Plan Review Stops For Permit 99050881
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-06-14 Cont ID  
Sent By dpalmer Date 1999-06-14 Time 12:21 Rev Time 0.00
Received By dpalmer Date 1999-06-14 Time 12:21 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO****************
  
 NEED TO SUBMIT PLANS WITH AIC RATING
 AND/OR FAULT CURRENT CALCULATIONS.
 ART.215-5
 NOTE:GROUNDING ELECTRODE CONDUCTOR
 TO GROUND ROD ALSO.
  
 PLEASE HAVE BEFORE ROUGH INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-11-18 Cont ID  
Sent By jleech Date 1999-11-18 Time 13:35 Rev Time 0.50
Received By jleech Date 1999-11-18 Time 13:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-06-19 Cont ID  
Sent By jleech Date 1999-06-19 Time 10:49 Rev Time 0.50
Received By jleech Date 1999-06-19 Time 10:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-07-27 Cont ID  
Sent By tlarge Date 1999-07-27 Time 14:40 Rev Time 0.33
Received By tlarge Date 1999-07-27 Time 13:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-07-27 Cont ID  
Sent By tlarge Date 1999-06-19 Time 09:09 Rev Time 0.50
Received By tlarge Date 1999-06-19 Time 09:09 Sent To  
Notes
2001-01-08 00:00:00CLEARLY SHOW FIXTURE CLEARANCES OF WATER
 CLOSET AND BIDET FROM WALLS AND CENTER-
 TO-CENTER MEASUREMENTS.S.P.C.SEC. 403.4
  
 BIDET DOWNSTREAM OF W.C.SHALL BE VENTED
 PER S.P.C.SEC. 913.2.
  
 SHWR.IN CABANA BATH IS NOT VENTED
 CORRECTLY.S.P.C. SEC.901.2
  
 W.C.IN CABANA BATH EXCEEDS ALLOWABLE
 DISTANCE FROM VENT PER COUNTYWIDE
 AMENDMENTS TO STANDARD PLBG.CODE SEC.
 908.1,FOOTNOTE #2.
  
 ISOMETRIC SHOWS W.C.'S DRAINING INTO 2"
 LINE.COMPLY W/S.P.C.SEC.AND TABLE 714.2
 FOOTNOTE #5.
  
 CLEANOUTS SHALL BE INSTALLLED PER S.P.C.
 SEC.710.2.1.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 1999-09-23 Cont ID  
Sent By jgomez Date 1999-09-23 Time 10:27 Rev Time 0.25
Received By jgomez Date 1999-09-23 Time 10:27 Sent To  
Notes
2001-01-08 00:00:00REMAINDER:
 1-SUBMIT TWO COPIES OF TRUSS DRAWINGS
 SIGNED AND SEALED BY TRUSS ENGINEER,
 INCLUDING TRUSS LAYOUT, AND REVIEWED
 BY THE ENGINEER OF RECORD.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-07-28 Cont ID  
Sent By jcaloger Date 1999-07-20 Time 12:01 Rev Time 0.00
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-05-25 Cont ID  
Sent By gjoyce Date 1999-05-25 Time 11:29 Rev Time 0.00
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***