Plan Review Details - Permit 99050879
Plan Review Stops For Permit 99050879
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-06-14 Cont ID  
Sent By dpalmer Date 1999-06-14 Time 11:02 Rev Time 0.00
Received By dpalmer Date 1999-06-14 Time 11:02 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO*******************
  
 NEED TO SUBMIT PLANS WITH AIC RATING
 LISTED ON PANEL SCHEDULE AND/OR FAULT
 CURRENT CALCULATIONS.ART.215-5
 NOTE:GROUNDING ELECTRODE CONDUCTOR
 TO GRND. ROD ALSO.
  
 PLEASE HAVE BEFORE ROUGH INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-06-19 Cont ID  
Sent By jleech Date 1999-06-19 Time 11:04 Rev Time 0.50
Received By jleech Date 1999-06-19 Time 11:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-12-21 Cont ID  
Sent By tlarge Date 1999-12-21 Time 09:30 Rev Time 0.30
Received By tlarge Date 1999-12-21 Time 09:30 Sent To  
Notes
2001-01-08 00:00:00REVISED GAS DRAWING.

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-07-27 Cont ID  
Sent By tlarge Date 1999-07-27 Time 14:25 Rev Time 0.33
Received By tlarge Date 1999-07-27 Time 13:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-07-27 Cont ID  
Sent By tlarge Date 1999-06-19 Time 09:58 Rev Time 0.75
Received By tlarge Date 1999-06-19 Time 09:58 Sent To  
Notes
2001-01-08 00:00:00SHOW FIXTURE CLEARANCES OF WATER CLOSET
 AND BIDET FROM WALLS AND CENTER-TO-
 CENTER MEASUREMENTS.403.4.
  
 BIDET DOWNSTREAM OF W.C.SHALL BE VENTED
 PER S.P.C.SEC.-913.2.
  
 SHWR.IN CABANA BATH IS NOT VENTED
 CORRECTLY.S.P.C.SEC.901.2.
  
 W.C.IN POWDER BATH EXCEEDS DISTANCE
 FROM VENT PER COUNTYWIDE AMENDMENTS
 SEC.908.1,FOOTNOTE #2.
  
 ISOMETRIC SHOWS W.C.'S DRAINING INTO 2"
 LINE.COMPLY W/S.P.C. SEC.AND TABLE 714.2
 FOOTNOTE #5.
  
 CLEANOUTS SHALL BE INSTALLED PER S.P.C.
 710.2.1.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 1999-09-23 Cont ID  
Sent By jgomez Date 1999-09-23 Time 10:08 Rev Time 0.25
Received By jgomez Date 1999-09-23 Time 10:08 Sent To  
Notes
2001-01-08 00:00:00REMAINDER:
 1-SUBMIT TWO COPIES OF TRUSS DRAWINGS
 SIGNED AND SEALED BY TRUSS ENGINEER,
 INCLUDING THE TRUSS LAYOUT, AND
 REVIEWED BY THE ENGINEER OF RECORD.
  
 2-IN THE FUTURE, PLEASE ADDRESS ANY
 CORRESPONDENCE TO THE PLAN EXAMINER
 WHO REVIEW THE PLANS. THANK YOU.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-07-20 Cont ID  
Sent By jcaloger Date 1999-07-20 Time 16:32 Rev Time 1.50
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-05-25 Cont ID  
Sent By gjoyce Date 1999-05-25 Time 11:49 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***