Plan Review Details - Permit 99050121
Plan Review Stops For Permit 99050121
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-06-11 Cont ID  
Sent By dpalmer Date 1999-06-11 Time 17:21 Rev Time 0.00
Received By dpalmer Date 1999-06-11 Time 17:21 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
  
 NEED PLANS TO SHOW AIC RATING ON PANEL
 SCHD.215-5
  
 NEED BEFORE ROUGH INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-07-08 Cont ID  
Sent By ndenmark Date 1999-07-08 Time 07:00 Rev Time 0.25
Received By ndenmark Date 1999-07-08 Time 07:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-07-07 Cont ID  
Sent By tlarge Date 1999-07-07 Time 15:36 Rev Time 0.33
Received By tlarge Date 1999-07-07 Time 15:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 1999-06-26 Cont ID  
Sent By tlarge Date 1999-06-26 Time 11:53 Rev Time 0.25
Received By tlarge Date 1999-06-26 Time 11:53 Sent To  
Notes
2001-01-08 00:00:00FIXTURES DOWNSTREAM OF W.C.'S SHALL BE
 VENTED PER SPC 913.2.
  
 CLARIFY TYPE OF VENT ON KIT.SINK.(CODE
 DOESN'T ADDRESS "ISLAND STUDOR VENT.")

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-06-15 Cont ID  
Sent By tlarge Date 1999-06-15 Time 17:46 Rev Time 0.00
Received By tlarge Date 1999-06-15 Time 17:45 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SANITARY RISER FOR REVIEW. SPC
 SEC.104.2.1.
  
 SUBMIT GAS DRAWING THAT CLEARLY REFLECTS
 ENTIRE SCOPE OF WORK TO BE PERFORMED.
 COMPLY W/STANDARD GAS CODE SEC.302.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 1999-09-24 Cont ID  
Sent By jgomez Date 1999-09-24 Time 10:29 Rev Time 0.50
Received By jgomez Date   Time   Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-FOOTING F1 WAS NOT REVISED. SOIL TEST
 REPORT REQUIRED A FOOTING WIDTH OF 18"
 TO 34".
 2-CONNECTION OF A GARAGE WITH ANY ROOM
 WITH A GAS APPLIANCE SHALL BE BY MEANS
 OF A DOORWAY WITH A RAISED SILL AT
 LEAST 8" ABOVE THE GARAGE FLOOR.
 SECTION 411.2.7 SBC 1994.
 DRAWINGS NOT REVISED.
 3-PROVIDE SPECIFICATIONS TO COMPLY WITH
 SECTION 402.7 SGC 1994 FOR INSTALLATION
 OF GAS APPLIANCES IN GARAGE.
 DRAWINGS NOT REVISED.
 4-ENTRY DOORS TO BE 32" MINIMUM CLEAR.
 TABLE 1004 SBC 1994. DWGS NOT REVISED.
 5-SPECIFY SIZE OF CEILINGS FANS AS PER
 TABLE 6-6 OF FLORIDA ENERGY CODE 1997.
 AND AS PER CREDIT TAKEN IN ENERGY CALCS
 DRAWINGS NOT REVISED.
 6-REVISE SPECIFICATION FOR INSULATION IN
 ATTIC. IT SHOULD BE R-30 AS PER ENERGY
 CALCULATIONS.SEE SHEET A-5, SECTION AA.
 7-PROVIDE CONNECTION DETAIL. SEE SHEET
 A-6 FOR COMMENTS. DRAWINGS NOT REVISED.
 8-SEE COMMENTS ON ALL PLANS.
  
 NOTE:
 PLEASE CLOUD ALL REVISIONS IN ORDER TO
 EXPEDITE THE REVIEW PROCESS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-07-12 Cont ID  
Sent By jgomez Date 1999-07-12 Time 14:02 Rev Time 2.00
Received By jgomez Date 1999-07-12 Time 14:02 Sent To O
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO

Review Stop Z ZONING
Rev No 1 Status P Date 1999-05-11 Cont ID  
Sent By gjoyce Date 1999-05-11 Time 11:32 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***