Plan Review Details - Permit 99050880
Plan Review Stops For Permit 99050880
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-06-11 Cont ID  
Sent By dpalmer Date 1999-06-11 Time 22:51 Rev Time 0.00
Received By dpalmer Date 1999-06-11 Time 22:51 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
  
 NEED FAULT CURRENT CALCULATIONS DONE
 FOR AIC RATING WHICH NEED TO BE ON PLANS
 ART.215-5
 NOTE:GROUNDING ELECTRODE COND.TO
 BLDG.STEEL ALSO.
  
 NEED INFORMATION BEFORE ROUGH .

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-07-21 Cont ID  
Sent By ndenmark Date 1999-07-21 Time 08:55 Rev Time 0.25
Received By ndenmark Date 1999-07-21 Time 08:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-07-21 Cont ID  
Sent By jleech Date 1999-06-19 Time 11:39 Rev Time 0.50
Received By ndenmark Date 1999-06-19 Time 11:39 Sent To  
Notes
2001-01-08 00:00:00SUBMIT MANUFACTORS SPECIFICATIONS FOR
 AIR HANDLER CFM CAPACITY.

Review Stop P PLUMBING
Rev No 2 Status N Date 1999-06-19 Cont ID  
Sent By tlarge Date 1999-06-19 Time 11:10 Rev Time 0.00
Received By tlarge Date 1999-06-19 Time 11:10 Sent To  
Notes
2001-01-08 00:00:00A GAS PERMIT IS REQ'D.AND A DRAWING
 SHALL BE SUBMITTED FOR REVIEW AND
 APPROVAL THAT CLEARLY REFLECTS THE
 ENTIRE SCOPE OF WORK TO BE PERFORMED.
 STANDARD GAS CODE SEC.104.1.1, 104.2.1,
 104.3.1.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-07-20 Cont ID  
Sent By tlarge Date 1999-06-19 Time 10:39 Rev Time 0.50
Received By tlarge Date 1999-06-19 Time 10:39 Sent To  
Notes
2001-01-08 00:00:00MAX.OF 2 W.C.'S PERMITTED ON 3" BUILDING
 DRAIN.S.P.C.SEC.& TABLE 714.1 FOOTNOTE
 #3.
  
 REMOVE TRAPS FROM WATER CLOSETS.S.P.C.
 SEC.1001.8.1.
  
 WASHING MACHINE TRAP SHALL BE PROTECTED
 PER S.P.C.SEC.901.2.
  
 SUBMIT ONE SAN.RISER THAT6 COMPLIES W/
 THE STANDARD PLBG.CODE. SPC.104.2.1.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 1999-09-23 Cont ID  
Sent By jgomez Date 1999-09-23 Time 12:20 Rev Time 0.30
Received By jgomez Date 1999-09-23 Time 12:19 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-REVISE ORIGINAL DRAWINGS SHOWING
 CORRECTIONS TO BEDROOM WINDOWS TO
 COMPLY WITH SEC. 1203.1 SBC 1997.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-07-21 Cont ID  
Sent By jcaloger Date 1999-07-21 Time 09:47 Rev Time 0.00
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-05-25 Cont ID  
Sent By gjoyce Date 1999-05-25 Time 11:40 Rev Time 0.00
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***