Plan Review Details - Permit 99050880
| Plan Review Stops For Permit 99050880 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
1999-06-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
1999-06-11 |
Time |
22:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
1999-06-11 |
Time |
22:51 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ****************PROVISO***************** | | | | | | NEED FAULT CURRENT CALCULATIONS DONE | | | FOR AIC RATING WHICH NEED TO BE ON PLANS | | | ART.215-5 | | | NOTE:GROUNDING ELECTRODE COND.TO | | | BLDG.STEEL ALSO. | | | | | | NEED INFORMATION BEFORE ROUGH . |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
1999-07-21 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-07-21 |
Time |
08:55 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
1999-07-21 |
Time |
08:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
1999-07-21 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
1999-06-19 |
Time |
11:39 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
1999-06-19 |
Time |
11:39 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SUBMIT MANUFACTORS SPECIFICATIONS FOR | | | AIR HANDLER CFM CAPACITY. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
1999-06-19 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-06-19 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
tlarge |
Date |
1999-06-19 |
Time |
11:10 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | A GAS PERMIT IS REQ'D.AND A DRAWING | | | SHALL BE SUBMITTED FOR REVIEW AND | | | APPROVAL THAT CLEARLY REFLECTS THE | | | ENTIRE SCOPE OF WORK TO BE PERFORMED. | | | STANDARD GAS CODE SEC.104.1.1, 104.2.1, | | | 104.3.1. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
1999-07-20 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-06-19 |
Time |
10:39 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
1999-06-19 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | MAX.OF 2 W.C.'S PERMITTED ON 3" BUILDING | | | DRAIN.S.P.C.SEC.& TABLE 714.1 FOOTNOTE | | | #3. | | | | | | REMOVE TRAPS FROM WATER CLOSETS.S.P.C. | | | SEC.1001.8.1. | | | | | | WASHING MACHINE TRAP SHALL BE PROTECTED | | | PER S.P.C.SEC.901.2. | | | | | | SUBMIT ONE SAN.RISER THAT6 COMPLIES W/ | | | THE STANDARD PLBG.CODE. SPC.104.2.1. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
1999-09-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
1999-09-23 |
Time |
12:20 |
Rev Time |
0.30 |
| Received By |
jgomez |
Date |
1999-09-23 |
Time |
12:19 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | CHECKLIST: | | | 1-REVISE ORIGINAL DRAWINGS SHOWING | | | CORRECTIONS TO BEDROOM WINDOWS TO | | | COMPLY WITH SEC. 1203.1 SBC 1997. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
1999-07-21 |
|
|
Cont ID |
|
| Sent By |
jcaloger |
Date |
1999-07-21 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
jcaloger |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
1999-05-25 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
1999-05-25 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|