Plan Review Details - Permit 99050442
Plan Review Stops For Permit 99050442
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 1999-08-06 Cont ID  
Sent By lsmith Date 1999-08-06 Time 14:07 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-06-28 Cont ID  
Sent By lmartine Date 1999-06-08 Time 12:43 Rev Time  
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-06-08 Cont ID  
Sent By lmartine Date 1999-05-21 Time 12:44 Rev Time  
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-06-08 Cont ID  
Sent By lmartine Date 1999-05-28 Time 12:43 Rev Time  
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-09-01 Cont ID  
Sent By ndenmark Date 1999-09-01 Time 11:57 Rev Time 0.25
Received By ndenmark Date 1999-09-01 Time 11:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-05-24 Cont ID  
Sent By ndenmark Date 1999-05-24 Time 11:29 Rev Time 0.33
Received By ndenmark Date 1999-05-24 Time 11:18 Sent To  
Notes
2001-01-08 00:00:00PROVISO: MEDICAL (DENTAL) GAS REQUIRES
 SEPARATE MECHANICAL PERMIT

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-08-21 Cont ID  
Sent By tlarge Date 1999-08-21 Time 08:36 Rev Time 0.75
Received By tlarge Date 1999-08-21 Time 08:35 Sent To  
Notes
2001-01-08 00:00:00CHANGE TO AIR-ADMITTANCE VALVES & ADD
 FUTURE LINE.8/21/99.

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-07-17 Cont ID  
Sent By pschmitz Date 1999-07-17 Time 07:08 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE ATTACHED RE:FACBC 4.1.1 (3).

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-06-25 Cont ID  
Sent By pschmitz Date 1999-06-10 Time 14:19 Rev Time 3.00
Received By tlarge Date 1999-06-10 Time 12:44 Sent To  
Notes
2001-01-08 00:00:00SUBMIT MANUF.VERIFICATION OF PH OF
 EFFLUENT FROM FILM PROCESSOR. SPC SEC.
 801.4
 SUBMIT MANUF.DATA SHEETS ON ALL MAKES/
 MODELS OF BACKFLOW PREVENTION DEVICES TO
 BE INSTALLED.SPC SEC.601.2,601.6,606.1
 606.2
 SINK IN STAFF LOUNGE SHALL COMPLY W/
 FLA.ACC.CODE FOR BLDG.CONST.SECS.4.24.1
 THRU 4.24.7
 SUBMIT FIRE SAFING DETAIL AND ASSEMBLY
 NO.FROM RECOGNIZED LISTING AGENCY.
 SPC 104.2.4
 WATER FILTER SYSTEM SHALL BE NSF
 APPROVED.SPC SEC.615.1
 SUBMIT MANUF.INSTALLATION INSTRUCTIONS
 AND DATA SHEETS ON X-RAY PROCESSOR,
 F.S.C.UNITS,DENTAL CHAIRS,MODEL TRIMMER,
 PLASTER TRAP,VACUUM PUMP,AIR COMPRESSOR,
 AND ALL OTHER RELATED EQUIPMENT PER SPC
 SECS.104.2.1 & NFPA 99-C(1993 ED.)
 SHT.P-1.-DETAILS FOR MODEL TRIMMER,FSC
 UNITS & PLASTER TRAP SHALL BE LEGIBLE.
 SPC SEC.104.2.1
 SHT.P-1.-NOTE #B-9.-"M" COPPER IS NOT
 PERMITTED U/G PER COUNTYWIDE AMEND.ORD.#
 3004-96.SEC.611.3.
 SHOW HOW WATER PIPING SYSTEM WILL BE
 PROTECTED FROM HAZARD & NOISE PER SPC
 SEC 607.8.1-607.8.3
 SHT.P-1.-NOTE #D-15.-DRAINAGE MATERIALS
 SHALL COMPLY W/SPC SEC.703.1 & TABLE 703
 HORIZ.PIPING SHALL BE SUPPORTED PER SPC
 310.3.
 CLEARLY SIZE THE WATER RISER IN IT'S
 ENTIRETY.SPC 104.2.1.,607.1,607.2.
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 610.1,610.4.1.
 FSC UNIT DRAINS SHALL BE TRAPPED PER SPC
 SEC.401.4
 SLOPE OF DRAINAGE PIPING TO COMPLY W/SPC
 705.2-705.4.
 CLEARLY NOTE OCCUPANT LOAD ON PLANS FOR
 DETERMINATION OF MIN.REQ'D.SANITARY
 FACILITIES.SPC SEC.407.1 THRU 407.2.2.
  
 *****************PROVISO****************
 A LETTER IS REQ'D.FROM THE MANUF. OF
 HE X-RAY PROCESSOR VERIFYING THE PH
 OF THE EFFLUENT WILL BE WITHIN THE
 ACCEPTABLE RANGE OF 5 AND 10 PRIOR TO
 THE INSTALLATION OF EQUIPMENT.6/25/99.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-05-14 Cont ID  
Sent By gjoyce Date 1999-05-14 Time 10:07 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***