Plan Review Details - Permit 99050869
Plan Review Stops For Permit 99050869
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-06-11 Cont ID  
Sent By dpalmer Date 1999-06-11 Time 20:55 Rev Time 0.00
Received By dpalmer Date 1999-06-11 Time 20:55 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO*****************
  
 NEED CALCULATIONS DONE FOR AIC RATING
 WHICH NEEDS TO BE DRAWN ON PANEL SCHD.
 ART.215-5
 NEED RISER DIAGRAM TO SHOW GROUNDING
 ELECTRODE CONDUCTOR DRAWN TO GROUND ROD,
 C.W.P.,AND BLDG.STEEL.215-5
 NOTE:NEED EQUIPMENT GROUNDING COND.
 DRAWN ON PLANS FROM MAIN DISC.TO
 PANEL AND FROM PANEL TO OTHER DISC.S
 250-92/250-95
 NOTE:SMOKE DETECTORS REQ`D INSIDE
 AND OUTSIDE BEDROOMS.
 NOTE:RECEPTS.SERVING KITCHEN COUNTER
 TOPS ARE TO BE DRAWN GFI/GFI PROTECTED.
 ART.210-8-A-6
 NOTE:MASTER BEDROOM HALL 210-52H
 NOTE:2`6`12`RULE 210-52A
  
 NEED TO SUBMIT BEFORE ROUGH INSPECTION!!

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-07-19 Cont ID  
Sent By fknapp Date 1999-07-19 Time 14:03 Rev Time 0.25
Received By ndenmark Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 1999-06-21 Cont ID  
Sent By tlarge Date 1999-06-21 Time 16:49 Rev Time 0.00
Received By tlarge Date 1999-06-21 Time 16:49 Sent To  
Notes
2001-01-08 00:00:00COMPLETE GAS DRAWING REQ'D.FOR
 INSTALLATION OF ALL GAS EQUIPMENT.
 STANDARD GAS CODE SEC.104.2.1
  
 GAS WTR.HEATER SHALL BE PROTECTED FROM
 PHYSICAL DAMAGE PER STD.GAS CODE SEC.
 402.7.2.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-07-19 Cont ID  
Sent By tlarge Date 1999-06-21 Time 16:00 Rev Time 0.75
Received By tlarge Date 1999-06-21 Time 16:00 Sent To  
Notes
2001-01-08 00:00:00REMOVE TRAPS FROM WATER CLOSETS ON SAN.
 ISOMETRIC.SPC SEC.1001.6,1001.8.
  
 SIZE ALL SECTIONS OF THE DWV SYSTEM.
 SPC 104.2.1.
  
 MAX.2 WATER CLOSETS PERMITTED ON 3"
 BUILDING DRAIN.SPC TABLES 714.1,FOOTNOTE
 #3,TABLE 714.2,FOOTNOTE #2.
  
 MIN.SIZE OF BLDG.SEWER SHALL BE 4" PER
 SPC TABLE 714.1,FOOTNOTE#2.
  
 MIN.SIZE OF U/G SAN.DRAINAGE SHALL BE
 2".SPC 714.4.
  
 "S-TRAP" ON KIT.SINK NOT PERMITTED PER
 SPC SEC.101.5.2.,901.2.
  
 TUBS NOT PROPERLY VENTED.SPC 901.2.
  
 WET VENTS SHALL RECEIVE DISCHARGE FROM
 FIXTURE DRAINS ONLY.COUNTYWIDE AMEND.TO
 STANDARD PLBG.CODE SEC.911.1.1.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-07-19 Cont ID  
Sent By fknapp Date 1999-07-19 Time 11:19 Rev Time 3.00
Received By fknapp Date 1999-07-19 Time 08:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-05-25 Cont ID  
Sent By gjoyce Date 1999-05-25 Time 11:13 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***