Plan Review Details - Permit 99050115
Plan Review Stops For Permit 99050115
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-06-11 Cont ID  
Sent By dpalmer Date 1999-06-11 Time 14:32 Rev Time 0.00
Received By dpalmer Date 1999-06-11 Time 14:32 Sent To  
Notes
2001-01-08 00:00:00*************PROVISO********************
  
 NEED TO SUBMIT FAULT CURRENT CALCS.
 FOR AIC RATING WHICH NEEDS TO BE LISTED
 ON PANEL SCHD.215-5
 NOTE:EQUIPMENT GROUNDING COND.REQ`D
 FROM MAIN DISC. TO PANEL.
  
 NEED BEFORE ROUGH INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-06-12 Cont ID  
Sent By jleech Date 1999-06-12 Time 13:16 Rev Time 0.50
Received By jleech Date 1999-06-12 Time 13:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-06-12 Cont ID  
Sent By jleech Date 1999-06-12 Time 13:16 Rev Time 0.50
Received By jleech Date 1999-06-12 Time 13:16 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-07-09 Cont ID  
Sent By bstaples Date 1999-07-09 Time 16:07 Rev Time 1.75
Received By bstaples Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-05-05 Cont ID  
Sent By gjoyce Date 1999-05-05 Time 17:24 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***