| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| | 1-ENTRY DOORS CAN'T HAVE STORM PANELS |
| | BECAUSE THE MAIN EGRESS OF THE HOUSE |
| | WILL BE BLOCKED. REVISE STORM PANELS |
| | INSTALLATION SCHEDULE AS REQUIRED. |
| | 2-ARCHITECT SPECIFIED GIRDER TRUSS AT |
| | FRONT PORCH. SPECIFY UPLIFT CONNECTORS. |
| | *PROVIDE COMPLETE SPECIFICATIONS FOR |
| | DETAIL B-6. |
| | *REVISE CONNECTOR C-A6 AS REQUIRED IN |
| | ORDER TO RESIST THE UPLIFT LOADS |
| | CALCULATED ON ENGINEERED TRUSSES. |
| | 3-ENGINEERED TRUSS LAYOUT DON NOT SHOW |
| | GIRDER TRUSS AT FRONT PORCH SPECIFIED |
| | BY ARCHITECT. REVISE AS REQUIRED. |
| | *TRUSS DRAWINGS NEED TO BE UPDATED TO |
| | ASCE 7-95. |
| | CUTTING AND PASTING ENGINEERED TRUSSES |
| | WILL NOT BE ACCEPTED. |
| | 4-REVISED ORIGINAL DRAWINGS SHOWING THE |
| | CORRECTIONS/CLARIFICATIONS. |
| | 5-SLIDING GLASS DOORS: |
| | *USE ONLY THE REINFORCED DOORS IN ORDER |
| | TO MEET THE DESIGN PRESSURES SPECIFIED |
| | BY THE ARCHITECT. |
| | *PROVIDE PRODUCT APPROVAL FOR SLIDING |
| | GLASS DOORS ASSEMBLY W/ TRANSOM ABOVE. |
| | 6-MINIMUM CLEAR OPENING AT BEDROOM |
| | WINDOWS TO BE 5.0 S.F AS PER SECTION |
| | 1005.4.4 SBC 1997. PROVIDE THE EXACT |
| | DIMENSIONS FOR WINDOWS AT BEDROOM #2 TO |
| | VERIFY CLEAR OPENING PRIOR TO |
| | INSTALLATION. |
| | 7-PROVIDE PRODUCT APPROVAL FOR ENTRY |
| | DOORS PRIOR TO INSTALLATION. |
| | 8-GARAGE DOOR PRODUCT APPROVAL DOESN'T |
| | MEET THE DESIGN PRESSURES CALCULATED BY |
| | ARCHITECT. UPGRADE GARAGE DOORS. |