Plan Review Details - Permit 99051159
Plan Review Stops For Permit 99051159
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-06-15 Cont ID  
Sent By dpalmer Date 1999-06-15 Time 17:06 Rev Time 0.00
Received By dpalmer Date 1999-06-15 Time 17:06 Sent To  
Notes
2001-01-08 00:00:00************PROVISO********************
  
 NEED TO SUBMIT PLANS WITH FAULT CURRENT
 CACULATIONS/FOR AIC RATING.215-5
 NOTE:EQUIPMENT GROUNDING CONDUCTOR
 REQ`D FROM FIRST MEANS OF DISC. TO
 PANEL.250-92/250-95
 NOTE:GROUNDING ELECTRODE CONDUCTOR
 SYSTEM TO BLDG.STEEL ALSO.
  
 NEED THE ABOVE INFORMATION SUBMITTED
 BEFORE ROUGH INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-06-26 Cont ID  
Sent By jleech Date 1999-06-26 Time 11:10 Rev Time 0.50
Received By jleech Date 1999-06-26 Time 11:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-06-30 Cont ID  
Sent By tlarge Date 1999-06-30 Time 07:27 Rev Time 0.00
Received By tlarge Date 1999-06-30 Time 07:27 Sent To  
Notes
2001-01-08 00:00:00COMPLETE GAS DRAWING AND PERMIT REQ'D.
 FOR GAS INSTALLATION.6/30/99.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-06-30 Cont ID  
Sent By tlarge Date 1999-06-30 Time 07:26 Rev Time 0.50
Received By tlarge Date 1999-06-30 Time 07:26 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 1999-09-20 Cont ID  
Sent By jgomez Date 1999-09-20 Time 14:56 Rev Time 0.00
Received By jgomez Date 1999-09-20 Time 14:56 Sent To O
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-ENTRY DOORS CAN'T HAVE STORM PANELS
 BECAUSE THE MAIN EGRESS OF THE HOUSE
 WILL BE BLOCKED. REVISE STORM PANELS
 INSTALLATION SCHEDULE AS REQUIRED.
 2-ARCHITECT SPECIFIED GIRDER TRUSS AT
 FRONT PORCH. SPECIFY UPLIFT CONNECTORS.
 *PROVIDE COMPLETE SPECIFICATIONS FOR
 DETAIL B-6.
 *REVISE CONNECTOR C-A6 AS REQUIRED IN
 ORDER TO RESIST THE UPLIFT LOADS
 CALCULATED ON ENGINEERED TRUSSES.
 3-ENGINEERED TRUSS LAYOUT DON NOT SHOW
 GIRDER TRUSS AT FRONT PORCH SPECIFIED
 BY ARCHITECT. REVISE AS REQUIRED.
 *TRUSS DRAWINGS NEED TO BE UPDATED TO
 ASCE 7-95.
 CUTTING AND PASTING ENGINEERED TRUSSES
 WILL NOT BE ACCEPTED.
 4-REVISED ORIGINAL DRAWINGS SHOWING THE
 CORRECTIONS/CLARIFICATIONS.
 5-SLIDING GLASS DOORS:
 *USE ONLY THE REINFORCED DOORS IN ORDER
 TO MEET THE DESIGN PRESSURES SPECIFIED
 BY THE ARCHITECT.
 *PROVIDE PRODUCT APPROVAL FOR SLIDING
 GLASS DOORS ASSEMBLY W/ TRANSOM ABOVE.
 6-MINIMUM CLEAR OPENING AT BEDROOM
 WINDOWS TO BE 5.0 S.F AS PER SECTION
 1005.4.4 SBC 1997. PROVIDE THE EXACT
 DIMENSIONS FOR WINDOWS AT BEDROOM #2 TO
 VERIFY CLEAR OPENING PRIOR TO
 INSTALLATION.
 7-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS PRIOR TO INSTALLATION.
 8-GARAGE DOOR PRODUCT APPROVAL DOESN'T
 MEET THE DESIGN PRESSURES CALCULATED BY
 ARCHITECT. UPGRADE GARAGE DOORS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 1999-07-20 Cont ID  
Sent By jgomez Date 1999-07-20 Time 17:10 Rev Time 1.00
Received By jgomez Date   Time   Sent To D
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-05-28 Cont ID  
Sent By gjoyce Date 1999-05-28 Time 14:12 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***