRICAL INSPECTOR | | | | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 FOR DV PALMER AND | | | 8451 FOR J LEAHY. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
13 |
Status |
P |
Date |
2000-10-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-16 |
Time |
18:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-16 |
Time |
18:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
12 |
Status |
P |
Date |
2000-10-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-10 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-10 |
Time |
09:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
11 |
Status |
P |
Date |
2000-10-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-10 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-10 |
Time |
09:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
10 |
Status |
P |
Date |
2000-09-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-26 |
Time |
18:08 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-26 |
Time |
18:08 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SHEET E-2 ONLY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
9 |
Status |
P |
Date |
2000-09-13 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2000-09-13 |
Time |
13:30 |
Rev Time |
3.00 |
| Received By |
jleahy |
Date |
2000-09-13 |
Time |
13:29 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REV. #8 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
P |
Date |
2000-09-13 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2000-09-13 |
Time |
13:29 |
Rev Time |
2.00 |
| Received By |
jleahy |
Date |
2000-09-13 |
Time |
13:28 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REV. #6 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
F |
Date |
2000-08-01 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2000-08-01 |
Time |
09:30 |
Rev Time |
2.45 |
| Received By |
jleahy |
Date |
2000-09-13 |
Time |
13:28 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | THERE ARE SEVERAL SETS OF PLANS AND NONE | | | OF THEM HAVE THE SAME AMOUNT OF PAGES | | | PLEASE FIX AND RESUBMIT!!!!!!!!!!!!!!!! |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2000-07-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-26 |
Time |
20:28 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-26 |
Time |
20:28 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************* NOTE******************** | | | | | | | | | PLAN REVISIONS WERE ONLY SUBMITTED FOR | | | SHEET E-2 . OUTSTANDING ISSUES PER | | | JAKE LEAHY. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2000-06-20 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2000-06-20 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2000-09-11 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1- AIC RATING STILL 200K ON CERTAIN | | | PANELS..... |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2000-06-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2000-06-06 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
rcordove |
Date |
2000-06-19 |
Time |
09:07 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1- ALL PANELS ARE SHOWN WITH 200K RATED | | | BUSS | | | | | | 2- OUTLET SPACING IS NOT TO CODE!!!!!!! |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2000-04-21 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2000-04-21 |
Time |
10:34 |
Rev Time |
4.00 |
| Received By |
jleahy |
Date |
2000-04-20 |
Time |
08:27 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PG.E-4 100 AMP DISC IN CORNER MUST MEE | | | 110-26. | | | | | | PG.E-9 LOADS ON PANEL "ACB" SHOWS NO | | | MOTOR CONTIBUTION PER 430-24,25,26 | | | | | | PG.E-13 "K" PANEL SHOWS THE OUTLETS AN | | | VENTILATING EQUIPMENT INCLUDED IN THE | | | DEMAND FOR THE THE KITCHEN EQUIP.SEE | | | 220-22 FOR REQUIREMENTS!!!!!!!!!!!!!! | | | | | | PG.E-13 THE LOAD CALCULATION FOR "MDP" | | | SHOWS LOADS THAT DO NOT MATCH WHAT IS | | | SHOWN ON THE INDIVIDUAL PANELS LOAD CALC | | | "ACB","A","B" SHOW LARGER THAN WHAT IS | | | SHOWN ON THE CALC FOR "MDP"!!!!!!!!!!!! | | | | | | PG.E-13PANELS "A,B" SHOW A 200A DISC | | | WITH A LOAD OF 25,000VA HOW WAS THIS | | | FIGURED?200AMPS AT 208 = 72,000 VA | | | | | | PG.E-13 ALL PANELS AND DISC. ON LOAD | | | SIDE OF THE MDP SHOW NO AIC RATING!!!! | | | | | | PLEASE CHECK ALL LOAD CALCULATIONS FOR | | | COMPLIANCE WITH THE CODE!!!!!BASED ON | | | WHAT IS SHOWN THE 3000 AMP MAIN IS TOO | | | SMALL!!! |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
1999-09-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
1999-09-27 |
Time |
12:27 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
1999-09-27 |
Time |
12:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
1999-07-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
1999-07-01 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2000-06-06 |
Time |
10:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2000-10-05 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2000-10-05 |
Time |
16:28 |
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | APPROVED REVISIONS. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
1999-07-09 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
1999-07-09 |
Time |
11:25 |
Rev Time |
99.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | APPROVED ON PERMIT 9902122 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2000-09-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-27 |
Time |
12:48 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-27 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLAN REVIEW FOR FIRST FLOOR LIFE SAFETY | | | DRAWING. | | | 1) IF ALL OF THE EXIT DOORS IN THE | | | HORIZONTAL PLANE ARE AT LEAST 36" WIDE, | | | THEY PROVIDE 1 1/2 UNITS OF EXIT WIDTH | | | AND CAN PROVIDE EXITING FOR 150 PERSONS. | | | 2) PLAN DOES NOT INDICATE WHAT PURPOSE | | | THE PRE-FUNCTION LOBBY SERVES AND WHAT | | | IF ANY OCCUPANT LOADS ARE EXPECTED FROM | | | THIS AREA. | | | 3) PLAN DOES NOT INDICATE RATED FIRE | | | WALL LOCATIONS FOR CORRIDORS PRE- | | | FUNCTION 106 AND 111. SINCE THESE | | | THESE PROVIDE EXITING FOR 30 OR MORE | | | PERSONS ONE HOUR FIRE SEPARATION IS | | | REQUIRED. OPENINGS ARE TO BE PROTECTED | | | WITH RATED FIRE DOORS. | | | 4) EXIT SIGNS SHOULD BE INCLUDED WITH | | | PLANS SO EXITING LOCATIONS ARE CLEARLY | | | IDENTIFIED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-09-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-21 |
Time |
14:12 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-21 |
Time |
14:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
1999-07-09 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
1999-07-09 |
Time |
10:04 |
Rev Time |
99.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO ON PLAN 6/1/99 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
P |
Date |
2000-10-06 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-10-06 |
Time |
06:47 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2000-10-06 |
Time |
06:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2000-10-02 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-10-02 |
Time |
16:25 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-10-02 |
Time |
16:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2000-08-16 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-08-16 |
Time |
07:08 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-08-16 |
Time |
07:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2000-07-26 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-26 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
cthirben |
Date |
2000-07-26 |
Time |
14:01 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NOTE: | | | OKED WITH NCD...... |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-07-18 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-18 |
Time |
15:56 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-07-18 |
Time |
15:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
1999-11-15 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-11-15 |
Time |
15:08 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
1999-11-15 |
Time |
15:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
1999-06-02 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-06-02 |
Time |
12:47 |
Rev Time |
2.00 |
| Received By |
ndenmark |
Date |
1999-06-02 |
Time |
12:47 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************PROVISO******************** | | | 1) STORAGE CLOSETS WITH JANITOR SINKS TO | | | HAVE EXHAUST FROM SPACE SEE AC-1 STORAGE | | | ROOM 103 PER 1994 SMC 501.4 | | | 2) DUCTS PENETRATING RATED WALLS TO HAVE | | | FIRE DAMPERS AT PENETRATION PER 1994 SMC | | | 610.1 SEE ELEC ROOM ON AC-2 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
9 |
Status |
P |
Date |
2000-09-10 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-09-10 |
Time |
12:46 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
F |
Date |
2000-08-27 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-27 |
Time |
06:58 |
Rev Time |
3.50 |
| Received By |
tlarge |
Date |
2000-08-27 |
Time |
05:15 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)3"STACK TO 2ND FLOOR CANNOT CONNECT TO | | | THE CIRCUIT AND LOOP SYSTEM FOR THE 2ND. | | | FLOOR PER SPC SEC.914.1. | | | | | | 2)SHT.P-7-THE GREASY WASTE SYSTEM SHALL | | | BE DESIGNED TO COMPLY W/SPC SEC.921.(A | | | VENT IS ALSO REQD.DOWNSTREAM OF THE | | | FIRST FIXTURE DRAIN ON THE SYSTEM.) | | | | | | 3)A MANUAL SHUT-OFF VALVE IS REQD.AT THE | | | SOLENOID VALVE W/A UNION DOWNSTREAM OF | | | SOLENOID VALVE PER NFPA SEC.5.5.4. | | | | | | 4)SHOW REQD.VALVE UPSTREAM OF MP REG.FOR | | | WATER HEATERS PER NFPA SEC.3.10.1. | | | | | | 5)INDICATE TABLE UTILIZED TO SIZE 2 PSI | | | SYSTEM TO WATER HEATERS. | | | | | | 6)REGULATORS SHALL BE VENTED TO ATMOS- | | | PHERE PER NFPA 54 SEC.2.8.4. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
F |
Date |
2000-08-04 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-04 |
Time |
18:47 |
Rev Time |
1.50 |
| Received By |
tlarge |
Date |
2000-08-04 |
Time |
17:57 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)THERE IS CONFLICTING INFORMATION ON | | | SHT.P-8 REGARDING THE GAS.COMPLY W/ | | | ATTACHED GAS REQS.AND CLEAN-UPTHE PLANS. | | | DELETE INFORMATION THAT IS OLD OR NOT | | | DIRECTLY RELATED TO THIS INSTALLATION. | | | | | | IF YOU HAVE ANY QUESTIONS CALL | | | 561-659-8096,EXT.8377. | | | | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
F |
Date |
2000-04-20 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-04-20 |
Time |
18:54 |
Rev Time |
2.50 |
| Received By |
tlarge |
Date |
2000-04-20 |
Time |
18:54 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | WATER HEATERS LOCATED ABOVE THE FIRST | | | FLOOR CEILING SHALL BE EQUIPPED W/PANS | | | AND DRAINS PER COUNTYWIDE AMENDMENTS TO | | | SPC SEC.507.8.1. | | | | | | SHUT OFF VALVES ARE REQD.ON WATER SUPPLY | | | BRANCH LINES PER SPC SEC.610.4.2. | | | | | | MAXIMUM OF 4 FIXTURES SHALL BE SUPPLIED | | | BY 1/2" H.W.LINE PER COUNTYWIDE AMEND- | | | MENTS TO SPC SEC.607.7. (SEE 4TH.FLR. | | | RESTROOMS & CHECK ENTIRE RISER.) | | | | | | FLOOR DRAINS SHALL BE LOCATED TO BE IN | | | FULL VIEW PER SPC SEC.409.4.1.2. | | | | | | SHOW LENGTHS OF ALL CUT SECTIONS OF NEW | | | GAS PIPE.NOTE APPROPRIATE GAS SIZING | | | CHART ON PLAN.SYSTEM SIZING SHALL BE | | | FROM POINT OF DELIVERY(EXISTING)TO MOST | | | REMOTE OUTLET PER SGC SEC.305.4, 305.6. | | | 1003.4.SUBMIT CALCULATIONS FOR SIZING. | | | | | | SHOW EMERGENCY SHUT-OFF VALVE FOR GAS | | | SYSTEM PER NFPA 96, SEC.7-4. | | | | | | GAS EQUIPMENT SHUTOFF VALVES AND CONN- | | | ECTIONS SHALL COMPLY W/NFPA 54,SEC.5.5.4 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
1999-09-02 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-09-02 |
Time |
12:32 |
Rev Time |
2.50 |
| Received By |
tlarge |
Date |
1999-09-02 |
Time |
12:32 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | APPROVED 2 SETS-3RD SET MISSING PLBG. | | | SHEETS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
1999-09-02 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-09-01 |
Time |
11:30 |
Rev Time |
1.50 |
| Received By |
tlarge |
Date |
1999-09-01 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | HANDICAP ACCESSIBLE STALL DOOR SHALL | | | COMPLY W/FACBC SEC.4.17.5,4.13.(DOOR | | | FROM ONE STALL SWINGS INTO CLEAR WIDTH | | | OF HANDICAP STALL. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
1999-09-02 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-08-20 |
Time |
12:40 |
Rev Time |
4.75 |
| Received By |
tlarge |
Date |
1999-08-20 |
Time |
12:40 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SHT.A7.1-WOMEN'S R.R.-MIN.CLEARANCE FOR | | | WHEELCHAIR IS 32" PER F.A.C.B.C. SEC. | | | 4.2.1.(SEE AREA AT ADDED H.C. STALL DOOR | | | AND STALL PARTITION.) | | | | | | SHT.P.7-8" RWL IS DRAINING INTO 6" LINE. | | | COMPLY W/SPC 307.5, TABLES 1108.1, | | | 108.2. | | | | | | SHT.P.8-SHOWER IN MEN'S ROOM NOT SHOWN | | | ON RISER.SPC SEC.104.2.1.(SEE P.3,3RD. | | | FLR.) | | | | | | SHT.P.8-(3RD.FLR.)-OVER 2 FIXTURES ON | | | 1/2" C.W.(SEE D.F.'S.)AMENDMENTS TO | | | CODE SEC.607.7 | | | | | | SHT.P.8-OVER 2 FIXTURES CONNECTED TO | | | 1/2"C.W.(SEE UPPER CAFE AREA)AMENDMENTS | | | TO STANDARD PLBG.CODE SEC.607.7.(SEE | | | P901,P902.) | | | | | | SHT.P.1-FLOOR DRAIN IN STORAGE ROOM | | | EXCEEDS DISTANCE FROM VENT.COMPLY W/ | | | TABLE 908.1 OF SPC. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
1999-09-02 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-07-30 |
Time |
16:01 |
Rev Time |
4.75 |
| Received By |
tlarge |
Date |
1999-07-30 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SHT A2.1-AN ADD'L.HANDICAP STALL IS | | | REQ'D.IN ROOM#113 PER F.A.C.B.C.SEC. | | | 4.22.4. | | | | | | COMMON LAUNDRY AREAS SHALL COMPLY W/ | | | F.A.C.B.C. SEC.4.1.6.9 (1)(B),4.27.1. | | | | | | HANDICAP SHOWERS AND SEATS SHALL COMPLY | | | W/F.A.C.B.C. SEC.4.21.2, 4.21.3. | | | | | | SHT.A7.2-ELEV.#8-HANDICAP URINAL SHALL | | | COMPLY W/F.A.C.B.C.SEC.4.18.2 (MAX.17" | | | A.F.F.) | | | | | | SHT.A7.3-ADDITIONAL H.C. STALL REQ'D. | | | IN MEN'S AND WOMEN'S RESTROOMS PER | | | F.A.C.B.C. SEC.4.22.4.**(NOTE:CHECK ALL | | | RESTROOMS FOR THIS REQ'.) | | | | | | SHT.A7.3-ELEV.#19-H.C URINAL SHALL BE | | | AT MAX.17" A.F.F.TO RIM PER F.A.C.B.C. | | | SEC.4.18.2. | | | | | | FLOOR DRAINS SHALL NOT EXCCED DISTANCE | | | FROM VENT PER SPC.SEC.908 & TABLE 908.1 | | | | | | MAX.TEMPERATURE OF WATER DISCHARGED TO | | | SANITARY SYSTEM SHALL NOT EXCEED 140 | | | DEGREES.SPC.SEC.807.3 | | | | | | MAX.TEMPERATURE TO RESTROOMS SHALL NOT | | | EXCEED 110 DEGREES PER FLA.ENERGY CODE | | | SEC.412.ABCD.2.3.2. | | | | | | WATER SUPPLY CONTROL SHALL COMPLY W/SPC | | | SEC.610.4.1, 610.4.2. | | | | | | FLOOR DRAINS ARE NOT PROPERLY VENTED. | | | COMPLY W/SPC SEC.901.2, TABLE 908.1 | | | | | | SUBMIT STORM RISER DIAGRAM FOR THE | | | STORM DRAINAGE SYSTEM.SPC 104.2.1. | | | | | | SUBMIT MANUF.SHEETS FOR GASEQUIPMENT. | | | EQUIPMENT SHALL BE LISTED PER STD.GAS | | | CODE SEC.402.1. | | | | | | CLEARLY SHOW WATER SOURCE FOR IRRIGATION | | | SYSTEM .BACKFLOW PREVENTION DEVICE IS | | | REQ'D.IF ON CITY WATER.SPC 601.6 | | | | | | EQUIPMENT SUPPLY LINES ON GAS HEADER ARE | | | UNDERSIZED.COMPLY W.STD.GAS CODE SEC. | | | 305.2(INDICATE TYPE OF PIPING TO BE | | | INSTALLED.)AND TABLES 305.4. | | | | | | SUBMIT CALCULATIONSFOR ROOF DRAINAGE | | | OVERFLOW.COMPLY W/SBC SEC.1507.4.3, | | | 1604.6.2.,STD.PLBG.CODE SEC.1109. | | | | | | SUPPLY OCCUPANT LOAD AS DETERMINED BY | | | SPC SEC.407.1.3 TO ENSURE COMPLIANCE | | | FOR MINIMUM FIXTURE REQUIREMENTS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
1999-09-02 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
1999-06-26 |
Time |
13:08 |
Rev Time |
3.00 |
| Received By |
tlarge |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | UNSAT | | | (1) COVER SHT.GIVE DETAILS OF OCCUPANCY | | | & SQUARE FOOTAGE FOR EACH FLOOR AND | | | NUMBER OF PEOPLE. | | | (2) SHT.L-1 IRRIGATION LAYOUT AND | | | LOCATION OF BACK FLOW PREVENTER. | | | (3) SHT. P-2 SHOW 2ND FLOOR REST RM'S | | | (4) SHT. P-6 ALL INDIRECT WASTE TO | | | FLOOR SINKS NO HUB DRAINS.SPC CH 8. | | | (5) SHT.P-8 GAS SOLENOID,A MANUAL | | | SHUT OFF VALVE UP STREAM, UNION DOWN | | | STREAM OF THE SOLENOID VALVE.SGC 508.2 | | | (6) SHT P-8 CK GAS PIPE SIZE ON HEADER, | | | FOR BTU LOAD OF EACH APPLIANCE. | | | "UNDER SIZED" | | | END OF COMMENTS |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
1999-09-03 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
1999-07-09 |
Time |
10:03 |
Rev Time |
1.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|