Plan Review Details - Permit 99051033
Plan Review Stops For Permit 99051033
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-06-15 Cont ID  
Sent By dpalmer Date 1999-06-15 Time 19:18 Rev Time 0.00
Received By dpalmer Date 1999-06-15 Time 19:18 Sent To  
Notes
2001-01-08 00:00:00************PROVISO*********************
  
 NEED TO SUBMIT PLANS WITH FAULT CURRENT
 CALCULATIONS/AND AIC RATING DRAWN ON
 PANEL SCHED.ART.215-5
 NOTE:MISSING LIGHT OUTSIDE GARAGE BACK
 DOOR.ART.210-70 MEANS OF EGRESS.
 NOTE:RECEPTS.SERVING KITCHEN COUNTER
 SPACE ARE TO BE GFI.ART210-8-A-6
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS AND ROOMS OPT./TO BE
 BEDROOMS.
 NOTE:MISSING RECEPT.REQ`D FOR A/C
 COND.UNIT ART.210-63
 NOTE:RECEPTS.REQ`D IN HALLS AS PER
 ART.210-52H
 NOTE:MANY MISSING RECEPTS.REQ`D AS PER
 ART.210-52A 2`6`12`RULE.
 NOTE:EQUIPMENT GROUNDING COND.REQ`D
 FROM MAIN DISCONNECT TO PANELS AS PER
 ART.250-92/250-95
 NOTE:GROUNDING ELECTRODE SYSTEM TO
 GRND.ROD,BLDG.STEEL.
  
 NEED TO HAVE ALL THE ABOVE INFORMATION
 BEFORE ROUGH INSPECTION.!!!

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-06-26 Cont ID  
Sent By jleech Date 1999-06-26 Time 11:47 Rev Time 0.50
Received By jleech Date 1999-06-26 Time 11:47 Sent To  
Notes
2001-01-08 00:00:00SEE NOTES UNDER A/C PERMIT#99051036.

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-08-04 Cont ID  
Sent By tlarge Date 1999-08-04 Time 10:19 Rev Time 0.33
Received By tlarge Date 1999-08-04 Time 10:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-08-04 Cont ID  
Sent By tlarge Date 1999-06-30 Time 13:14 Rev Time 0.50
Received By tlarge Date 1999-06-30 Time 13:14 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SANITARY RISER THAT COMPLIES W/
 THE STANDARD PLBG. CODE.SPC 104.2.1,
 104.3.1.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 1999-12-30 Cont ID  
Sent By jgomez Date 1999-12-30 Time 11:09 Rev Time 0.50
Received By jgomez Date 1999-12-30 Time 11:09 Sent To  
Notes
2001-01-08 00:00:00SLIDING GLASS DOORS PRODUCT APPROVAL:
  
 CHECKLIST:
  
 1-SIZE OF SLIDING GLASS DOORS SPECIFIED
 IN ARCHITECT'S DRAWINGS IS BIGGER THAN
 SIZE OF SLIDING GLASS DOORS SHOWN ON
 THE PRODUCT APPROVAL. THEREFORE,
 THIS PRODUCT APPROVAL IS NOT ACCEPTED.
 PROVIDE A COMPLETE SITE SPECIFIC
 ENGINEERING ANALYSIS, DRAWINGS, SPECS
 AND COPIES OF TESTS PERFORMED.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 1999-12-10 Cont ID  
Sent By jgomez Date 1999-12-10 Time 16:29 Rev Time 0.50
Received By jgomez Date 1999-12-10 Time 16:28 Sent To  
Notes
2001-01-08 00:00:00TRUSS DRAWINGS CHECKLIST:
 1-REVISE MEAN ROOF HEIGHT. THERE IS ONLY
 ONE MEAN ROOF HEIGHT FOR THE ENTIRE
 BUILDING. FOOTNOTES AT TABLE 1606.2A
 SBC 1994.
 MEAN ROOF HEIGHT IS 24'-0" PLUS OR
 MINUS. SEE ARCHITECT'S DRAWINGS.
 2-THERE ARE SLIGHT VARIATIONS ON TRUSS
 LAYOUT AND ARCHITECT'S FRAMING PLANS.
 PROVIDE THE SPECIFIC CONNECTORS AS
 REQUIRED. SEE COMMENTS ON TRUSS LAYOUT
 3-ARCHITECT TO REVISE AND SPECIFY ALL
 HURRICANE CONNECTORS THAT WILL RESIST
 THE UPLIFT LOADS CALCULATED ON
 ENGINEERED TRUSSES. NOTE THAT THERE
 ARE SOME CONNECTORS THAT NEED TO BE
 UPGRADED IN ORDER TO RESIST THOSE
 LOADS. EG: SEE TRUSS B9 ENGINEERED
 CALCULATIONS AND CONNECTORS SPECIFIED.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 1999-08-02 Cont ID  
Sent By jgomez Date 1999-08-02 Time 14:39 Rev Time 3.00
Received By jgomez Date   Time   Sent To O
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO
 1)PROVIDE PRODUCT APPROVAL FOR:ROUND
 WINDOWS, MULLIONS, BUTT GLAZING SYSTEM
 2)RESUBMIT PRODUCT APPROVAL FOR:SLIDING
 GLASS DOORS, GARAGE DOORS.
 3)PROVIDE COMPLETE INFORMATION FOR STORM
 PANELS UNDER A SEPARATE PERMIT.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 1999-07-19 Cont ID  
Sent By jgomez Date 1999-07-19 Time 13:40 Rev Time 3.00
Received By jgomez Date   Time   Sent To D
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-05-27 Cont ID  
Sent By gjoyce Date 1999-05-27 Time 08:05 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***