Plan Review Details - Permit 99050910
Plan Review Stops For Permit 99050910
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 1999-06-16 Cont ID  
Sent By hpiskura Date 1999-06-16 Time 13:18 Rev Time  
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 1999-06-21 Cont ID  
Sent By lmartine Date 1999-06-21 Time 13:57 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 1999-06-07 Cont ID  
Sent By ndenmark Date 1999-06-07 Time 09:49 Rev Time 1.00
Received By ndenmark Date 1999-06-07 Time 09:49 Sent To  
Notes
2001-01-08 00:00:00**************DENIED********************
 1) PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2) AIR BALANCE SCHEDULE REQUIRED TO
 COMPLY WITH SMC 1994 501.2
 3) FIRE DAMPERS REQUIRED AT ALL RATED
 WALL PENETRATIONS
 4) RETURN AIR REQUIRED FROM ALL AREAS W/
 300 CFM OR GREATER SUPPLY AIR

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-06-23 Cont ID  
Sent By pschmitz Date 1999-06-12 Time 07:03 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00UNSAT
 (1) SHT C15 SHOW LOCATION OF BACK FLOW
 PREVENTERS ON WATER SERVICE TO EA
 BUILDING.
 (2) SHT PW2 FIRE HOSE STAND PIPE
 SYSTEM TO BE A SEPERATE SYSTEM AND
 PROTECTED WITH A BACK FLOW PREVENTER.
 6-23-99 WTR HTR LOCATION ON FLOOR
 AS PERHARRY MCDONALD.515-6586
 SEC. 501.7 SPC 94.
 (4) SHT PW2 SHOW 2ND FLOOR REST RM
 DRAIN WASTE,VENT & WATER ISOMTRRIC.
 END OF COMMENTS