Plan Review Details - Permit 99050128
Plan Review Stops For Permit 99050128
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-07-17 Cont ID  
Sent By dpalmer Date 2000-07-17 Time 17:24 Rev Time 0.00
Received By dpalmer Date 2000-07-17 Time 17:24 Sent To  
Notes
2001-01-08 00:00:00**************** PROVISO **************
  
 1)NOTE: PLEASE PROVDED A REVISED PANEL
 SHEDULE BEFORE FINAL ELECTRICAL INSPEC.
 IS CALLD IN, IF THERE ARE ANY QUESTIONS]
 PLEASE CALL 659-8096 EXT 8272
  
 ALSO,ADDITION ELECTRODE TO BOND COLD
 WATER PIPE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 1999-11-18 Cont ID  
Sent By jleahy Date 1999-11-18 Time 13:30 Rev Time 1.00
Received By jleahy Date 1999-11-18 Time 13:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 1999-10-18 Cont ID  
Sent By dpalmer Date 1999-10-18 Time 19:47 Rev Time 0.00
Received By jleahy Date 1999-11-18 Time 13:22 Sent To  
Notes
2001-01-08 00:00:00*************DENIED********************
  
  
 1)NOTE:AS PER ART:215-5 PANEL SCHEDULE
 TO SHOW BOTH A/C UNITS AND TO SHOW BATH
 GFI CIRCUT WHICH IS REQ`D BY ART:210-52D
 2)NOTE:AS PER ARTS:110-9/215-5 NEED TO
 SHOW AIC RATING OF MAINS AND BRANCH
 BREAKERS. AIC RATING IS FIGURED FROM
 FAULT CURRENT CALCULATIONS.
 3)NOTE:AS PER ART:250-81 NED TO SHOW
 GROUNDING ELECTRODE CONDUCTOR GOING TO
 BLDG. STEEL OF NEW ADDITION AND TO GRND.
 ROD.
 4)NOTE:AS PER ART;215-5 PLEASE GIVE
 BETTER DISCRIPTION OF RISER DIAGRAM
 PERTAINING TO 2ND.METER AND 100 AMP
 PANEL.????
 5)NOTE:AS PER 1996 NFPA-72 SMOKE
 DETECTORS NEED TO BE IN AREA OUTSIDE
 BEDROOM.SEE PLANS RELOCATING 1 SMOKE DEC
 INTO HALL FROM LIVING ROOM. ALSO OTHER
 TWO SMOKE DETECTOR THAT ARE CIRCLED ARE
 NOT REQ`D BUT ARE ALLOWED TO BE
 INSTALLED.
 6)NOTE:AS PER ART:210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTER SPACE ARE TO BE
 GFI/GFI PROTECTED.
 7)NOTE;AS PER ART:210-52-C-3 REQ`MENTS
 FOR OUTLET SPACING ON PENINSULAR.
 8)NOTE:AS PER ART:210-52 OUTLET SPACING
 INSIDE BEDROOM AS REQ`D FOR THE 2`6`12`
 RULE.
  
 PLEASE HAVE ALL THE ABOVE SUBMITTED FOR
 REVIEW AND APPROVAL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 1999-06-07 Cont ID  
Sent By fknapp Date 1999-06-07 Time 07:40 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00***********DENIED**********************
  
 NEED COMPLETE SQUARE FOOTAGE CALCULATION
 SQ.FT. BEING ADDED DOES NOT MATCH
 APPLICATION WITH PRINTS.!!!!!
 NOTE:SERVICE GROUNDING ELECTRODE SYSTEM.
 NOTE:NEED FAULT CURRENT CACULATIONS
 FOR AIC RATING.215-5
 NOTE:NEED NEUTRAL COND. FROM METERCAN
 TO DISC.TO PANEL.
 NOTE:REQ`MENTS FOR KITCHEN RECEPTS.
 210-8-A-6/210-52C-1-2-3-4-5
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.
 NOTE:REQ`MENTS FOR OUTLET SPACING 210-52

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-07-18 Cont ID  
Sent By cthirben Date 2000-07-18 Time 08:46 Rev Time 1.00
Received By cthirben Date 2000-07-18 Time 08:46 Sent To  
Notes
2001-01-08 00:00:00NOTES:
 RELOCATE AHU IN STORAGE AREA.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-10-19 Cont ID  
Sent By jleech Date 1999-10-19 Time 08:52 Rev Time 0.50
Received By jleech Date 1999-10-19 Time 08:52 Sent To  
Notes
2001-01-08 00:00:00NO ENERGY CALKS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 1999-06-07 Cont ID  
Sent By ndenmark Date 1999-06-07 Time 15:04 Rev Time 0.25
Received By ndenmark Date 1999-06-07 Time 15:04 Sent To  
Notes
2001-01-08 00:00:00****************DENIED******************
 NO A/C PLANS INCLUDED SUBMIT PLANS FOR
 REVIEW

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-06-05 Cont ID  
Sent By fknapp Date 1999-10-18 Time 07:36 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 1999-11-23 Cont ID  
Sent By fknapp Date 1999-11-23 Time 10:24 Rev Time 3.00
Received By fknapp Date 1999-11-22 Time 11:44 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR:
 DOUBLE FRONT DOORS WITH SIDELITES
 MIAMI SLIDE DOOR
  
 PLEASE SUBMIT PRIOR TO INSTALLATION
  
 2)PROVIDE PRODUCT APPROVALS FOR STORM
 PANELS WITH INSTALLATION SCHEDULE AND
 KEY PLAN WITH SPECIFIC MOUNTING TO BE
 USED UNDER SEPERATE PERMIT.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 1999-10-18 Cont ID  
Sent By fknapp Date 1999-10-18 Time 06:46 Rev Time 2.00
Received By fknapp Date 1999-10-18 Time 06:46 Sent To E
Notes
2001-01-08 00:00:00DENIED:
  
 1)PROVIDE ENERGY CALCULATIONS INCLUDING
 MANUEL J.
  
 2)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVAL FOR:
 NEW EXTERIOR DOORS
 ROOF COVERING
 UL APPROVED FIREPLACE
  
 3)PROVIDE ELEVATIONS OF EXISTING BUILD-
 ING FOR REVIEW TO CALCULATE TABLE 600.
  
 4)PROVIDE SOIL TEST REPORT.
  
 5)PROVIDE HURRICANE MISSILE IMPACT
 PROTECTION INFORMATION.
  
 6)PROVIDE WINDOW AND DOOR BUCK DETAIL
 FOR WINDLOAD RESISTANCE.
  
 7)PROVIDE RAISED SEAL ON PLANS.
  
 8)PROVIDE DETAIL OF CONNECTION FROM NEW
 WALLS TO EXISTING WALLS.
  
 SBC 104.2.2
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO., THE PERMIT PLANS STAMPED BY
 THEM AND THE PINK RECIEPT ATTACHED TO
 THE PERMIT APPLICATION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 1999-07-02 Cont ID  
Sent By fknapp Date 1999-07-02 Time 14:58 Rev Time 0.00
Received By fknapp Date 1999-07-01 Time 17:19 Sent To  
Notes
2001-01-08 00:00:00DENIED SEECHECKLIST

Review Stop Z ZONING
Rev No 1 Status P Date 1999-05-13 Cont ID  
Sent By gjoyce Date 1999-05-05 Time 11:22 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***