| Plan Review Stops For Permit 99050128 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2000-07-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-17 |
Time |
17:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-17 |
Time |
17:24 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** PROVISO ************** | | | | | | 1)NOTE: PLEASE PROVDED A REVISED PANEL | | | SHEDULE BEFORE FINAL ELECTRICAL INSPEC. | | | IS CALLD IN, IF THERE ARE ANY QUESTIONS] | | | PLEASE CALL 659-8096 EXT 8272 | | | | | | ALSO,ADDITION ELECTRODE TO BOND COLD | | | WATER PIPE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
1999-11-18 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
1999-11-18 |
Time |
13:30 |
Rev Time |
1.00 |
| Received By |
jleahy |
Date |
1999-11-18 |
Time |
13:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
1999-10-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
1999-10-18 |
Time |
19:47 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
1999-11-18 |
Time |
13:22 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************DENIED******************** | | | | | | | | | 1)NOTE:AS PER ART:215-5 PANEL SCHEDULE | | | TO SHOW BOTH A/C UNITS AND TO SHOW BATH | | | GFI CIRCUT WHICH IS REQ`D BY ART:210-52D | | | 2)NOTE:AS PER ARTS:110-9/215-5 NEED TO | | | SHOW AIC RATING OF MAINS AND BRANCH | | | BREAKERS. AIC RATING IS FIGURED FROM | | | FAULT CURRENT CALCULATIONS. | | | 3)NOTE:AS PER ART:250-81 NED TO SHOW | | | GROUNDING ELECTRODE CONDUCTOR GOING TO | | | BLDG. STEEL OF NEW ADDITION AND TO GRND. | | | ROD. | | | 4)NOTE:AS PER ART;215-5 PLEASE GIVE | | | BETTER DISCRIPTION OF RISER DIAGRAM | | | PERTAINING TO 2ND.METER AND 100 AMP | | | PANEL.???? | | | 5)NOTE:AS PER 1996 NFPA-72 SMOKE | | | DETECTORS NEED TO BE IN AREA OUTSIDE | | | BEDROOM.SEE PLANS RELOCATING 1 SMOKE DEC | | | INTO HALL FROM LIVING ROOM. ALSO OTHER | | | TWO SMOKE DETECTOR THAT ARE CIRCLED ARE | | | NOT REQ`D BUT ARE ALLOWED TO BE | | | INSTALLED. | | | 6)NOTE:AS PER ART:210-8-A-6 ALL OUTLETS | | | SERVING KITCHEN COUNTER SPACE ARE TO BE | | | GFI/GFI PROTECTED. | | | 7)NOTE;AS PER ART:210-52-C-3 REQ`MENTS | | | FOR OUTLET SPACING ON PENINSULAR. | | | 8)NOTE:AS PER ART:210-52 OUTLET SPACING | | | INSIDE BEDROOM AS REQ`D FOR THE 2`6`12` | | | RULE. | | | | | | PLEASE HAVE ALL THE ABOVE SUBMITTED FOR | | | REVIEW AND APPROVAL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
1999-06-07 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
1999-06-07 |
Time |
07:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***********DENIED********************** | | | | | | NEED COMPLETE SQUARE FOOTAGE CALCULATION | | | SQ.FT. BEING ADDED DOES NOT MATCH | | | APPLICATION WITH PRINTS.!!!!! | | | NOTE:SERVICE GROUNDING ELECTRODE SYSTEM. | | | NOTE:NEED FAULT CURRENT CACULATIONS | | | FOR AIC RATING.215-5 | | | NOTE:NEED NEUTRAL COND. FROM METERCAN | | | TO DISC.TO PANEL. | | | NOTE:REQ`MENTS FOR KITCHEN RECEPTS. | | | 210-8-A-6/210-52C-1-2-3-4-5 | | | NOTE:SMOKE DETECTORS REQ`D INSIDE AND | | | OUTSIDE BEDROOMS. | | | NOTE:REQ`MENTS FOR OUTLET SPACING 210-52 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-07-18 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-18 |
Time |
08:46 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-07-18 |
Time |
08:46 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NOTES: | | | RELOCATE AHU IN STORAGE AREA. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
1999-10-19 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
1999-10-19 |
Time |
08:52 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
1999-10-19 |
Time |
08:52 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NO ENERGY CALKS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
1999-06-07 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-06-07 |
Time |
15:04 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
1999-06-07 |
Time |
15:04 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ****************DENIED****************** | | | NO A/C PLANS INCLUDED SUBMIT PLANS FOR | | | REVIEW |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
1999-06-05 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
1999-10-18 |
Time |
07:36 |
Rev Time |
0.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
P |
Date |
1999-11-23 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
1999-11-23 |
Time |
10:24 |
Rev Time |
3.00 |
| Received By |
fknapp |
Date |
1999-11-22 |
Time |
11:44 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************PROVISO****************** | | | | | | SBC 104.2.2 | | | | | | 1)PROVIDE 2 CURRENT COPIES OF PRODUCT | | | APPROVALS FOR: | | | DOUBLE FRONT DOORS WITH SIDELITES | | | MIAMI SLIDE DOOR | | | | | | PLEASE SUBMIT PRIOR TO INSTALLATION | | | | | | 2)PROVIDE PRODUCT APPROVALS FOR STORM | | | PANELS WITH INSTALLATION SCHEDULE AND | | | KEY PLAN WITH SPECIFIC MOUNTING TO BE | | | USED UNDER SEPERATE PERMIT. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
1999-10-18 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
1999-10-18 |
Time |
06:46 |
Rev Time |
2.00 |
| Received By |
fknapp |
Date |
1999-10-18 |
Time |
06:46 |
Sent To |
E |
|
| Notes |
| 2001-01-08 00:00:00 | DENIED: | | | | | | 1)PROVIDE ENERGY CALCULATIONS INCLUDING | | | MANUEL J. | | | | | | 2)PROVIDE 2 CURRENT COPIES OF PRODUCT | | | APPROVAL FOR: | | | NEW EXTERIOR DOORS | | | ROOF COVERING | | | UL APPROVED FIREPLACE | | | | | | 3)PROVIDE ELEVATIONS OF EXISTING BUILD- | | | ING FOR REVIEW TO CALCULATE TABLE 600. | | | | | | 4)PROVIDE SOIL TEST REPORT. | | | | | | 5)PROVIDE HURRICANE MISSILE IMPACT | | | PROTECTION INFORMATION. | | | | | | 6)PROVIDE WINDOW AND DOOR BUCK DETAIL | | | FOR WINDLOAD RESISTANCE. | | | | | | 7)PROVIDE RAISED SEAL ON PLANS. | | | | | | 8)PROVIDE DETAIL OF CONNECTION FROM NEW | | | WALLS TO EXISTING WALLS. | | | | | | SBC 104.2.2 | | | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH CO., THE PERMIT PLANS STAMPED BY | | | THEM AND THE PINK RECIEPT ATTACHED TO | | | THE PERMIT APPLICATION. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
1999-07-02 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
1999-07-02 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
fknapp |
Date |
1999-07-01 |
Time |
17:19 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED SEECHECKLIST |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
1999-05-13 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
1999-05-05 |
Time |
11:22 |
Rev Time |
|
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|